MSR18T

Click to enlarge - 440R-ZBR520AZ1-2_Product


Description

The Minotaur MSR18T is a monitoring safety relay unit with dual channel input, 5 safety outputs and 2 auxiliary outputs. It is designed for operation as E-Stop, safety gate applications, and 2-hand control applications.

The MSR18T is a versatile unit with extensive diagnostics. It can be used with E-Stop buttons, gate interlocks, two-hand controls as well as expansion relays when additional inputs are needed.

When used in a suitably configured circuit, the MSR18T provides additional safety rated output circuits with checking and monitoring of its status. Safety critical faults or power failures will cause them to initiate a lock-out to a safe state.


Features


LED Indicators

Red Input Short
Green Power
Green Run
Red Input Fault
Red Output Fault
  

Specifications

Safety Ratings
Standards EN 954-1, ISO13849-1, IEC/EN 60204-1, IEC 60947-5-1, ANSI B11.19, AS4024.1, EN 574
Safety Classification Cat. 4 per EN 954-1 (ISO 13849-1)
Functional Safety Data ⋆ 
Note: For up-to-date information, visit http://www.ab.com/safety/
PFHD: < 2.5 x 10-9
MTTFd: > 45662 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus & TÜV
Power Supply
Input Power Entry
Power Consumption 3.6 W @ 24V AC/DC
6.1 VA, 5.7 W @ 120V/240V AC
Inputs
Safety Inputs 1 N.C. or 1 N.C. & 1 N.O. or 2 N.C.
Input Simultaneity 0.5 seconds
Input Resistance, Max. 100 W
Reset
Power On Delay/Recovery Time /
Response Time
Outputs
Safety Contacts  
Auxiliary Contacts  
Thermal CurrentIlth 1 x 8 A, 2 x 7 A, 3 x 5.5 A, 4 x 5 A, or 5 x 4.5 A (nonswitching)
Rated Impulse withstand VoltageIlth 3000V
Switching Current @ Voltage, Min. 20 mA @ 24V AC/DC
Fuses, Output (External) 1.6 slow blow (external)
Electrical Life (Operations) 220V AC/4A/880VA cosf = 0.35 - 100,000 operations
220V AC/1.7A/375VA cosf = 0.6 - 500,000 operations
30V DC/2A/60W - 1,000,000 operations
10V DC/0.01A/0.1W - 2,000,000 operations
Mechanical Life 5,000,000 operations
Utilization Category
C300/AC-15 0.75 A @ 250V AC 1.5 A @ 120V AC
Q300/DC-13 2 A @ 24V DC  
Environmental
Enclosure Type Rating/
Terminal Protection
/
IP20, DIN 0470
Operating Temperature [C (F)] -25…55° (-13…131°)
Vibration 0.75 mm (0.30 in.) peak, 10…55 Hz
Shock 5 g, 11 ms half-sine
Physical Characteristics
Mounting 35 mm DIN Rail
Weight [g (lb)]
Conductor Size, Max.
 
⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Power cycled once per 8 hrs

Product Selection

Inputs Safety Outputs Auxiliary Outputs Terminals Reset Type Power Supply Cat. No.
1 N.C., 1 N.C. & 1 N.O., 2 N.C. 5 N.O. 2 N.C. Fixed Automatic/Manual or Monitored/Manual 24V AC/DC and 120V AC 440R-ZBR520AZ1
24V AC/DC and 240V AC 440R-ZBR520AZ2
  

Approximate Dimensions

Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.

Click to enlarge - 440R-ZBR520AZ#_Dim2

Block Diagram

Click to enlarge - 440R-ZBR520AZ#_Block Diagram

Typical Wiring Diagrams

Click to enlarge - 440R-ZBR520AZ#_Wiring 01      Click to enlarge - 440R-ZBR520AZ#_Wiring 02
     
Single-Channel Input, Monitored Manual Reset,
Single-Channel Output, Monitored Output
  Dual-Channel Input 1 N.O. & 1 N.C., Automatic Reset,
Dual-Channel Output, No Monitored Outputs

Click to enlarge - 440R-ZBR520AZ#_Wiring 03   Click to enlarge - 440R-ZBR520AZ#_Wiring 04
     
Two-Hand Control, Automatic Reset,
Dual-Channel Output, No Monitored Output
  Dual-Channel (2 N.C.), Monitored Manual Reset,
Dual-Channel Output, Monitored Output
Note: EN 574 Cat. 3B