Safedge™ Controllers

Click to enlarge - 440F-Safedge_Controllers_Product


Description

The Safedge controllers are designed to operate with the Safedge profiles. The controller continuously monitors the profile for actuation and generates an output signal when the profile is depressed.

The Safedge controller provides a low voltage to the profile. When the profile is pressed, the controller detects a change in resistance and turns off its output relays. When pressure is released from the profile, the output relays of the controller return to an on state. The controller has redundant voltage free positively-guided output relays, which can be used to interface with a machine control system.

The 251 controller comes capable of operating at 24V AC/DC, or 120/230V AC from separate terminals. An internal switch changes the operating voltage from 120V AC to 230V AC. The 252 controller operates at 24V AC/DC.

An auxiliary output relay is available to provide a signal about the controller’s status. Three LEDs indicate whether the controller is in RUN, STOP or OPEN condition. The controller operates in manual or automatic reset mode.


Features


LED Indicators

Green Run
Yellow Open Circuit
Red Stop
  

Specifications

Safety Ratings
Standards EN1760-2, EN954-1, ISO 13849-1, AS 4024.5, EN 954-1, ANSI B11.19
Safety Classification Cat. 3 per EN 954-1
Certifications CE Marked for all applicable directives, cULus, and TÜV
Power Supply
Input Power Entry 251: 24V AC/DC or 115/230V AC 50/60 Hz; 252: 24V AC/DC 50/60 Hz
Power Consumption 251: < 6 VA
252: < 4 VA
Inputs
Safety Inputs Profile: 6 kW, 12V DC open circuit, 4V DC run condition
Monitoring: 1 N.O.
Response Time 13 ms, max.
Outputs
Safety Contacts 251: 2 N.O.; 252: 1 N.O.
Auxiliary Contacts 1 N.C.
Rated Impulse withstand Voltage 2500V
Switching Current @ Voltage, Min. 10 mA @ 10V
Fuses, Output 4 A on AC, 2 A on DC (external)
Electrical Life (Operations) 220V AC/4 A/880VA cosf = 0.3… 0.1 M
220V AC/1.7 A375VA cosf = 0.6…0.5 M
30V DC/2 A/60 W = 1 M
10V DC/0.01 A/0.1 W = 2 M
Environmental and Physical Characteristics
Enclosure Type Rating/
Terminal Protection
251D, 252D: IP40 (NEMA 1); 251P: IP65 (NEMA 13)/
IP20 DIN 0470
Operating Temperature [C (F)] -10…55° (-14…131°)
Vibration 0.15 mm, 10…55 Hz
Shock 10 g, 11 ms, half-sine
Mounting Surface mount 35 mm or DIN Rail
Weight [g (lb)] 251D: 450 (1.0)
252D: 181 (0.4)
251P: 650 (1.4)
Conductor Size, Max. 251D, 252D: 1 x 4 mm2 (10 AWG) stranded, 1 x 4 mm2 (10 AWG) solid
251P: 1 x 1.1 mm2 (18 AWG) stranded, 1 x 1.5 mm2 (16 AWG) solid
 
⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period

Product Selection

Inputs Safety Outputs Auxiliary Outputs Terminals Reset Type Power Supply Cat. No.
Safedge 2 N.O. 1 N.C. Fixed Automatic/Manual 24V AC/DC or 115/230V AC 440F-C251D
1 N.O. 24V AC/DC 440F-C252D
2 N.O. 24V AC/DC or 115/230V AC 440F-C251P
 

Approximate Dimensions

Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.

440F-C251D 440F-C251P 440F-C252D
Click to enlarge - 440F-C251D_Dims Click to enlarge - 440F-C251P_Dims Click to enlarge - 440F-C252D_Dims

Block Diagram

Click to enlarge - 440F-C25#D_Diagram

Accessories

Description Cat. No.
500 mA fuse—Bussmann Cat. No. ETF-500 mA 440R-A31562
Fuse, 2 A—Bussmann Cat. No. ETF-2 440A-A09197
  

Typical Wiring Diagrams

Click to enlarge - 440F-C25##_1_Wiring      Click to enlarge - 440F-C25##_2_Wiring
 
Series Terminated, Safedge Input, Manual Reset,
Dual Channel Output, Monitored Output
  Series Terminated, Cascaded, Safedge Input,
Automatic Reset, Dual Channel Output, No Output Monitored
 
Click to enlarge - 440F-C25##_3_Wiring   Click to enlarge - 440F-C25##_4_Wiring
 
Parallel Terminated, Safedge Input, Manual Reset,
Dual Channel Output, Monitored Output
  Series Terminated, Safedge Input, Automatic Reset,
Single Channel Output, No Output Monitored