Contactors and Control Relays

Catalogs > Safety Products Catalog > Power > Contactors and Control Relays > Bulletin 700S-P and 700S-PK Heavy-Duty Safety Control Relay

Bulletin 700S-P and 700S-PK Heavy-Duty Safety Control Relay

Introduction Certifications Product Selection Specifications Approximate Dimensions
Specifications

Type 700S-P 700S-PK
Electrical
Contact Rating Continuous 10 A @ 600V AC
5 A @ 600V DC
20 A @ 600V AC
10 A @ 600V DC
Ratings
Make/Break
AC NEMA A600 NEMA A600
DC NEMA P600 NEMA P600
Minimum Contact Switching Ratings 10V, 50 mA 3 Hp @ 240V AC - N.O.
2 Hp @ 240V AC - N.O./N.C.
1 HP @ 120V AC - N.O./N.C.
20 A resistive heating to 600V AC
20 A Tungsten lighting load to 480V AC
DC Switching Contacts
in Series
Volts DC Volts DC
24V 64V 125V 250V 500V 600V 24V 64V 125V 250V 500V 600V
1 5 A 2.2 A 1.1 A 0.55 A 0.24 A 0.2 A 10 A 5 A 2.2 A 0.55 A 0.24 A 0.2 A
2 10 A 10 A 5 A 2 A 0.7 A 0.5 A 20 A 10 A 5 A 2 A 0.7 A 0.5 A
3 7 A 3 A 1.5 A 1.0 A 15 A 7 A 3 A 1.5 A 1.0 A
4 10 A 5 A 2.5 A 1.5 A 20 A 10 A 5 A 2.5 A 1.5 A
Coil Voltage Range⋆  AC 85…110% 85…110%
DC 80…110% 80…110%
Battery
Charging
85…115% 85…115%
Coil Consumption     50 Hz 60 Hz 50 Hz 60 Hz
AC Inrush 132 VA 138 VA 132 VA 138 VA
Sealed 19.3 VA 19 VA 19.3 VA 19 VA
DC Inrush 12.7 W 12.7 W
Sealed 12.7 W 12.7 W
Additional Contact Rating for AC Single-Phase Loads 3 HP @ 240V AC - N.O.
2 HP @ 240V AC - N.O./N.C.
1 HP @ 130V AC - N.O./N.C.
20 A Resistive Heating to 600V AC
20 A Tungsten Lighting Load to 480V AC
Cartridge Cat. No. Bulletin 700S-CMS
Mechanical
Mechanically Linked Contacts All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles
Operating Time Pickup AC – 10…20 ms
DC – 30…50 ms
AC – 10…20 ms
DC – 30…50 ms
Dropout AC – 10…20 ms
DC – 20…33 ms
AC – 10…20 ms
DC – 20…33 ms
Mechanical Life 10 million operations
Construction
Contact Arrangement 2 to 12 Poles, Double Break Contacts
N.O. or N.C. (8 N.C. Maximum)
2 to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)
Contact Material/Design Silver Nickel/Bifurcated Silver Cadmium Oxide
Mounting Panel mount or mount on 700-MP Relay or DIN Rail
Horizontal Mounting Recommended
Panel mount or mount on 700-MP Relay or DIN Rail
Horizontal Mounting Recommended
Environmental
Temperature Operating§  –20…+65 °C (–4…+149 °F) –20…+65 °C (–4…+149 °F)
Storage –40…+65 °C (–40…+149 °F) –40…+65 °C (–40…+149 °F)
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in (0.9…1.4 N•m) 8…12 lb•in (0.9…1.4 N•m)
  
⋆ Coil voltage required for proper operation (percent of rated coil voltage).
§ Temperature inside the panel.