Bulletin 100S-C/104S-C Safety Contactors
|
|
- Mechanically linked N.C. auxiliary contacts
- Front-mounted auxiliary contacts:
Gold bifurcated
Permanently fixed
Protective cover to prevent manual operation
Red contact housing foreasy identification
Incorporates IEC 60947-5-1 Mechanically Linked or IEC 60947-4-1 "Mirror Contact" symbol
- AC and DC operating coils
- SUVA Third-Party certification
Bulletin 100S-C/104S-C safety contactors provide mechanically linked positively guided contacts, required in feedback circuits of modern safety applications. The mechanically linked N.C. auxiliary contacts will not change state when a power pole welds. In addition, the gold-plated bifurcated auxiliary contacts are ideally suited for low-energy applications or feedback control circuits with multiple series-connected N.C. auxiliary contacts.
Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories and/or replacement coils.
Standards Compliance and Certifications
Standards Compliance
EN50205
CSA C22.2 No. 14
UL 508
EN/IEC 60947-4
IEC 60947-4-1 Annex H — Mirror Contacts
IEC 60947-5-1 Annex L — Mechanically Linked Contacts
Certifications
SUVA Third-Party Certified
CE Marked
cULus Listed (File No. E3125;
Guide NLDX, NLDX7)
Product Selection
3-Pole AC- and DC-Operated Contactors
| Ie [A] | Ratings for Switching AC Motors — AC-2, AC-3, AC-4 | Aux. Contacts | Cat. No.⋆ | ||||||||||||
| 3-Phase kW (50 Hz) | Hp (60 Hz) |
|
|
||||||||||||
| AC-3 | AC-1 | 230V | 400V/ 415V |
500V | 690V | 1-Phase | 3-Phase |
|
|||||||
| 115V | 230V | 200V | 230V | 460V | 575V | N.O. | N.C. | ||||||||
| 9 | 32 | 3 | 4 | 4 | 4 | 1/2 | 1-1/2 | 2 | 2 | 5 | 7-1/2 | 0 | 5 | 100S-C09Ä05BC | |
| 1 | 4 | 100S-C09Ä14BC | |||||||||||||
| 12 | 32 | 4 | 5.5 | 5.5 | 5.5 | 1/2 | 2 | 3 | 3 | 7-1/2 | 10 | 0 | 5 | 100S-C12Ä05BC | |
| 1 | 4 | 100S-C12Ä14BC | |||||||||||||
| 16 | 32 | 5.5 | 7.5 | 7.5 | 7.5 | 1 | 3 | 5 | 5 | 10 | 15 | 0 | 5 | 100S-C16Ä05BC | |
| 1 | 4 | 100S-C16Ä14BC | |||||||||||||
| 23 | 32 | 7.5 | 11 | 13 | 10 | 2 | 3 | 5 | 7-1/2 | 15 | 15 | 0 | 5 | 100S-C23Ä05BC | |
| 1 | 4 | 100S-C23Ä14BC | |||||||||||||
| 30 | 65 | 10 | 15 | 15 | 15 | 2 | 5 | 7-1/2 | 10 | 20 | 25 | 0 | 4 | 100S-C30Ä04BC | |
| 1 | 4 | 100S-C30Ä14BC | |||||||||||||
| 37 | 65 | 11 | 18.5/20 | 20 | 18.5 | 3 | 5 | 10 | 10 | 25 | 30 | 0 | 4 | 100S-C37Ä04BC | |
| 1 | 4 | 100S-C37Ä14BC | |||||||||||||
| 43 | 85 | 13 | 22 | 25 | 22 | 3 | 7-1/2 | 10 | 15 | 30 | 30 | 0 | 4 | 100S-C43Ä04BC | |
| 1 | 4 | 100S-C43Ä14BC | |||||||||||||
