Single-Function Safety Relays

Catalogs > Safety Products Catalog > Logic > Safety Relays > Single-Function Safety Relays > MSR9T

MSR9T

Introduction Specifications Product Selection Accessories Approximate Dimensions Typical Wiring Diagrams Application Details
Click to enlarge - 440R-F23027-8_Product


Description

The MSR9T has one normally closed and one normally open dual-channel input for use with gate interlocks and emergency stop buttons in higher risk applications. The MSR9T is typically used for gate interlocks incorporating the diversity of one positive opening and one non-positive opening interlock.

The MSR9T has output monitoring that can accommodate an automatic/manual reset. Automatic/manual reset can use a jumper or can be used to check operation of the contacts.

The MSR9T has two normally open safety outputs and one normally closed auxiliary output. The safety outputs have independent and redundant internal contacts to support the safety function. The auxiliary contact is a nonsafety output intended to provide an external signal about the status of the safety outputs.


Features


LED Indicators

Green Power On
Green Output On