Contactors and Control Relays

Catalogs > Safety Products Catalog > Power > Contactors and Control Relays > Bulletin 100S-C/104S-C Safety Contactors

Bulletin 100S-C/104S-C Safety Contactors

Introduction Standards Compliance and Certifications Product Selection Bulletin 100S-C/104D-C Accessories Specifications Bulletin 100S-C/104S-C Approximate Dimensions
Specifications

  100S/104S-C
  09 12 16 23 30 37 40 43 60 72 85
Coil Type : Conventional X X X X X X X X X X X
    Electronic — EI
Conductor Cross Sections - Main Contacts
Terminal type
Click to enlarge - 140M-29-1 ¬  Click to enlarge - 140M-29-2 T  Click to enlarge - 140M-29-2 ‡ 
Click to enlarge - 140M-29-4   (1) conductor
(2) conductors
[mm2]
[mm2]
1…4
1…4
2.5…10
2.5…10
2.5…16
2.5…10
2.5…35
2.5…25
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 (1) conductor
(2) conductors
[mm2]
[mm2]
1.5…6
1.5…6
2.5…16
2.5…16
2.5…25
2.5…16
2.5…50
2.5…35
Click to enlarge - Contactors_2-30-9 b max. [mm]
c max. [mm]
s max. [mm]
Æ min. [mm]
Recommended torque [Nm]   1.5…2.5 2.5…3.5 2.5…3.5 3.5…6
Cross section per UL/CSA [AWG]   16…10 14…4 14…6 14…4 14…1
Recommended torque [lb-in]   13.3…22 22…31 22…31 31…53
With terminal lug kit    
Cross section per UL/CSA [AWG]  
Recommended torque [lb-in]  
With Frame Terminal Block        
Click to enlarge - 140M-29-4   top opening
bottom opening
[mm2]
[mm2]
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 top opening
bott. opening
[mm2]
[mm2]
Click to enlarge - Contractors2_30-13 b max.
s top
s bottom
[mm]
[mm]
[mm]
Recommended torque [Nm]  
Cross section per UL/CSA top [AWG]  
bottom [AWG]  
Recommended torque [lb-in]  
  
¬ Pozidriv No. 2 / Blade No. 3 screw
T Pozidriv No. 2 / Blade No. 4 screw
‡ Hexagonal socket screw

  100S-D
95 110 95 110 140 180 210 250 300 420 630 860
Coil Type : Conventional X X X X
Electronic — EI X X X X X X X X X X
Conductor Cross Sections - Main Contacts
Terminal type
Click to enlarge - Contractors2_31-1 Click to enlarge - Contractors2_31-1 Click to enlarge - Contractors2_31-1 Click to enlarge - Contractors2_31-1
Click to enlarge - 140M-29-4   (1) conductor
(2) conductors
[mm2]
[mm2]





Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 (1) conductor
(2) conductors
[mm2]
[mm2]





Click to enlarge - Contactors_2-30-9 Click to enlarge - 140M-29-6 b max. [mm] 20 25 30 52 52
Click to enlarge - 140M-29-6 c max. [mm] 10 12.5 15 22 22
Click to enlarge - 140M-29-6 s max. [mm] 5 5 6 2 x 8 2 x 8
Click to enlarge - 140M-29-6 Æ min. [mm] 6.1 8.3 10.5 13 13
Recommended torque Click to enlarge - 140M-29-6 [Nm] 8…10 10…12 16 68 68
Cross section per UL/CSA Click to enlarge - 140M-29-6 [AWG]
Recommended torque Click to enlarge - 140M-29-6 [lb-in] 70…90 90…110 130…150 600 600
With terminal lug kit Click to enlarge - 140M-29-6 100-DL110‡  100-DLE110‡  100-DL180‡  100-DL420‡  100-DL630 100-DL860
Cross section per UL/CSA Click to enlarge - 140M-29-6 [AWG] 8…2/0 8…2/0 6…300 MCM (2x) 4…350 MCM (2X) 2/0…
500MCM
(4X) 2/0…
500MCM
Recommended torque Click to enlarge - 140M-29-6 [lb-in] 90 90 250 250 400 400
With Frame Terminal Block     Click to enlarge - 140M-29-6 100-DTB110‡  100-DTB180‡  100-DTB420¬ 
Click to enlarge - 140M-29-4   top opening
bottom opening
[mm2]
[mm2]
16…35
16…70
16…35
16…95
25…240§ 
25…240
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 top opening
bott. opening
[mm2]
[mm2]
16…50
16…95
16…50
16…120
25…300
25…300
Click to enlarge - Contractors2_30-13   b max.
s top
s bottom
[mm]
[mm]
[mm]
16
3…9
3…12
20
3…9
3…14
25
4…20
4…20
Recommended torque Click to enlarge - 140M-29-6 [Nm] 8…10 10…12 20…25
Cross section per UL/CSA top Click to enlarge - 140M-29-6 [AWG] 6…1 / 0 AWG 6…1 / 0 AWG 4 AWG…600 MCM
bottom Click to enlarge - 140M-29-6 [AWG] 6…3 / 0 AWG 6 AWG…250 MCM 4 AWG…600 MCM
Recommended torque Click to enlarge - 140M-29-6 [lb-in] 70…90 90…110 180…220
     
