MSR121RT

Click to enlarge - 440R-J23099-102_Product


Description

The Allen-Bradley Guardmaster Minotaur MSR121RT is a safety monitoring relay that provides three normally open safety contacts, a normally open auxiliary contact and a solid state auxiliary output for use with interfacing to PLCs.

The MSR121RT has a versatile input arrangement. It can be connected to a single or dual channel safety gate or e-stop, a safety mat input or a light curtain that provides cross fault detection.

Reset and output monitoring is determined by the wiring configuration. Automatic/manual reset can use a jumper or can be used to check operation of external contactors. Monitored manual requires the use of a manually operated normally open momentary switch.

The MSR121RT has 3 normally open safety rated outputs. The safety outputs have independent and redundant internal contacts to help ensure the safety function. It has one normally closed auxiliary output as well as a solid state PNP auxiliary output to indicate the status of the MSR121RT to a indicator lamp or a PLC.


Features


Click to enlarge - 440R-J23#_Curve


LED Indicators

Green Power On
Green Output On
  

Specifications

Safety Ratings
Standards EN 954-1, ISO13849-1, IEC/EN 60204-1, IEC 60947-5-1, ANSI B11.19, AS4024.1
Safety Classification Cat. 3 per EN 954-1 (ISO 13849-1)
Functional Safety Data ⋆ 
Note: For up-to-date information, visit http://www.ab.com/safety
PFHD: < 2.5 x 10-9
MTTFd: > 45662 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus, and c-Tick
Power Supply
Input Power Entry 24V AC/DC, 115/230V AC, 50/60 Hz
Power Consumption <4V A
Inputs
Safety Inputs 1 N.C. & 1 N.O.
Input Simultaneity 0.5 seconds
Input Resistance, Max. 500 W
Reset Auto./Manual
Power On Delay/Recovery Time /
Response Time 50 ms
Outputs
Safety Contacts  
Auxiliary Contacts  
Thermal CurrentIlth 4 A (nonswitching)
Rated Impulse withstand VoltageIlth 2500V
Switching Current @ Voltage, Min. 10 mA @ 10V
Fuses, Output (External) 5 A quick acting (external)
Electrical Life (Operations) 220V AC/4A/880VA cosf = 0.35…0.1 M
220V AC/1.7A/375VA cosf = 0.6…0.5 M
30V DC/2A/60W = 1 M
10V DC/0.01A/0.1W = 2 M
Mechanical Life 2,000,000 operations
Utilization Category
A600/AC-15 (Ue) 600V 500V 240V 120V
  (le) 1.2 A 1.4 A 3 A 6 A
N600/DC-13 (Ue) 600V 500V 250V 120V
  (le) 0.4 A 0.55 A 1.1 A 2.2 A
Environmental
Enclosure Type Rating/
Terminal Protection
IP40 (NEMA 1), DIN 0470/
IP20, DIN 0470
Operating Temperature [C (F)] -10…+55 ° (14…131 °)
Vibration 0.75 mm (0.30 in.) peak, 10…55 Hz
Shock 30 g, 11 ms half-sine
Physical Characteristics
Mounting 35 mm DIN Rail
Weight [g (lb)] 210 (0.46)
Conductor Size, Max. 1 x 2.5 mm2 (14 AWG) stranded, 1 x 4 mm2 (12 AWG) solid
 
⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Power cycled once per 8 hrs

Product Selection

Inputs Safety Outputs Auxiliary Outputs Power Supply Cat. No.
1 N.C., 2 N.C., LC or SM 3 N.O. 1 N.C. and 1 PNP Solid State 24V AC/DC 440R-J23102
115V AC 440R-J23100
230V AC 440R-J23099
  

Approximate Dimensions

Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.

Click to enlarge - 440R-J23#_Dim

Block Diagram

Click to enlarge - 440R-J23#_Block Diagram

Typical Wiring Diagrams

Click to enlarge - 440R-J23#_Wiring 01      Click to enlarge - 440R-J23#_Wiring 02
 
24V DC Light Curtain 115/230V AC Safety Relay, Monitored Manual Reset, Monitored Output      Safety Mat Monitored Manual Reset, Monitored Output
 
Click to enlarge - 440R-J23#_Wiring 03      Click to enlarge - 440R-J23#_Wiring 04
 
Dual Channel E-Stop, Monitored Manual Reset, Monitored Output      Single Channel Safety Gate, Automatic Reset, No Output Monitoring