| Ie [A]
|
Switching of 3-phase motors AC-2, AC-3
|
Coil Type
|
Auxiliary contacts
|
Cat. No.♦
|
| 60 °C
|
40 °C
|
kW (50 Hz)⋆
|
Hp (60 Hz)
|
N.O.
|
N.C.
|
| AC-3
|
AC-1
|
230V
|
400V
|
415V
|
500V
|
690V
|
1000V
|
200V
|
230V
|
460V
|
575V
|
|
|
| 115
|
250
|
37
|
63
|
66/75♣
|
80
|
111
|
63
|
40
|
40
|
75
|
100
|
Conventional
|
2
|
2
|
100S-D115Ä22BC
|
| 115
|
250
|
37
|
63
|
66/75♣
|
80
|
111
|
63
|
40
|
40
|
75
|
100
|
Electronic
|
2
|
2
|
100S-D115Ä22BC
|
| 140
|
250
|
45
|
78
|
82/90♣
|
80/100§
|
110/132§
|
75
|
40
|
50
|
100
|
125
|
Conventional
|
2
|
2
|
100S-D140Ä22BC
|
| 140
|
250
|
45
|
78
|
82/90♣
|
80/100§
|
110/132§
|
75
|
40
|
50
|
100
|
125
|
Electronic
|
2
|
2
|
100S-D140Ä22BC
|
| 180
|
250
|
55
|
101
|
100♣
|
90/125§
|
132/160§
|
90
|
50
|
60
|
150
|
150
|
Conventional
|
2
|
2
|
100S-D180Ä22BC
|
| 180
|
250
|
55
|
101
|
100♣
|
90/125§
|
132/160§
|
90
|
50
|
60
|
150
|
150
|
Electronic
|
2
|
2
|
100S-D180Ä22BC
|
| 210
|
350
|
63
|
118
|
110♣
|
205
|
200
|
110
|
60
|
75
|
150
|
200
|
Electronic
|
2
|
2
|
100S-D210Ä22BC
|
| 250
|
350
|
80
|
140
|
150♣
|
250
|
250
|
133
|
75
|
100
|
200
|
250
|
Electronic
|
2
|
2
|
100S-D250Ä22BC
|
| 300
|
450
|
90
|
170
|
160♣
|
290
|
300
|
160
|
100
|
125
|
250
|
300
|
Electronic
|
2
|
2
|
100S-D300Ä22BC
|
| 420
|
540
|
132
|
238
|
250
|
420
|
425
|
220
|
150
|
175
|
350
|
400
|
Electronic
|
2
|
2
|
100S-D420Ä22BC
|
| 630
|
800
|
200
|
355
|
355
|
500
|
500
|
—
|
200
|
250
|
500
|
600
|
Electronic
|
2
|
2
|
100S-D630Ä22BC
|
| 860
|
1000
|
250
|
500
|
500
|
500
|
600
|
—
|
250
|
300
|
600
|
700
|
Electronic
|
2
|
2
|
100S-D860Ä22BC
|
|
|
⋆ Preferred values according to IEC 60072-1. The N.C. contacts meet IEC 60947-4 Annex F requirements for mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit. § Higher kW rating only applies to contactors with electronic coil. ♦ If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-D95Ä22BC becomes Cat. No. 100S-D95Ä22C.
|
| ♣ 415V: Values for AC-3 and AC-4 lifespan -25%
|
| Ie [A]
|
Switching of 3-phase motors AC-2, AC-3
|
Auxiliary contacts
|
Coil Type
|
Conventional Coil Cat. No.
|
Electronic Coil Cat. No.♦
|
| 60 °C
|
40 °C
|
kW (50 Hz) ⋆
|
Hp (60 Hz)
|
N.O.
