MSR117T

Click to enlarge - 440R-B23211_Product_4C


Description

The MSR117T has one normally closed single-channel input for use with gate interlocks and emergency stop buttons in lower risk applications. The MSR117T has output monitoring that can accommodate an automatic/manual reset function. Automatic/manual reset can use a jumper or can be used to check operation of the contacts.

The MSR117T has three normally open safety outputs and one normally closed auxiliary output. The safety outputs have independent and redundant internal contacts to help ensure the safety function. The auxiliary contact is a nonsafety output intended to provide an external signal about the status of the safety outputs.

The MSR117T can be activated via the terminals A1-A2 and the feedback/reset loop X1-X2. Then the safety outputs 13-14, 23-24 and 33-34 close and enable operation.


Features


Click to enlarge - 440R-B23211_Application 01

Specifications

Safety Ratings
Standards IEC/EN 60204-1, ISO 12100, ISO 13849-1 (EN 954-1)
Safety Classification Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1
Functional Safety Data ⋆ 
Note: For up-to-date information, visit http://www.ab.com/safety/
PFHD: < 2.53 x 10-9
MTTFd: > 425 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus, and TÜV
Power Supply
Input Power Entry 24V AC/DC
Power Consumption 2 W
Inputs
Safety Inputs 1 N.C.
Input Resistance, Max. 25 ohms
Reset Auto./Manual or Monitored Manual
Power On Delay/
Recovery Time
1 sec/110 ms
Response Time 30 ms
Outputs
Safety Contacts 3 N.O.
Auxiliary Contacts 1 N.C.
Thermal CurrentIlth 2 x 5 A or 3 x 4 A
Rated Impulse withstand Voltage 2500V
Switching Current @ Voltage, Min. 10 mA @ 10V
Fuses, Output 6 A slow blow or 10 A quick blow (external)
Electrical Life 230V AC/4 A/880V A cosf=0.35…0.1 M
230V AC/1.7 A/375V A cosf=0.6…0.5 M

30V DC/2 A/60 = 1 M
10V DC/0.01 A/0.1 W = 2 M
Mechanical Life 2,000,000 cycles
Environmental and Physical Characteristics
Enclosure Type Rating/
Terminal Protection
IP40 (NEMA 1), DIN 0470/
IP20, DIN 0470
Operating Temperature [C (F)] -5…+55 ° (23…131 °)
Vibration 10…55 Hz, 0.35 mm
Shock 10 g, 16 ms 100 shocks
Mounting 35 mm DIN Rail
Weight [g (lb)] 180 (0.37)
Conductor Size, Max. 0.2…4 mm2 (24…12 AWG) wire size only
 
⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period

Product Selection

Inputs Safety Outputs Auxiliary Outputs Terminals Reset Type Power Supply Cat. No.
1 N.C. 3 N.O. 1 N.C. Fixed Auto./Manual or Monitored Manual 24V AC/DC 440R-B23211
  

Approximate Dimensions

Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.

Click to enlarge - 440R-B23211_Dims

Connections

Click to enlarge - 440R-B23211_Connect

Block Diagram

Click to enlarge - 440R-B23211_Block Diagram

Typical Wiring Diagrams

Click to enlarge - MSR 117 Wiring