Catalogs > Safety Products Catalog > Power > Contactors and Control Relays > Bulletin 100S-C/104S-C Safety Contactors
Bulletin 100S-C/104S-C Safety Contactors
| Introduction | Standards Compliance and Certifications | Product Selection | Bulletin 100S-C/104S-C Accessories | Specifications | Bulletin 100S-C/104S-C Approximate Dimensions |
3-Pole AC- and DC-Operated Contactors
| Ie [A] | Ratings for Switching AC Motors — AC-2, AC-3, AC-4 | Aux. Contacts | Cat. No.⋆ | ||||||||||||
| 3-Phase kW (50 Hz) | Hp (60 Hz) |
|
|
||||||||||||
| AC-3 | AC-1 | 230V | 400V/ 415V |
500V | 690V | 1-Phase | 3-Phase |
|
|||||||
| 115V | 230V | 200V | 230V | 460V | 575V | N.O. | N.C. | ||||||||
| 9 | 32 | 3 | 4 | 4 | 4 | 1/2 | 1-1/2 | 2 | 2 | 5 | 7-1/2 | 0 | 5 | 100S-C09Ä05BC | |
| 1 | 4 | 100S-C09Ä14BC | |||||||||||||
| 12 | 32 | 4 | 5.5 | 5.5 | 5.5 | 1/2 | 2 | 3 | 3 | 7-1/2 | 10 | 0 | 5 | 100S-C12Ä05BC | |
| 1 | 4 | 100S-C12Ä14BC | |||||||||||||
| 16 | 32 | 5.5 | 7.5 | 7.5 | 7.5 | 1 | 3 | 5 | 5 | 10 | 15 | 0 | 5 | 100S-C16Ä05BC | |
| 1 | 4 | 100S-C16Ä14BC | |||||||||||||
| 23 | 32 | 7.5 | 11 | 13 | 10 | 2 | 3 | 5 | 7-1/2 | 15 | 15 | 0 | 5 | 100S-C23Ä05BC | |
| 1 | 4 | 100S-C23Ä14BC | |||||||||||||
| 30 | 65 | 10 | 15 | 15 | 15 | 2 | 5 | 7-1/2 | 10 | 20 | 25 | 0 | 4 | 100S-C30Ä04BC | |
| 1 | 4 | 100S-C30Ä14BC | |||||||||||||
| 37 | 65 | 11 | 18.5/20 | 20 | 18.5 | 3 | 5 | 10 | 10 | 25 | 30 | 0 | 4 | 100S-C37Ä04BC | |
| 1 | 4 | 100S-C37Ä14BC | |||||||||||||
| 43 | 85 | 13 | 22 | 25 | 22 | 3 | 7-1/2 | 10 | 15 | 30 | 30 | 0 | 4 | 100S-C43Ä04BC | |
| 1 | 4 | 100S-C43Ä14BC | |||||||||||||
| 60 | 100 | 18.5 | 32 | 37 | 32 | 5 | 10 | 15 | 20 | 40 | 50 | 0 | 4 | § | 100S-C60Ä04BC |
| 1 | 4 | § | 100S-C60Ä14BC | ||||||||||||
| 72 | 100 | 22 | 40 | 45 | 40 | 5 | 15 | 20 | 25 | 50 | 60 | 0 | 4 | § | 100S-C72Ä04BC |
| 1 | 4 | § | 100S-C72Ä14BC | ||||||||||||
| 85 | 100 | 25 | 45 | 55 | 45 | 7-1/2 | 15 | 25 | 30 | 60 | 60 | 0 | 4 | § | 100S-C85Ä04BC |
| 1 | 4 | § | 100S-C85Ä14BC | ||||||||||||
| 97 | 130 | 30 | 55 | 55 | 55 | 10 | 15 | 30 | 30 | 75 | 75 | 0 | 4 | § | 100S-C97Ä04BC |
| 1 | 4 | § | 100S-C97Ä14BC | ||||||||||||
| ⋆ For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||||||||
| If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä05BC becomes Cat. No. 100S-C09Ä05C. | |||||||||||||||
| § Bifurcated front-mount auxiliary contacts on Cat. Nos. 100S-C60…C97 conform to mirror contact performance only. | |||||||||||||||
| Ä Coil Voltage Code, see Ä Coil Voltage Code and Terminal Position | |||||||||||||||
|
|
4-Pole AC- and DC-Operated Contactors
| Ie [A] | Ratings for Switching AC Motors | Contact Configuration | Cat. No.⋆ § | Price | ||||||||||||||