  ¬ Pozidriv No. 2 / Blade No. 3 screw
T Pozidriv No. 2 / Blade No. 4 screw
‡ Hexagonal socket screw
§ Hexagonal screw
§ 25…95 mm2 with sleeve per DIN 46228

Coil Data

  100S/104S-C
  09 12 16 23 30 37 40*200 40*400 43 60 72 85 90*200 90*400
Coil Type : Conventional X X X X X X X X X X X X X X
Electronic — EI
Operating Limits
50 Hz, 60 Hz, 50/60 Hz pick-up [x Us] 0.85…1.1 0.85….1.1 0.85….1.1
dropout [x Us] 0.3…0.6 0.3…0.6 0.3…0.6
DC control pick-up [x Us] 0.8…1.1 0.8…1.1 0.8…1.1
dropout [x Us] 0.1…0.6 0.1…0.6 0.1…0.6
Coil Consumption
50 Hz, 60 Hz, 50/60 Hz pick-up [VA/W] 70/50 70/50 80/60 130/90 130/90 200/110 400/240
hold-in [VA/W] 8/2.6 9/3 9/3 12/3.6 10/3.2 16/4.5 24/9
DC control pick-up [W] 6.5 9.2 9.2 10.1 10.1 200 325
hold-in [W] 6.5 9.2 9.2 10.1 10.1 4.5 5.5
Operating Times
AC closing delay [ms] 15…30 15…30 15…30 15…30 15…30 20…40 20…30
opening delay [ms] 10…60 10…60 10…60 10…60 10…60 10…60 20…40
With RC module opening delay [ms] 10…60 10…60 10…60 10…60 10…60 10…60 20…40
DC closing delay [ms] 40…70 40…70 50…80 50…80 50…80 20…40 15…25 20…25
opening delay [ms] 7…15 7…15 7…15 7…15 7…15 20…25
With integrated diode opening delay [ms] 14…20 17…23 17…23 17…23 £ 220V 20…35
With external diode opening delay [ms] 70…95 80…125 80…125 80…125 £ 220V 80…125
  

  100S-D
95/110 140/180 95 110 140 180 210 250 300 420 630 860
Coil Type : Conventional X X
Electronic — EI X X X X X X X X X X
Operating Limits
50 Hz, 60 Hz, 50/60 Hz pick-up [x Us] 0.85…1.1 0.85…1.1 0.8…1.1
dropout [x Us] 0.3…0.6 0.3…0.5 0.3…0.8
DC control pick-up [x Us] 0.85…1.1 0.85…1.1 0.85…1.1
dropout [x Us] 0.3…0.6 0.3…0.5 0.3…0.8
Coil Consumption
50 Hz, 60 Hz, 50/60 Hz pick-up [VA/W] 650/310 380/240¬  490/270¬  1915/1720¬ 
hold-in [VA/W] 50/10 13/6 18/7 33/30
DC control pick-up [W] 540 265ยน 340¬  1980¬ 
hold-in [W] 8 6 7 30
Operating Times
AC closing delay [ms] 20…47 20…45 60…100
opening delay [ms] 6…12 25…110 70…145
With RC module opening delay [ms] 9…18
DC closing delay [ms] 27…47 25…50 60…100
opening delay [ms] 12…20 35…110 70…145
With integrated diode opening delay [ms] 12…20
With external diode opening delay [ms]
  
¬ Electronic coil drives are designed to minimize power requirements, but this control may exhibit a higher inrush (540W, < 10 ms) when energizing. This must be taken into account for the proper sizing of supply devices, all-or-nothing relays and cross-sections of coil supply lines. Please contact your nearest Rockwell Automation distributor for detailed information.