Timing Control Unit

Catalogs > Safety Products Catalog > Logic > Safety Relays > Timing Control Unit > CU1

CU1

Introduction Specifications Product Selection Accessories
Approximate Dimensions Block Diagram Typical Wiring Diagrams Application Details
Specifications

Standards EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-5-1, ANSI B11.19, AS4024.1
Category Cat. 1 per EN 954-1 (ISO13849-1)
Certifications
Power Supply 24V AC/DC, 115V AC, or 230V AC
Power Consumption <4 VA
Safety Inputs 1 N.O.
Input Resistance, Max. 500 W
Reset Type Automatic/Manual
Safety Outputs Delayed—3 N.O. Safety
Delayed—2 N.C. Auxiliary
Output Utilization per IEC60947-5-1 (Inductive)¬  B300, AC-15: 4 A/250V AC, 4 A/125V AC
P300, DC-13: 3 A/24V DC
Thermal Current 2 x 4 A, nonswitching
Time Range (Off-Delay) 0.1s…40 min.
Fuses, Input 500 mA time lag (external)
Fuses, Output 5 A quick acting (external)
Switching Current @ Voltage, Max. 10 mA/10V
Status Indicators Red = Power on
Red/Green = Timing/Output on
Rated Impulse withstand Voltage 2500V
Operating Temperature [C (F)] -10…55° (14…131°)
Relative humidity 90%
Enclosure Type Rating IP40, DIN 0470
Terminal Protection IP20 DIN 0470
Conductor Size, Max. 1 x 2.5 mm2 (14 AWG) stranded
1 x 4 mm2 (12 AWG) solid
Installation Group C in accordance with VDE 0110
Pollution Degree 3
Torque Settingste—terminal screws 1 N•m (8 lb•in)
Housing Material Red Polycarbonate
Mounting 35 mm DIN Rail
Weight [g (lb)] 360 (0.79)
Electrical Life 220V AC/4A/880VA cosf = 3.5—100,000 operations
220V AC/1.7A/375VA cosf = 0.6—500,000 operations
30V DC/2A/60W—1,000,000 operations
10V DC/0.01A/0.1W—2,000,000 operations
Mechanical Life 2,000,000 operations
Vibration 0.75 mm (0.30 in) peak, 10…55 Hz
Shock 30 g, 11 ms half-sine
  
¬ See Output Ratings see Output Ratings for details. Consult factory for ratings not shown.