Mat Controllers

Catalogs > Safety Products Catalog > Logic > Safety Relays > Specialty Safety Relays > Mat Controllers > MatGuard™ Controllers

MatGuard™ Controllers

Introduction Specifications Product Selection Approximate Dimensions Typical Wiring Diagrams
Specifications

Safety Ratings
Standards EN1760-1, EN 954-1, ISO13849-1, IEC/EN 60204-1, ANSI RIA R15.06, ANSI B11.19, AS 4024.5
Safety Classification Cat. 3 per EN 954-1 (ISO 13849-1), SIL CL2 per EN IEC 62061, PLe per ISO 13849-1
Functional Safety Data ¬ 
Note: For up-to-date information, visit http://www.ab.com/safety/
PFHD: See website
MTTFd: See website
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus, and TÜV
Power Supply
Input Power Entry 24V AC/DC or 115/230V AC
Power Consumption 6 W, 9V A
Inputs
Safety Inputs Safety Mats
Reset Monitored Manual or Automatic/Manual
Response Time 35 ms, Mat pressed to output open
Outputs
Safety Contacts 2 N.O.
Auxiliary Contacts 1 N.C.
Switching Current @ Voltage, Min. 10 mA @ 10V
Fuses, Output 5 A fast acting (external)
Electrical Life (Operations) 220V AC/4 A/880VA cosf = 0.35…0.1 M
220V AC/1.7 A375VA cosf = 0.6…0.5 M
30V DC/2 A/60 W = 1 M
10V DC/0.01 A/0.1 W = 2 M
Mechanical Life 10,000,000 operations
Environmental and Physical Characteristics
Enclosure Type Rating/

Terminal Protection
4000P: IP65 (NEMA 13); 4000S: IP62 (NEMA 12)/
IP20, DIN 0470
Operating Temperature [C (F)] -10…+45 ° (14…113 °)
Vibration 0.15 mm, 10…55 Hz
Mounting Surface (Wall) Mount
Weight [g (lb)] 4000P: 880 (1.94); 4000S: 3200 (7.05)
Conductor Size, Max. 4000P, 4000S: 1 x 1.5 mm2 (16 AWG), max.
 
¬ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period