| 60 | 100 | 18.5 | 32 | 37 | 32 | 5 | 10 | 15 | 20 | 40 | 50 | 0 | 4 | § | 100S-C60Ä04BC |
| 1 | 4 | § | 100S-C60Ä14BC | ||||||||||||
| 72 | 100 | 22 | 40 | 45 | 40 | 5 | 15 | 20 | 25 | 50 | 60 | 0 | 4 | § | 100S-C72Ä04BC |
| 1 | 4 | § | 100S-C72Ä14BC | ||||||||||||
| 85 | 100 | 25 | 45 | 55 | 45 | 7-1/2 | 15 | 25 | 30 | 60 | 60 | 0 | 4 | § | 100S-C85Ä04BC |
| 1 | 4 | § | 100S-C85Ä14BC | ||||||||||||
| 97 | 130 | 30 | 55 | 55 | 55 | 10 | 15 | 30 | 30 | 75 | 75 | 0 | 4 | § | 100S-C97Ä04BC |
| 1 | 4 | § | 100S-C97Ä14BC | ||||||||||||
| ⋆ For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||||||||
| If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä05BC becomes Cat. No. 100S-C09Ä05C. | |||||||||||||||
| § Bifurcated front-mount auxiliary contacts on Cat. Nos. 100S-C60…C97 conform to mirror contact performance only. | |||||||||||||||
| Ä Coil Voltage Code, see Ä Coil Voltage Code and Terminal Position | |||||||||||||||
|
|
4-Pole AC- and DC-Operated Contactors
| Ie [A] | Ratings for Switching AC Motors | Contact Configuration | Cat. No.⋆ § | Price | ||||||||||||||
| AC-2, AC-3, AC-4 | Hp (60 Hz) | |||||||||||||||||
| 3-Phase kW (50 Hz) | Main Pole | Auxillary Contacts | ||||||||||||||||
| AC-3 | AC-1 | 230V | 400V/ 415V |
500V | 690V | 1-Phase | 3-Phase |
|
|
|
|
AC Coil |
DC Coil |
|||||
|
|
||||||||||||||||||
| 115V | 230V | 200V | 230V | 460V | 575V | N.O. | N.C. | N.O. | N.C. | |||||||||
| 9 | 32 | 3 | 4 | 4 | 4 | 1/2 | 1-1/2 | 2 | 2 | 5 | 7-1/2 | 4 | 0 | 0 | 4 | 100S-C09Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C09Ä304BC | ||||||||||||||
| 12 | 32 | 4 | 5.5 | 5.5 | 5.5 | 1/2 | 2 | 3 | 3 | 7-1/2 | 10 | 4 | 0 | 0 | 4 | 100S-C12Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C12Ä304BC | ||||||||||||||
| 16 | 32 | 5.5 | 7.5 | 7.5 | 7.5 | 1 | 3 | 5 | 5 | 10 | 15 | 4 | 0 | 0 | 4 | 100S-C16Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C16Ä304BC | ||||||||||||||
| 23 | 32 | 7.5 | 11 | 13 | 10 | 2 | 3 | 5 | 7-1/2 | 15 | 15 | 4 | 0 | 0 | 4 | 100S-C23Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C23Ä304BC | ||||||||||||||
| ⋆ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||||||||||||||
| Three-phase ratings only apply to contactors with at least three N.O. power poles. | ||||||||||||||||||
| Ä Coil Voltage Code, see Ä Coil Voltage Code and Terminal Position | ||||||||||||||||||
| § If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä404BC becomes Cat. No. 100S-C09Ä404C. | ||||||||||||||||||
Reversing AC- and DC-Operated Contactors
- 3 Main Contacts
