Catalogs > Safety Products Catalog > Power > Safety Isolation System
Safety Isolation System
| Introduction | Specifications | Sequence of Operation | Communication | Product Selection | Introduction |
| Optional Expansion Module | Remote Lockout Station | Verification Module | Multiplexer/Permissive Module | System Selection Process |
| Certifications | cULus TÜV Rheinland Certified CE marked for all applicable directives |
| Standards | IEC/EN 60204-1 IEC/EN 60439-1 Category 4 to EN 954-1/ISO 13849-1 98/37/EC Machinery Directive 89/336/EC EMC Directive 73/23/EC Low Voltage Directive UL508A |
| Estimated Component Life Remote Lockout Station Power Contactors (Isolation & Grounding) | 23… 85 A: 2,000,000 operations 110…1200 A: 1,000,000 operations |
| Storage Temperature [C (F)] | -10…+60° (14…140°) |
| Operating Temperature [C (F)] | 0…+40° (32…104°) |
| Relative Humidity (noncondensing) | 90% (Ambient) |
| Power Panel Construction | NEMA Type 12/IP54 UL Type 4/IP66 UL Type 4x MCC (Bulletin 2100) with and without Bus |
| Expansion Module Construction | 4-port: Supports up to 4 remote lockout stations 10 port: Supports up to 10 remote lockout stations |
| Safety Isolation System Inputs | Remote Lockout Stations |
| Input Options | Safety Mats, Light Curtains, and E-Stop Stations |
| System Operational Limits | +10%, -15% of the line voltage |