| AC-2, AC-3, AC-4 | Hp (60 Hz) | |||||||||||||||||
| 3-Phase kW (50 Hz) | Main Pole | Auxillary Contacts | ||||||||||||||||
| AC-3 | AC-1 | 230V | 400V/ 415V |
500V | 690V | 1-Phase | 3-Phase |
|
|
|
|
AC Coil |
DC Coil |
|||||
|
|
||||||||||||||||||
| 115V | 230V | 200V | 230V | 460V | 575V | N.O. | N.C. | N.O. | N.C. | |||||||||
| 9 | 32 | 3 | 4 | 4 | 4 | 1/2 | 1-1/2 | 2 | 2 | 5 | 7-1/2 | 4 | 0 | 0 | 4 | 100S-C09Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C09Ä304BC | ||||||||||||||
| 12 | 32 | 4 | 5.5 | 5.5 | 5.5 | 1/2 | 2 | 3 | 3 | 7-1/2 | 10 | 4 | 0 | 0 | 4 | 100S-C12Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C12Ä304BC | ||||||||||||||
| 16 | 32 | 5.5 | 7.5 | 7.5 | 7.5 | 1 | 3 | 5 | 5 | 10 | 15 | 4 | 0 | 0 | 4 | 100S-C16Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C16Ä304BC | ||||||||||||||
| 23 | 32 | 7.5 | 11 | 13 | 10 | 2 | 3 | 5 | 7-1/2 | 15 | 15 | 4 | 0 | 0 | 4 | 100S-C23Ä404BC | ||
| 3 | 1 | 0 | 4 | 100S-C23Ä304BC | ||||||||||||||
| ⋆ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||||||||||||||
| Three-phase ratings only apply to contactors with at least three N.O. power poles. | ||||||||||||||||||
| Ä Coil Voltage Code, see Ä Coil Voltage Code and Terminal Position | ||||||||||||||||||
| § If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä404BC becomes Cat. No. 100S-C09Ä404C. | ||||||||||||||||||
Reversing AC- and DC-Operated Contactors
- 3 Main Contacts
- Includes Mechanical/Electrical Interlock
- Includes Reversing Power Wiring
|
| Ie [A] | Ratings for Switching AC Motors | Aux. Contacts Installed per Contactor |
Cat. No.⋆ | ||||||||||||
| AC-2, AC-3, AC-4 |
|
|
|||||||||||||
| 3-Phase kW (50 Hz) | Hp (60 Hz) | ||||||||||||||
| AC-3 | AC-1 | 230V | 400V/ 415V |
500V | 690V | 1-Phase | 3-Phase |
|
|||||||
| 115V | 230V | 200V | 230V | 460V | 575V | N.O. | N.C. § | ||||||||
| 9 | 32 | 3 | 4 | 4 | 4 | 1/2 | 1-1/2 | 2 | 2 | 5 | 7-1/2 | 0 | 6 | 104S-C09Ä012BC | |
| 1 | 5 | 104S-C09Ä210BC | |||||||||||||
| 12 | 32 | 4 | 5.5 | 5.5 | 5.5 | 1/2 | 2 | 3 | 3 | 7-1/2 | 10 | 0 | 6 | 104S-C12Ä012BC | |
| 1 | 5 | 104S-C12Ä210BC | |||||||||||||
| 16 | 32 | 5.5 | 7.5 | 7.5 | 7.5 | 1 | 3 | 5 | 5 | 10 | 15 | 0 | 6 | 104S-C16Ä012BC | |
| 1 | 5 | 104S-C16Ä210BC | |||||||||||||
| 23 | 32 | 7.5 | 11 | 13 | 10 | 2 | 3 | 5 | 7-1/2 | 15 | 15 | 0 | 6 | 104S-C23Ä012BC | |
| 1 | 5 | 104S-C23Ä210BC | |||||||||||||
| 30 | 65 | 10 | 15 | 15 | 15 | 2 | 5 | 7-1/2 | 10 | 20 | 25 | 0 | 5 | 104S-C30Ä010BC | |
| 1 | 5 | 104S-C30Ä210BC | |||||||||||||
| 37 | 65 | 11 | 18.5/20 | 20 | 18.5 | 3 | 5 | 10 | 10 | 25 | 30 | 0 | 5 | 104S-C37Ä010BC | |
| 1 | 5 | 104S-C37Ä210BC | |||||||||||||
| 43 | 85 | 13 | 22 | 25 | 22 | 3 | 7-1/2 | 10 | 15 | 30 | 30 | 0 | 5 | 104S-C43Ä010BC | |