- Includes Mechanical/Electrical Interlock
- Includes Reversing Power Wiring
|
| Ie [A] | Ratings for Switching AC Motors | Aux. Contacts Installed per Contactor |
Cat. No.⋆ | ||||||||||||
| AC-2, AC-3, AC-4 |
|
|
|||||||||||||
| 3-Phase kW (50 Hz) | Hp (60 Hz) | ||||||||||||||
| AC-3 | AC-1 | 230V | 400V/ 415V |
500V | 690V | 1-Phase | 3-Phase |
|
|||||||
| 115V | 230V | 200V | 230V | 460V | 575V | N.O. | N.C. § | ||||||||
| 9 | 32 | 3 | 4 | 4 | 4 | 1/2 | 1-1/2 | 2 | 2 | 5 | 7-1/2 | 0 | 6 | 104S-C09Ä012BC | |
| 1 | 5 | 104S-C09Ä210BC | |||||||||||||
| 12 | 32 | 4 | 5.5 | 5.5 | 5.5 | 1/2 | 2 | 3 | 3 | 7-1/2 | 10 | 0 | 6 | 104S-C12Ä012BC | |
| 1 | 5 | 104S-C12Ä210BC | |||||||||||||
| 16 | 32 | 5.5 | 7.5 | 7.5 | 7.5 | 1 | 3 | 5 | 5 | 10 | 15 | 0 | 6 | 104S-C16Ä012BC | |
| 1 | 5 | 104S-C16Ä210BC | |||||||||||||
| 23 | 32 | 7.5 | 11 | 13 | 10 | 2 | 3 | 5 | 7-1/2 | 15 | 15 | 0 | 6 | 104S-C23Ä012BC | |
| 1 | 5 | 104S-C23Ä210BC | |||||||||||||
| 30 | 65 | 10 | 15 | 15 | 15 | 2 | 5 | 7-1/2 | 10 | 20 | 25 | 0 | 5 | 104S-C30Ä010BC | |
| 1 | 5 | 104S-C30Ä210BC | |||||||||||||
| 37 | 65 | 11 | 18.5/20 | 20 | 18.5 | 3 | 5 | 10 | 10 | 25 | 30 | 0 | 5 | 104S-C37Ä010BC | |
| 1 | 5 | 104S-C37Ä210BC | |||||||||||||
| 43 | 85 | 13 | 22 | 25 | 22 | 3 | 7-1/2 | 10 | 15 | 30 | 30 | 0 | 5 | 104S-C43Ä010BC | |
| 1 | 5 | 104S-C43Ä210BC | |||||||||||||
| 60 | 100 | 18.5 | 32 | 37 | 32 | 5 | 10 | 15 | 20 | 40 | 50 | 0 | 5 | ♣ | 104S-C60Ä010BC |
| 1 | 5 | ♣ | 104S-C60Ä210BC | ||||||||||||
| 72 | 100 | 22 | 40 | 45 | 40 | 5 | 15 | 20 | 25 | 50 | 60 | 0 | 5 | ♣ | 104S-C72Ä010BC |
| 1 | 5 | ♣ | 104S-C72Ä210BC | ||||||||||||
| 85 | 100 | 25 | 45 | 55 | 45 | 7-1/2 | 15 | 25 | 30 | 60 | 60 | 0 | 5 | ♣ | 104S-C85Ä010BC |
| 1 | 5 | ♣ | 104S-C85Ä210BC | ||||||||||||
| 97 | 130 | 30 | 55 | 55 | 55 | 10 | 15 | 30 | 30 | 75 | 75 | 0 | 5 | ♣ | 104S-C97Ä010BC |
| 1 | 5 | ♣ | 104S-C97Ä210BC | ||||||||||||
| ⋆ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||||||||
| If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C09Ä05BC becomes Cat. No. 104S-C09Ä05C. | |||||||||||||||
| § One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock. | |||||||||||||||
| ♣ Bifurcated front-mount auxiliary contacts on Cat. Nos. 104S-C60…C97 conform to mirror contact performance only. | |||||||||||||||
| Ä Coil Voltage Code, see Ä Coil Voltage Code and Terminal Position | |||||||||||||||
Ä Coil Voltage Code and Terminal Position
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09Ä05BC becomes Cat. No.100S-C09D05BC.
