Bulletin 700S-CF Safety Control Relay
Features- IEC industrial safety relay
- Mechanically linked contacts as per IEC 60947-5-1
- Third party certification SUVA
- Red cover and mechanically linked contact symbol on front face
- Gold plated, bifurcated version for low level switching applications
- Permanently fixed front mounted auxiliary contact block
|
Standards Compliance
-
EN/IEC 60947-1, -5-1
UL 508
CSA C22.2 No. 14
Certifications
- cULus Listed (File No. E14840, Guide NKCR/NKCR7)
- CE Marked
Product Selection
| Build a Catalog Number |
Type CF and CFB Safety Control Relays — 8-Pole AC Coil Voltage (Ratings for 700S-CF Only)
Ä AC Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CF440ÄBC becomes Cat. No. 700S-CF440DBC for 120V, 60 Hz.
| [V] | 12 | 24 | 32 | 36 | 42 | 48 | 100 | 100- 110 |
110 | 120 | 127 | 200 | 200- 220 |
208 | 208- 240 |
220- 230 |
| 50 Hz | R | K | V | W | X | Y | KP | — | D | P | S | KG | L | — | — | F |
| 60 Hz | Q | J | — | V | — | X | — | KP | — | D | — | — | KG | H | L | — |
| 50/60 Hz | — | KJ | — | — | — | KY | KP | — | KD | — | — | KG | KL | — | — | KL |
| [V] | 230 | 230- 240 |
240 | 277 | 347 | 380 | 380- 400 |
400 | 400- 415 |
440 | 480 | 500 | 550 | 600 |
| 50 Hz | — | VA | T | — | — | — | N | — | G | B | — | M | C | — |
| 60 Hz | — | — | A | T | I | E | — | — | — | N | B | — | — | C |
| 50/60 Hz | KF | — | KA | — | — | — | — | KN | — | KB | — | — | — | — |
Product Selection, Continued
Type CF and CFB Safety Control Relays — 8-Pole DC Coil Voltage (Ratings for 700S-CF Only)
Ä DC Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 700S-CF440ÄC becomes Cat. No. 700S-CF440ZJC for 24V DC.
| [V] | 9 | 12 | 24 | 36 | 48 | 60 | 64 | 72 | 80 | 110 | 115 | 125 | 220 | 230 | 250 |
| Standard | ZR | ZQ | ZJ | ZW | ZY | ZZ | ZB | ZG | ZE | ZD | ZP | ZS | ZA | ZF | ZT |
| Standard with diode | — | — | DJ | — | — | — | — | — | — | — | — | — | — | — | — |
| Electronic with diode | — | — | EJ | — | — | — | — | — | — | — | — | — | — | — | — |
Specifications
| Main Relay Cat. Nos. 700-CF, 700S-CF |
Front Mounted Standard Auxiliary Contacts | Main Relay Cat. No. 700-CFB, 700S-CFB |
Master Relay Cat. No. 700-CFM |
Front Mounted Bifurcated Auxiliary Contacts | Side-mounted Auxiliary Contacts | |||
| Contact Ratings — NEMA | A600, P600 | A600, Q600 | A600, Q600 | 2 x A600, P600 | A600, Q600 | A600, Q600 | ||
| Min. Contact Rating | 17V, 10 mA | 17V, 5 mA | 8V, 5 mA | — | 5V, 3 mA | 17V, 10 mA | ||
| Contact Ratings — IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1 |
24V | 10 A | 6 A | 3 A | 15 A | 3 A | 6 A | |
| 48V | 10 A | 6 A | 3 A | 15 A | 3 A | 6 A | ||
| 120V | 10 A | 6 A | 3 A | 15 A | 3 A | 6 A | ||
| 240V | 10 A | 5 A | 3 A | 15 A | 3 A | 5 A | ||
| 400V | 6 A | 3 A | 2 A | 7.5 A | 2 A | 3 A | ||
| 480V/500V | 2.5 A | 1.6 A | 1.2 A | 5 A | 1.2 A | 1.6 A | ||
| 600V | 1 A | 1 A | 0.7 A | 2 A | 0.7 A | 1 A | ||
| 690V | 1 A | 1 A | 0.7 A | 2 A | 0.7 A | 1 A | ||
| AC-12 (Control of resistive loads) IEC 60947-5-1 |
