MSR38D/DP
|
Description
The Minotaur MSR38D/DP is a microprocessor-based, monitoring safety relay, with delayed, safety-rated, solid-state outputs.
The inputs of the MSR38D/DP are the same as the MSR30. They can be connected to gate interlocks, e-stop devices or four-wire safety mats. The gate interlocks and e-stops can be either single channel or dual channel normally-closed circuits.
The reset capability of the MSR38D/DP allows it to set up for monitored manual or automatic/manual reset.
The outputs include two delayed normally-open safety rated outputs that can be connected to loads up to 2 A at 24V DC. These outputs can be used to send a safety stop signal to a machine or manufacturing system. The delay is accomplished by the configuration of jumpers on the terminals. The delay can be easily adjusted by reconfiguring the jumpers.
The MSR38D/DP also has one solid-state normally-closed auxiliary output, which must only be used to indicate the status of the MSR38D/DP. The auxiliary output responds immediately to the change in input status; it is not delayed.
Features
- Category 4 per EN 954-1
- Stop Category 0 or 1
- Two delayed solid-state safety outputs
- One solid-state auxiliary output
- One N.C., two N.C. or safety mat input
- Monitored manual or automatic/manual reset
LED Indicators
| Green | Power (Pwr) |
| Green | K1 Closed |
| Green | K2 Closed |
Specifications
| Safety Ratings | |
| Standards | EN 954-1, ISO 13849-1, IEC/EN 60204-1, ANSI B11.19, AS4024.1 |
| Safety Classification | Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1 |
| Functional Safety Data ⋆ Note: For up-to-date information, visit http://www.ab.com/safety/ |
PFHD: < 9.2 x 10-10 MTTFd: > 631 years Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics |
| Certifications | CE Marked for all applicable directives, cULus, c-Tick, and TÜV |
| Power Supply | |
| Input Power Entry | 24V DC SELV |
| Power Consumption | 3 W |
| Inputs | |
| Safety Inputs | 1 N.C. or 2 N.C. or SM |
| Input Resistance, Max. | 200 W |
| Reset | Auto./Manual or Monitored Manual |
| Power On Delay/ Recovery Time |
3 seconds/20 ms |
| Response Time | 15 ms |
| Outputs | |
| Safety Contacts | 2 N.O. SS, 2 A @ 24V DC |
| Auxiliary Contacts | 1 N.O. SS, 50 mA @ 24V DC |
| Fuses, Output | External 6 A slow blow or 10 A fast acting |
| Power LED Diagnostics | 3 s Blink: Initialization Constant: Normal Operation 2 Blinks: Configuration change during operation 4 Blinks: Solid state output switch fault 5 Blinks: Reset switch closed after reset Continuous blinking: Internal fault |
| Environmental and Physical Characteristics | |
| Enclosure Type Rating/ Terminal Protection |
IP40 (NEMA 1), DIN 0470/ IP20, DIN 0470 |
| Operating Temperature [C (F)] | -5…+55 ° (23…131 °) |
| Vibration | 10…55 Hz, 0.35 mm |
| Shock | 10 g, 16 ms, 100 shocks |
| Mounting | 35 mm DIN Rail |
| Weight [g (lb)] | 130 (0.287) |
| Conductor Size, Max. | 0.2…2.5 mm2 (24…14 AWG) |
| ⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions: - Mission time/Proof test interval of 20 years |
|
Wiring Terminations
| S11 & S21 | Pulse train output |
| S12 & S22 | Input contacts |
| A1 S34 | Reset switch |
| S11 S34 | Automatic reset, start-up test disabled |
| S21 S34 | Automatic reset, start-up test enabled |
| A1 Y2 | Monitoring circuit |
| A1 Y41 | Cross-fault monitoring disabled |
Product Selection
| Inputs | Delayed Safety Outputs |
Instantaneous Auxiliary Outputs |
Terminals | Reset Type | Power Supply | Cat. No. |
| 1 N.C., 2 N.C., Safety Mat | 2 N.O. Solid State | 1 N.O. Solid State | Fixed | Auto./Manual or Monitored Manual | 24V DC SELV | 440R-M23203 |
| Removable | 440R-M23204 | |||||
Accessories
| Description | Cat. No. |
| Bag of 4, 4-Pin Screw Terminal Blocks | 440R-A23209 |
| Bag of 4, 4-Pin Spring Clamp Terminal Blocks | 440R-A23228 |
Approximate Dimensions
Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.
|
Block Diagram
|
Typical Wiring Diagrams
See MSR30 on page Description for additional input wiring configurations.
|
|
|
| Dual Channel E-Stop, Dual Channel Delayed Outputs, Monitored Manual Reset, Output Monitoring |
Single Channel Gate Interlock, Single Channel Delayed Output, Automatic Reset, No Output Monitoring |
|
Apply jumpers (links) on the terminals identified to achieve the desired off delay.
| Delay(s) | Y11 | Y12 | Y13 | Delay(s) | Y11 | Y12 | Y13 | Delay(s) | Y11 | Y12 | Y13 |
| 0 | — | — | — | 8 | S21 | S11 | — | 50 | — | S21 | S21 |
| 0.5 | S11 | — | — | 10 | — | S11 | S21 | 60 | S11 | S11 | S11 |
| 1 | — | S11 | — | 12 | S21 | — | S11 | 80 | S11 | S11 | S21 |
| 1.5 | — | — | S11 | 15 | — | S21 | S11 | 100 | S11 | S21 | S11 |
| 2 | S21 | — | — | 18 | S11 | S11 | — | 120 | S11 | S21 | S21 |
| 3 | — | S21 | — | 21 | S11 | — | S11 | 160 | S21 | S11 | S11 |
| 4 | — | — | S21 | 26 | — | S11 | S11 | 200 | S21 | S11 | S21 |
| 5 | S11 | S21 | — | 30 | S21 | S21 | — | 250 | S21 | S21 | S11 |
| 6 | S11 | — | S21 | 40 | S21 | — | S21 | 300 | S21 | S21 | S21 |