| [V] | 12 | 24 | 32 | 36 | 42 | 48 | 100 | 100-110 | 110 | 120 | 127 | 200 | 200-220 | 208 | 208-240 | 220-230 |
| AC, 50 Hz | R | K | V | W | X | Y | KP | — | D | P | S | KG | L | — | — | F |
| AC, 60 Hz | Q | J | — | V | — | X | — | KP | — | D | — | — | KG | H | L | — |
| AC, 50/60 Hz | | KJ | — | — | — | KY | KP | — | KD | — | — | KG | KL§ | — | — | KL§ |
| [V] | 230 | 230-240 | 240 | 277 | 347 | 380 | 380-400 | 400 | 400-415 | 440 | 480 | 500 | 550 | 600 | ||
| AC, 50 Hz | — | VA | T | — | — | — | N | — | G | B | — | M | C | — | ||
| AC, 60 Hz | — | — | A | T | I | E | — | — | — | N | B | — | — | C | ||
| AC, 50/60 Hz | KF | — | KA | — | — | — | — | KN | — | KB | — | — | — | — | ||
| § Not available in 100S/104S-C97 contactors | ||||||||||||||||
| [V] | 9 | 12 | 24 | 36 | 48 | 60 | 64 | 72 | 80 | 110 | 115 | 125 | 220 | 230 | 250 | ||
| 100S/104S-C09…C43 | Standard | DC | ZR | ZQ | ZJ | ZW | ZY | ZZ | ZB | ZG | ZE | ZD | ZP | ZS | ZA | ZF | ZT |
| with Integrated Diode | — | — | DJ | — | — | — | — | — | — | — | — | — | — | — | — | ||
| Electronic with Integrated Diode | — | — | EJ | — | — | — | — | — | — | — | — | — | — | — | — | ||
| 100S/104S-C60…C97 | with Integrated Diode | DR | DQ | DJ | DW | DY | DZ | DB | DG | DE | DD | DP | DS | DA | DF | DT | |
Coil Terminal Position
- All contactors are delivered with the coil terminals located on the line side.
- For load side coil terminations, insert a U prior to the coil voltage code.
Example: Cat. No. 100S-C09UD05BC.
Bulletin 100S-C/104S-C Accessories
Control Modules (For 100S-C09…C97 contactors)
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 100-FL11Ä becomes Cat. No. 100-FL11D.
| [V]⋆ | 24V | 48V | 100V | 110V | 120V | 230-240V | 240V | 277V | 380-400V | 400-415V | 440V | 480V |
| AC, 50 Hz | K | Y | KP | D | — | VA | T | — | N | G | B | — |
| AC, 60 Hz | J | — | — | — | D | — | A | T | — | — | N | B |
| ⋆ For special voltages, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||||||||
Control Modules (For 100S-C09…C97 contactors), Continued
Assembly Components (For 100S-C09…C97 contactors)
Marking Systems (For 100S-C09…C97 contactors)
Terminal Kits (For 100S-C09…C97 contactors)
Specifications
Coil Data
| 100S/104S-C | |||||||||||||
| 09 | 12 | 16 | 23 | 30 | 37 | 43 | 60 | 72 | 85 | 97 | |||
| Coil Type | Conventional | X | X | X | X | X | X | X | X | X | X | X | |
| Electronic — EI | — | — | — | — | — | — | — | — | — | — | — | ||
| Operating Limits | |||||||||||||
| 50 Hz, 60 Hz, 50/60 Hz | pick-up | [x Us] | 0.85…1.1 | 0.85….1.1 | |||||||||
| dropout | [x Us] | 0.3…0.6 | 0.3…0.6 | ||||||||||
| DC (conventional) | pick-up | [x Us] | 0.8…1.1 | 0.8…1.1 | |||||||||
| dropout | [x Us] | 0.1…0.6 | 0.1…0.6 | ||||||||||
| DC (electronic) | pick-up | [x Us] | 0.7…1.25 | — | |||||||||
| dropout | [x Us] | 0.1…0.5 | — | ||||||||||
| Coil Consumption | |||||||||||||
| 50 Hz, 60 Hz, 50/60 Hz | pick-up | [VA/W] | 70/50 | 70/50 | 80/60 | 130/90 | 200/110 | ||||||
| hold-in | [VA/W] | 8/2.6 | 9/3 | 9/3 | 10/3.2 | 16/4.5 | |||||||