|
N.C. ⋆
|
| AC-3
|
AC-1
|
230V
|
400V
|
415V
|
500V
|
690V
|
1000V
|
200V
|
230V
|
460V
|
575V
|
|
|
| 115
|
250
|
37
|
63
|
75
|
80
|
111
|
63
|
40
|
40
|
75
|
100
|
3
|
2/1L
|
Conventional
|
100S-D115Ä33LC§
|
|
100S-D115Ä22BC
|
| 140
|
250
|
45
|
78
|
75
|
80/100♣
|
110/132♣
|
75
|
40
|
50
|
100
|
125
|
3
|
2/1L
|
Conventional
|
100S-D140Ä33LC§
|
|
100S-D140Ä22BC
|
| 180
|
250
|
55
|
101
|
100
|
90/125♣
|
132/160♣
|
90
|
50
|
60
|
150
|
150
|
3
|
2/1L
|
Conventional
|
100S-D180Ä33LC§
|
|
100S-D180Ä22BC
|
| 210
|
350
|
63
|
118
|
110
|
205
|
200
|
110
|
60
|
75
|
150
|
200
|
2
|
2
|
Electronic
|
—
|
100S-D210Ä22BC
|
| 250
|
350
|
80
|
140
|
150
|
250
|
250
|
133
|
75
|
100
|
200
|
250
|
2
|
2
|
Electronic
|
—
|
100S-D250Ä22BC
|
| 300
|
450
|
90
|
170
|
160
|
290
|
300
|
160
|
100
|
125
|
250
|
300
|
2
|
2
|
Electronic
|
—
|
100S-D300Ä22BC
|
| 420
|
540
|
132
|
238
|
250
|
420
|
425
|
220
|
150
|
175
|
350
|
400
|
2
|
2
|
Electronic
|
—
|
100S-D420Ä22BC
|
| 630
|
800
|
200
|
355
|
355
|
500
|
500
|
—
|
200
|
250
|
500
|
600
|
2
|
2
|
Electronic
|
—
|
100S-D630Ä22BC
|
| 860
|
1000
|
250
|
500
|
500
|
500
|
600
|
—
|
250
|
300
|
600
|
700
|
2
|
2
|
Electronic
|
—
|
100S-D860Ä22BC
|
|
|
⋆ Preferred values according to IEC 60072-1. The N.C. contacts meet IEC 60947-4 Annex F requirements for mirror contact performance. The N.C. mirror contacts are wired in series or parallel and must be used as monitoring contacts with feedback to the safety circuit. § For conventional DC coil only. The pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts. ♣ Higher kW rating only applies to contactors with electronic coil. ♦ If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the Cat. No. Example: Cat. No. 100S-D95Ä22BC becomes Cat. No. 100S-D95Ä22C.
|
Electronic Coil w/ PLC Interface♣
|
[V]
|
24
|
42…64
|
100
|
110… 130
|
200
|
208… 277
|
200… 220
|
230… 250
|
277
|
380… 415
|
380… 440
|
440… 480
|
380… 500
|
500
|
| 100S-D115…100S-D300
|
AC, 50/60 Hz
|
EJ∆
|
EY
|
EP
|
ED
|
EG
|
EA
|
—
|
—
|
—
|
—
|
VN
|
—
|
EN
|
—
|
| 100S-D420
|
AC, 50/60 Hz
|
—
|
—
|
EP
|
ED
|
EG
|
EA
|
—
|
—
|
—
|
—
|
—
|
—
|
EN
|
—
|
| 100S-D630…100S-D860
|
AC, 50/60 Hz
|
—
|
—
|
EP
|
ED
|
EG
|
—
|
EG
|
EA
|
ET
|
EN
|
—
|
EB
|
—
|
EM
|
|
|
Electronic Coil w/ EI Interface ∆
|
[V]
|
24
|
48…72
|
110…130
|
200…255
|
| 100S-D115…100S-D300
|
DC
|
EZJ
|
EZY
|
EZD
|
EZA
|
| 100S-D420
|
DC
|
—
|
—
|
EZD
|
EZA
|
| 100S-D630…860
|
DC
|
—
|
—
|
ED
|
EA
|
|
|
|
|
Description
|
Pkg. Qty.♣
|
Cat. No.
|
|
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm
|
10
|
100-FMS
|
|
Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
|
10
|
100-FMP
|
Transparent Cover To be used with marking tag sheets
|
100
|
100-FMC
|
|
Marking Tag Adapters To be used with marking tag: System V4/V5 System V4 / V5
|
100
|
100-FMA1
|
| System 1492 W
|
100
|
100-FMA2
|
|
|
| ♣ Must be ordered in package quantities.
|
|
|
Description
|
Connection Diagram
|
Suppressor Rating
|
For Use With
|
Cat. No.
|
|
Suppressor Module for Bul. 100-D Contactors For limiting surge voltage when coil circuits are interrupted Supplied as standard on all conventional DC coil contactors and all electronic coil contactors (as part of the supply module or delivered with separate suppressor module)
|
|
RC Module (AC control) for contactors with conventional coil 21...48V, 50 Hz; 24...55V, 60 Hz
|
100-D115...100-D180
|
100-DFSC48
|
| 95...110V, 50 Hz; 110...127V, 60 Hz
|
100-DFSC110
|
| 180...277V, 50 Hz; 208...277V, 60 Hz
|
100-DFSC240
|
| 380...550V, 50 Hz; 440...600V, 60 Hz
|
100-DFSC550
|
|
Varistor Module for contactors with conventional coil 55V AC
|
100-D115...100-D420
|
100-DFSV55
|
| 56...136V AC
|
100-DFSV136
|
| 137...277V AC
|
100-DFSV277
|
| 278...600V AC
|
100-DFSV575
|
| 208...277V AC⋆
|
100-D115...100-D420
|
100-DFSV550
|
|
|
| ⋆ For overvoltage category IV (IEC 947 for 100-D...-EI) e.g., lightning protection requirements.
|
| Package Quantity = 1
|
|
|
Description
|
For Use With
|
Cat. No.
