Delayed Outputs

Catalogs > Safety Products Catalog > Logic > Safety Relays > Single-Function Safety Relays > Delayed Outputs > MSR138DP

MSR138DP

Introduction Specifications Product Selection Accessories Approximate Dimensions Block Diagram Typical Wiring Diagrams
Click to enlarge - 440R-M23##_MSR138_4C


Description

The MSR138DP can be connected in 3 different input wiring configurations: 1 normally closed, 2 normally closed, or 2 OSSD. When connected in the two normally closed fashion, the MSR138DP checks for cross faults across the two inputs. When connected to light curtains, the light curtain must perform the cross-fault detection.

The MSR138DP has output monitoring that can accommodate either automatic/manual reset or a monitored manual reset. When configured with automatic/manual reset (jumpers on X1-X2 and X3-X4), the MSR138DP can have the reset terminals S33-S34 jumpered or can be converted to an unmonitored manual reset by adding a normally open switch in the monitoring loop (S33-S34). When configured to monitored manual reset, the MSR138DP checks the output monitoring circuit through the manual application of the reset switch. The unit cannot be reset until the timing function has completed.

The outputs of the MSR138DP include two normally open immediate safety outputs and three normally open delayed safety outputs. The outputs of the MSR138.1DP include two normally open immediate safety rated outputs, two normally open delayed safety outputs and one normally closed delayed safety output. The safety outputs have independent and redundant internal contacts to support the safety function. If a reset request is made during the time cycle, it will cause a lockout condition. Cycle inputs after timing has completed and reset after the delay time has expired to clear lockout. Connecting contacts 55-56 of the MSR138.1DP in series to Y1-Y2 can avoid this lockout.

A normally closed timer reset switch can be added to force the delayed contacts open prior to the completion of the timing cycle.


Features


LED Indicators

Green Power—Illuminates when power on
Green Start—Illuminates when S33-S34 is closed
Green CH1 IN—Illuminates when channel 1 input is closed
Green CH2 IN—Illuminates when channel 2 input is closed
Green CH1—Illuminates when K1 is closed
Green CH2—Illuminates when K2 is closed
Green CHT1—Illuminates during timing period
Green CHT2—Illuminates during timing period