| DC (conventional) | pick-up | [W] | 6.5 | 9.2 | 9.2 | 10.1 | 200 | ||||||
| hold-in | [W] | 6.5 | 9.2 | 9.2 | 10.1 | 4.5 | |||||||
| DC (electronic) | pick-up (avg/peak) | [W] | 10/22 | 10/22 | 10.1 | — | |||||||
| hold-in | [W] | 1.5 | 10.1 | — | |||||||||
| Operating Times | |||||||||||||
| AC | closing delay | [ms] | 15…30 | 15…30 | 15…30 | 15…30 | 20…40 | ||||||
| opening delay | [ms] | 10…60 | 10…60 | 10…60 | 10…60 | 10…60 | |||||||
| With RC module | opening delay | [ms] | 10…60 | 10…60 | 10…60 | 10…60 | 10…60 | ||||||
| DC (conventional) | closing delay | [ms] | 40…70 | 40…70 | 50…80 | 50…80 | 20…40 | ||||||
| opening delay | [ms] | 7…15 | 7…15 | 7…15 | 7…15 | — | |||||||
| With integ. diode | opening delay | [ms] | 14…20 | 17…23 | 17…23 | 17…23 | £ 220V 20…35 | ||||||
| With external diode | opening delay | [ms] | 70…95 | 80…125 | 80…125 | 80…125 | £ 220V 80…125 | ||||||
| DC (electronic) | closing delay | [ms] | 20…40 | — | |||||||||
| opening delay | [ms] | 20…40 | — | ||||||||||
| Max. Ripple | ± 15% | — | |||||||||||
| 100S-D | ||||||||||||||
| 115 | 140/180 | 95 | 110 | 140 | 180 | 210 | 250 | 300 | 420 | 630 | 860 | |||
| Coil Type | Conventional | X | X | — | — | — | — | — | — | — | — | — | — | |
| Electronic — EI | — | — | X | X | X | X | X | X | X | X | X | X | ||
| Operating Limits | ||||||||||||||
| 50 Hz, 60 Hz, 50/60 Hz | pick-up | [x Us] | 0.85…1.1 | 0.85…1.1 | 0.8…1.1 | |||||||||
| dropout | [x Us] | 0.3…0.6 | 0.3…0.5 | 0.3…0.8 | ||||||||||
| DC control | pick-up | [x Us] | 0.85…1.1 | 0.85…1.1 | 0.85…1.1 | |||||||||
| dropout | [x Us] | 0.3…0.6 | 0.3…0.5 | 0.3…0.8 | ||||||||||
| Coil Consumption | ||||||||||||||
| 50 Hz, 60 Hz, 50/60 Hz | pick-up | [VA/W] | 650/310 | 380/240⋆ | 490/270⋆ | 1915/1720⋆ | ||||||||
| hold-in | [VA/W] | 50/10 | 13/6 | 18/7 | 33/30 | |||||||||
| DC control | pick-up | [W] | 540 | 265⋆ | 340⋆ | 1980⋆ | ||||||||
| hold-in | [W] | 8 | 6 | 7 | 30 | |||||||||
| Operating Times | ||||||||||||||
| AC | closing delay | [ms] | 20…47 | 20…45 | 60…100 | |||||||||
| opening delay | [ms] | 6…12 | 25…110 | 70…145 | ||||||||||
| With RC module | opening delay | [ms] | 9…18 | — | — | |||||||||
| DC | closing delay | [ms] | 27…47 | 25…50 | 60…100 | |||||||||
| opening delay | [ms] | 12…20 | 35…110 | 70…145 | ||||||||||
| With integrated diode | opening delay | [ms] | 12…20 | — | — | |||||||||
| With external diode | opening delay | [ms] | — | — | — | — | ||||||||
| ⋆ Electronic coil drives are designed to minimize power requirements, but this control may exhibit a higher inrush (540 W, < 10 ms) when energizing. This must be taken into account for the proper sizing of supply devices, all-or-nothing relays and cross-sections of coil supply lines. Please contact your local Rockwell Automation sales office or Allen-Bradley distributor for detailed information. | ||||||||||||||
Bulletin 100S-C/104S-C Approximate Dimensions
Bulletin 100S-C/104S-C Contactors and Accessories
Approximate dimensions are shown in millimeters (inches) and not intended for manufacturing purposes.