40 °C | Ith | 20 A | 10 A | 10 A | 20 A | 10 A | 10 A |
| 230 V | 8 kW | |||||||
| 400 V | 14 kW | |||||||
| 690 V | 24 kW | |||||||
| 60 °C | Ith | 20 A | 6 A | 6 A | 20 A | 6 A | 6 A | |
| 230V | 8 kW | |||||||
| 400V | 14 kW | |||||||
| 690V | 24 kW | |||||||
| DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1 |
24V | 15 A | 10 A | 6 A | 20 A | 6 A | 6 A | |
| 48V | 10 A | 9 A | 3.2 A | 20 A | 3.2 A | 3.2 A | ||
| 110V | 6 A | 3.5 A | 1 A | 8 A | 1 A | 1 A | ||
| 220V | 1 A | 0.7 A | 0.5 A | 1.5 A | 0.5 A | 0.5 A | ||
| 440V | 0.4 A | 0.2 A | 0.2 A | 0.4 A | 0.2 A | 0.2 A | ||
| DC-13 IEC 60947-5-1, Solenoids and contactors | 24V | 5 A | 5 A | 2.5 A | 5 A | 2.5 A | 5 A | |
| 48V | 3 A | 3 A | 1.5 A | 3 A | 1.5 A | 3 A | ||
| 110V | 1.2 A | 1.2 A | 0.6 A | 1.2 A | 0.6 A | 1.2 A | ||
| 220V | 0.6 A | 0.6 A | 0.3 A | 0.6 A | 0.3 A | 0.6 A | ||
| 440V | 0.3 A | 0.15 A | 0.15 A | 0.3 A | 0.15 A | 0.15 A | ||
| ⋆ Side mounted auxiliary contacts provide mirror contact performance with main poles only. | ||||||||
Specifications, Continued
| DC Switching Ratings for 700S-CF Main Poles in Series (Resistive Load at 60 °C) |
|||
| 1 pole | 2 poles | 3 poles | |
| 24/48V | 25/20 A | 25 A | 25 A |
| 125V | 6 A | 25 A | 25 A |
| 220V | 1.5 A | 8 A | 25 A |
| 440V | 0.4 A | 1 A | 3 A |
Approximate Dimensions
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended for manufacturing purposes.
|
Approximate Dimensions, Continued
AC and DC EJ Safety Control Relays
| Cat. No. | a | b | c | c1 | c2 | Æd | d1 | d2 |
| 700S-CF | 45 | 81 | 119.5 | 114.5 | 6 | 2 - 4.5 | 60 | 35 |
| (1-25/32) | (3-3/16) | (4-3/4) | (4-43/64) | (1/4) | (2 - 3/16) | (2-23/64) | (1-25/64) | |
DC Safety Control Relays
| Cat. No. | a | b | c | c1 | c2 | Æd | d1 | d2 |
| 700S-CF | 45 | 81 | 145.5 | 140.5 | 6 | 2 - 4.5 | 60 | 35 |
| (1-25/32) | (3-3/16) | (5-49/64) | (5-37/64) | (1/4) | (2 - 3/16) | (2-23/64) | (1-25/64) | |
Accessories
| Safety Control Relays with | mm | [in.] |
| Auxiliary contact block for side mounting 1- or 2-pole | a + 9 | (a + 23/64) |
| Electronic Timing Module on coil terminal side | b + 24 | (b + 15/16) |
| Interface Module on coil terminal side | b + 9 | (b + 23/64) |
| Surge Suppressor on coil terminal side | b + 3 | (b + 1/8) |
| Labeling with label sheet | + 0 | (+ 0) |
| Marking tag sheet with clear cover | + 0 | (+ 0) |
| Marking tag adapter for System Bul. 1492W | + 5.5 | (+ 7/32) |
Mounting Position
|
Safety Relay Circuit With 5 Safety Outputs
- Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire).
- High output switching capability and long contact life.
- Circuit complies with EN 954 categories 1, 2, 3, 4.
- Helps prevent restart of the 5 safety outputs if there is a single fault anywhere in the system.
Basic Circuit
(1) Output Circuit (3 Relays, 9 Terminal Blocks)
|
⋆ Numbers shown are the line numbers where the contacts for this relay appear.
Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.