|
|
Terminal Lugs Set of two Protection class IP2X per IEC 60529 and DIN 40 050
|
100-D115
|
100-DTB110
|
| 100-D115, 100-D140, 100-D180, 100-D115E…D180E, 193-EC_F, 193-EE_F
|
100-DTB180
|
| 100-D210...100-D420, 193-EC_G, 193-EF2C, 193-EE_G
|
100-DTB420
|
|
Terminal Lugs (UL/CSA), Copper Frame Set of three
|
100-D115
|
100-DL110
|
| 100-D115E, 193-EC_F, 193-EE_F
|
100-DLE110
|
| 100-D115, 100-D140, 100-D180, 193-EC_F, 193-EE_F
|
100-DL180
|
| 100-D210…100-D420, 193-EC_G, 193-EE_G
|
100-DL420
|
| 100-D630, 100-D860, 193-EC_H, 193-EE_H
|
100-DL630
|
| 100-D630, 100-D860, 193-EC_H, 193-EE_H
|
100-DL860
|
|
Control Circuit Terminal 2 x 2.5 mm2
|
Connects to Cat. Nos. 100-D115...D180
|
100-DAT1
|
| Connects to Cat. Nos. 100-D210...D420
|
100-DAT2
|
|
Terminal Shields Set of two Protection class IP10 per IEC 60529 and DIN 40 050 For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies
|
100-D115
|
100-DTS110
|
| 100-D115…100-D180, 193-FE
|
100-DTS180
|
| 100-D210...100-D420, 193-FE
|
100-DTS420
|
|
Terminal Covers Protection class IP20 per IEC 60529 and DIN 40 050 For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies
|
100-D115…100-D180, 193-EC_F, 193-EE_F
|
100-DTC180
|
| 100-D210...100-D420, 193-EC_G, 193-EE_G
|
100-DTC420
|
| 100-D630…100-D860, 193-EC_H, 193-EE_H
|
100-DTC860
|
|
Mounting Plate Galvanized steel plate for starter combinations For direct-on-line, reversing, two-speed, wye-delta/ star-delta, and Dahlander assemblies
|
100-D115...100-D180
|
Direct-on-line
|
100-DMS180
|
| Reversing, two-speed or changeover
|
100-DMU180
|
| Y-D or Dahlander
|
100-DMY180
|
| 100-D210...100-D420
|
Direct-on-line
|
100-DMS420
|
| Reversing, two-speed or changeover
|
100-DMU420
|
| Y-D or Dahlander
|
100-DMY420
|
| 100-D630...100-D860
|
Direct-on-line
|
100-DMS860
|
| Reversing, two-speed or changeover
|
100-DMU860
|
| Y-D or Dahlander
|
100-DMY860
|
Mounting Plate For two-speed or changeover switches
|
For interlocking between 100-C60…C97 and 100-D115…D180 contactors
|
100-DMU85
|
|
|
|
|
Description
|
Circuit Diagram
|
For Use With
|
Cat. No.
|
|
Interlock — Mechanical Only No additional space required
|
|
100-D115…100-D420
|
100-DMA00
|
|
Interlock — Dual Electrical/Mechanical No additional space required Two N.C. auxiliary contacts
|
|
100-D115…100-D860
|
100-DMD02
|
Interlock — Mechanical Only No additional space required
|
|
100-D115…100-D860
|
100-DMD00
|
Interlock — Mechanical Only Provides interlocking between Bul. 100-C and Bul. 100-D contactors
|
|
100-C60…100-C97 between 100-D115…100-D180
|
100-DMC00
|
Interlock — Dual Electrical/Mechanical Provides interlocking between Bul. 100-C and Bul. 100-D contactors Two N.C. auxiliary contacts
|
|
100-C60…100-C97 between 100-D115…100-D180
|
100-DMC02
|
|
|
| Package Quantity = 1
|
| Cat. No.
|
a
|
b
|
c
|
c1
|
Æd
|
d1
|
d2
|
Æe
|
e1
|
e2
|
e3
|
e4
|
| 100S-D115
|
120
|
170
|
156
|
110.5
|
5.2
|
145
|
100
|
M6
|
16
|
38.5
|
147
|
8
|
| 100S-D115E…100S-D180E, 100S-D140, 100S-D180
|
120
|
170
|
156
|
110.5
|
5.2
|
145
|
100
|
M8
|
20
|
39
|
160
|
10
|
| 100S-D210E…100S-D420E
|
155
|
205
|
180
|
110.5
|
6.5
|
180
|
130
|
M10
|
25
|
48
|
193
|
12.5
|
| 100S-D630E…100S-D860E
|
255
|
310
|
265
|
110.5
|
10
|
230
|
225
|
M12
|
40
|
70
|
291
|
22
|
|
|
| Contactor with
|
mm
|
| Auxiliary contact block ⋆
|
100-DS1… 100-DS2…
|
a a + 13.5 each
|
| Mechanical Interlock
|
100-DM…
|
a + a
|
| Frame terminal block
|
100-DTB110 100-DTB180 100-DTB420
|
b + 7 each b + 7 each b + 8.5 each
|
| Label holder
|
|
c…+ 5
|
|
|
⋆ Conventional DC coil contactors will have an additional auxiliary contact block that will add 13.5 mm to the a dimension on the right-hand side.