|
Mounting
Position
|
|
AC Contactors and DC Contactors with Electronic Coils
| Cat. No. | a | b | c | c1 | c2 | Æd | d1 | d2 |
| 100S-C09…100S-C23 | 45 (1-25/32) |
81 (3-3/16) |
119.5 (4-3/4) |
114.5 (4-43/64) |
6 (15/64) |
2-4.5 (2-3/16) |
60 (2-23/64) |
35 (1-3/8) |
| 100S-C30, 100S-C37 | 45 (1-25/32) |
81 (3-3/16) |
136.5 (5-37/64) |
131.6 (5-11/32) |
6.5 (1/4) |
2-4.5 (2-3/16) |
60 (2-23/64) |
35 (1-3/8) |
| 100S-C43 | 54 (2-1/8) |
81 (3-3/16) |
139.5 (5-11/16) |
134.6 (5-29/64) |
6.5 (1/4) |
2-4.5 (2-3/16) |
60 (2-23/64) |
45 (1-25/32) |
| 100S-C60…100S-C97 | 72 (2-53/64) |
122 (4-51/64) |
156 (6-11/32) |
150.5 (6-1/8) |
8.5 (21/64) |
4-5.4 (4-7/32) |
100 (3-15/16) |
55 (2-11/64) |
DC Contactors
| Cat. No. | a | b | c | c1 | c2 | Æd | d1 | d2 |
| 100S-C09Z...100S-C16Z | 45 (1-25/32) |
81 (3-3/16) |
145.5 (5-49/64) |
140.5 (5-37/64) |
6 (15/64) |
2-4.5 (2-3/16) |
60 (2-23/64) |
35 (1-3/8) |
| 100S-C23Z | 45 (1-25/32) |
81 (3-3/16) |
162.5 (6-7/16) |
158 (6-1/4) |
6 (15/64) |
2-4.5 (2 -3/16) |
60 (2-23/64) |
35 (1-3/8) |
| 100S-C30Z...100S-C37Z | 45 (1-25/32) |
81 (3-3/16) |
180.5 (7-5/32) |
175.5 (6-61/64) |
6.5 (1/4) |
2-4.5 (2-3/16) |
60 (2-23/64) |
35 (1-3/8) |
| 100S-C43Z | 54 (2-1/8) |
81 (3-3/16) |
183.5 (7-17/64) |
179 (7-3/32) |
6.5 (1/4) |
2-4.5 (2-3/16) |
60 (2-23/64) |
45 (1-25/32) |
| 100S-C60D...100S-C97D | 72 (2-53/64) |
122 (4-51/64) |
156 (6-11/32) |
150.5 (6-1/8) |
8.5 (21/64) |
4-5.4 (4-7/32) |
100 (3-15/16) |
55 (2-11/64) |
Accessories
| Contactors with | mm | (inches) | |
| Auxiliary contact block for side mounting | 1- or 2-pole | a + 9 | (a + 23/64) |
| Electronic Timing Module | on coil terminal side | b + 24 | (b + 15/16) |
| Mechanical Interlock | on side of contactor | a + 9 | (a + 23/64) |
| Interface Module | on coil terminal side | b + 9 | (b + 23/64) |
| Surge Suppressor | on coil terminal side | b + 3 | (b + 1/8) |
| Labeling with ⋆ | label sheet marking tag sheet with clear cover marking tag adapter for System V4 / V5 marking tag adapter for System Bul. 1492W |
+ 0 + 0 + 5.5 + 5.5 |
(+ 0) (+ 0) (+ 7/32) (+ 7/32) |