Back EMF Monitors

Catalogs > Safety Products Catalog > Logic > Safety Relays > Specialty Safety Relays > Back EMF Monitors > CU3

CU3

Introduction Specifications Product Selection Accessories Approximate Dimensions—mm (inches) Block Diagram Typical Wiring Diagrams
Specifications

Safety Ratings
Standards EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-5-1, ANSI B11.19, AS4024.1
Safety Classification Cat. 1 per EN 954-1
Functional Safety Data ¬ 
Note: For up-to-date information, visit http://www.ab.com/Safety/
PFHD: See website
MTTFd: See website
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE marked for all applicable directives, cULus, c-Tick, and TÜV
Power Supply
Input Power Entry 24V AC/DC, 115/230V AC
Power Consumption <4 VA
Motor Voltage 500V max.
Inputs
Safety Inputs Z1/Z2 Motor Voltage
Reset Automatic/Manual
Outputs
Safety Contacts 2 N.O.
Auxiliary Contacts 1 N.C.
Rated Impulse withstand Voltage 2500V
Switching Current @ Voltage, Min. 10 mA/10V
Fuses, Output 5 A quick acting (external)
Electrical Life (Operations) 220V AC/4 A/880VA cosf = 0.35…0.1 M
220V AC/1.7 A375VA cosf = 0.6…0.5 M
30V DC/2 A/60 W = 1 M
10V DC/0.01 A/0.1 W = 2 M
Mechanical Life 2,000,000 operations
Utilization Category
Inductive: B300: AC-15 5 A @ 250V AC 5 A @ 120V AC
Inductive: DC-13 3 A/24V DC  
Environmental and Physical Characteristics
Enclosure Type Rating/
Terminal Protection
IP40, DIN 0470/
IP20 DIN 0470
Operating Temperature [C (F)] -10…55° (14…131°)
Vibration 0.75 mm (0.30 in) peak, 10…55 Hz
Shock 30 g, 11 ms half-sine
Mounting 35 mm DIN Rail
Weight [g (lbs)] 510 (1.12)
Conductor Size, Max. 1 x 2.5 mm2 (14 AWG) stranded, 1 x 4 mm2 (12 AWG) solid
 
¬ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period