| 1 | 5 | 104S-C43Ä210BC | |||||||||||||
| 60 | 100 | 18.5 | 32 | 37 | 32 | 5 | 10 | 15 | 20 | 40 | 50 | 0 | 5 | ♣ | 104S-C60Ä010BC |
| 1 | 5 | ♣ | 104S-C60Ä210BC | ||||||||||||
| 72 | 100 | 22 | 40 | 45 | 40 | 5 | 15 | 20 | 25 | 50 | 60 | 0 | 5 | ♣ | 104S-C72Ä010BC |
| 1 | 5 | ♣ | 104S-C72Ä210BC | ||||||||||||
| 85 | 100 | 25 | 45 | 55 | 45 | 7-1/2 | 15 | 25 | 30 | 60 | 60 | 0 | 5 | ♣ | 104S-C85Ä010BC |
| 1 | 5 | ♣ | 104S-C85Ä210BC | ||||||||||||
| 97 | 130 | 30 | 55 | 55 | 55 | 10 | 15 | 30 | 30 | 75 | 75 | 0 | 5 | ♣ | 104S-C97Ä010BC |
| 1 | 5 | ♣ | 104S-C97Ä210BC | ||||||||||||
| ⋆ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||||||||
| If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C09Ä05BC becomes Cat. No. 104S-C09Ä05C. | |||||||||||||||
| § One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock. | |||||||||||||||
| ♣ Bifurcated front-mount auxiliary contacts on Cat. Nos. 104S-C60…C97 conform to mirror contact performance only. | |||||||||||||||
| Ä Coil Voltage Code, see Ä Coil Voltage Code and Terminal Position | |||||||||||||||
Ä Coil Voltage Code and Terminal Position
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09Ä05BC becomes Cat. No.100S-C09D05BC.
| [V] | 12 | 24 | 32 | 36 | 42 | 48 | 100 | 100-110 | 110 | 120 | 127 | 200 | 200-220 | 208 | 208-240 | 220-230 |
| AC, 50 Hz | R | K | V | W | X | Y | KP | — | D | P | S | KG | L | — | — | F |
| AC, 60 Hz | Q | J | — | V | — | X | — | KP | — | D | — | — | KG | H | L | — |
| AC, 50/60 Hz | | KJ | — | — | — | KY | KP | — | KD | — | — | KG | KL§ | — | — | KL§ |
| [V] | 230 | 230-240 | 240 | 277 | 347 | 380 | 380-400 | 400 | 400-415 | 440 | 480 | 500 | 550 | 600 | ||
| AC, 50 Hz | — | VA | T | — | — | — | N | — | G | B | — | M | C | — | ||
| AC, 60 Hz | — | — | A | T | I | E | — | — | — | N | B | — | — | C | ||
| AC, 50/60 Hz | KF | — | KA | — | — | — | — | KN | — | KB | — | — | — | — | ||
| § Not available in 100S/104S-C97 contactors | ||||||||||||||||
| [V] | 9 | 12 | 24 | 36 | 48 | 60 | 64 | 72 | 80 | 110 | 115 | 125 | 220 | 230 | 250 | ||
| 100S/104S-C09…C43 | Standard | DC | ZR | ZQ | ZJ | ZW | ZY | ZZ | ZB | ZG | ZE | ZD | ZP | ZS | ZA | ZF | ZT |
| with Integrated Diode | — | — | DJ | — | — | — | — | — | — | — | — | — | — | — | — | ||
| Electronic with Integrated Diode | — | — | EJ | — | — | — | — | — | — | — | — | — | — | — | — | ||
| 100S/104S-C60…C97 | with Integrated Diode | DR | DQ | DJ | DW | DY | DZ | DB | DG | DE | DD | DP | DS | DA | DF | DT | |
Coil Terminal Position
- All contactors are delivered with the coil terminals located on the line side.
- For load side coil terminations, insert a U prior to the coil voltage code.
Example: Cat. No. 100S-C09UD05BC.