Catalogs > Safety Products Catalog > Logic > Safety Relays > Modular Safety Relays (200 Series) > MSR210P
MSR210P
| Introduction | Specifications | Product Selection | Accessories | Approximate Dimensions | Block Diagram | Typical Wiring Diagrams |
| Safety Ratings | ||
| Standards | EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-4-1, IEC 60947-5-1, ANSI 11.19, AS 4024.1 | |
| Safety Classification | Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1 | |
| Functional Safety Data ¬ Note: For up-to-date information, visit http://www.ab.com/safety/ |
PFHD: < 3.44 x 10-9 MTTFd: > 203 years Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics |
|
| Certifications | CE Marked for all applicable directives, cULus, c-Tick, and TÜV | |
| Power Supply | ||
| Input Power Entry | 24V DC 0.8…1.1 x rated voltage | |
| Power Consumption | 8 W | |
| Inputs | ||
| Safety Inputs | 1 N.C., 2 N.C., 3 N.C., or SM | |
| Input Simultaneity | Infinite | |
| Input Resistance, Max. | Inputs: 900 W Reset: 3200 W |
|
| Reset | Auto./Manual or Monitored Manual | |
| Power On Delay/ Recovery Time |
3 seconds/ 40…145 ms, depending on expansion modules used |
|
| Response Time | MSR210: 29 ms MSR210 + Input Exp. Mod.: 34 ms + 6 ms/module |
|
| Outputs | ||
| Safety Contacts | 2 N.O. | |
| Auxiliary Contacts | 1 N.C., 2 PNP | |
| Thermal CurrentIlth | 1 x 6 A or 2 x 4 A (nonswitching) | |
| Rated Impulse withstand Voltage | 2500V | |
| Switching Current @ Voltage, Min. | 10 mA @ 10V DC | |
| Fuses, Output | External 6 A slow blow or 10 A fast acting | |
| Solid State Output Rating | 20 mA @ 30V DC short-circuit protection | |
| Electrical Life (Operations) | (With surge suppression) 250V AC/6 A/1500VA cosf = 1…0.1 M 250V AC/2 A/500VA cosf = 1…0.5 M 250V AC/4 A/1000VA cosf = 0.35…0.3 M 250V AC/1.5 A/1000VA cosf = 0.6…0.1 M 24V DC/2 A/48 W = 1 M 10V DC/0.01 A/0.1 W = 2 M |
|
| Mechanical Life | 2,000,000 cycles | |
| Utilization Category | ||
| Inductive: AC-15 | 3 A @ 250V AC | 3 A @ 125V AC |
| Inductive: DC-13 | 2.5 A @ 24V DC | |
| UL | 1 x B300, R300, or 2 x C300 1 x 6 A or 2 x 4 A Resistive | |
| Environmental and Physical Characteristics | ||
| Enclosure Type Rating/ Terminal Protection |
IP40 (NEMA 1)/ IP20 |
|
| Operating Temperature [C (F)] | -5…+55 ° (23…131 °) | |
| Vibration | 10…55 Hz, 0.35 mm | |
| Shock | 10 g, 16 ms, 100 shocks | |
| Mounting | 45 mm housing, 35 mm DIN Rail | |
| Weight [g (lb)] | 280 (0.62) | |
| Conductor Size, Max. | 0.2…4 mm2 (24…12 AWG) | |
| ¬ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions: - Mission time/Proof test interval of 20 years - Functional test at least once within six-month period |
||
