Configurable Safety Relays (300 Series)

Catalogs > Safety Products Catalog > Logic > Safety Relays > Configurable Safety Relays (300 Series) > MSR330P

MSR330P

Introduction Specifications Product Selection Accessories Approximate Dimensions Typical Wiring Diagrams
Specifications

Safety Ratings
Standards IEC/EN 60204-1, ISO TR 12100, EN 61508, ISO 13849-1 (EN 954-1)
Safety Classification Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1
Functional Safety Data ¬ 
Note: For up-to-date information, visit http://www.ab.com/safety/
PFHD: < 2.3 x 10-10
MTTFd: > 454 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus, c-Tick, and TÜV
Power Supply
Input Power Entry 24V DC from the base unit
Power Consumption 1.5 W
Inputs
Reset Selected on base module
Response Time Does not add additional response time to base module
Outputs
Safety Contacts 3 N.O.
Auxiliary Contacts 1 N.C.
Thermal CurrentIlth 2 x 6 A or 3 x 5 A
Rated Impulse withstand Voltage 2500V
Switching Current @ Voltage, Min. 10 mA @ 10V
Fuses, Output External 6 A slow blow or 10 A quick blow
Mechanical Life 2,000,000 cycles
Utilization Category
UL B300, P300, 2 x 6 A or 3 x 5 A/250V AC, 24V DC
Environmental and Physical Characteristics
Enclosure Type Rating/
Terminal Protection
IP40 (NEMA 1)/
IP20, DIN 0470
Operating Temperature [C (F)] -5…+55 ° (23…131 °)
Vibration 10…55 Hz, 0.35 mm
Shock 10 g, 16 ms, 100 shocks
Mounting 35 mm DIN Rail
Weight [g (lb)] 190 (0.42)
Conductor Size, Max. 0.2…2.5 mm2 (24…12 AWG)
 
¬ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period