Bulletin 2041

Click to enlarge - Bulletin 2041 Panel closed


Description

The Bulletin 2041 Safety Power Control combines safety circuits and power control of the redundant contactors and a safety relay. The Bulletin 2041 is TÜV certified for category 4 safety circuits. The safety circuit interface is designed to work with either light curtain outputs or safety interlock switches. The Bulletin 2041 also interfaces with Safety Monitoring Relays, Safety PLC, and GuardLogix solutions to allow for control of power circuits from 9…860 A at 600V maximum. This makes system integration quicker and easier by using a modular approach to the safety solution.

Features


Specifications

Input Line Voltage Range 600V AC maximum
Control Voltage Range 24V DC or
110/120V AC (50/60 Hz)
Enclosure Rating Type 12 (IP54)
Open Frame
System Operational Limits +10%, -15% of the line voltage
Estimated Component Life 1,000,000 operations
Storage Temperature [C (F)] -40…+80° (-40…176°)
Operating Temperature, Ambient [C (F)] -25…+40° (-13…104°)
Relative humidity 90% noncondensing
Approvals CE Marked for all applicable directives
TÜV Category 4
cULus
Standards/Certifications Category 4 systems
UL 508A
  

Product Selection

Bulletin 2041 cat. nos. can be configured by selecting the appropriate codes from the tables below.

2041 C30   J   1   1CD 7B
    a   b   c   d   e

a
Contactor Size
Code Amps [A]
C09 9
C12 12
C16 16
C23 23
C30 30
C37 37
C43 43
C60 60
C72 72
C85 85
D95 95
D110 110
D140 140
D180 180
D210 210
D250 250
D300 300
D420 420
D630 630
D860 860

b
Enclosure Type
Code Description
J Type 12/IP54
N Open (no enclosure)
components are mounted
on a sub-panel

c
Control Voltage
Code Description
1 24V DC
DJ = 9…85 A
EZJ = 95…300 A
420…860 = Not available
2 120V AC
D = 9…85 A
ED = 95…860 A

d
E3 Plus Overload Relay
(193-ECxxx)¬ 
Code Load Rating Amps [A] Starter
1PB 0.4…2.0 C09…C23
1AB 1…5
1BB 3…15
1CB 5…25
1AD 1…5 C30…C43
1BD 3…15 A
1CD 5…25
1DD 9…45
1DE 9…45 C60…C85
1EE 18…90
1FF 28…140 D95…D180
1GF 42…210
1GG 42…210 D210…D420
1HG 60…302
1JG 84…420
1KH 125…630 D630…D860
1LH 172…860
E1 Plus Overload Relay
(193-Exxx)¬ 
Code Load Rating Amps [A] Starter
EAB 0.1…0.5 C09…C23
EBB 0.2…1.0
ECB 1…5
EDB 3.2…16
EEB 5.4…27
EED 5.4…27 C30…C43
EFD 9…45
EGE 18…90 C60…C85
EHF 30…150 D95…D180
EJF 40…200
EJG 40…200 D210…D420
EKG 60…100
ELG 100…500
EMH 120…600 D630…D860
ENH 160…800

¬ If the overload relay configuration code field is left blank, an overload relay will not be provided.


e
Operator Devices
Code Description
Blank No options
7B Front mount safety reset
4R Red pilot light
(replaces standard green)

Typical Wiring Diagram

Click to enlarge - 2041 Wiring Diagram

Approximate Dimensions [mm (in.)]

Dimensions are not intended to be used for manufacturing purposes.

Type 12 Enclosure
Contactor Size Panel Dimensions
(H x W x D)
(M2) Height
[mm (in.)]
(M1) Width
[mm (in.)]
Mounting Holes
[mm (in.)]
C09…C16 12 x 10 x 8 324 (12.75) 203 (8.0) 8 (0.31)
C23…C30 16 x 12 x 10 368 (14.5) 267 (10.5) 13 (0.5)
C37…C43 16 x 12 x 10 368 (14.5) 267 (10.5) 13 (0.5)
C60…C85 16 x 12 x 10 368 (14.5) 267 (10.5) 13 (0.5)
C95…D180 24 x 24 x 10 572 (22.5) 572 (22.5) 13 (0.5)
D210 24 x 24 x 10 572 (22.5) 572 (22.5) 13 (0.5)
D250…D300 24 x 24 x 10 572 (22.5) 572 (22.5) 13 (0.5)
D420 24 x 24 x 10 572 (22.5) 572 (22.5) 13 (0.5)
D630…D860 36 x 30 x 12 572 (22.5) 724 (28.5) 13 (0.5)
 

Open Panel
Contactor Size Panel Dimensions
(H x W x D)
(MH) Height
[mm (in.)]
(MW) Width
[mm (in.)]
Mounting Holes
[mm (in.)]
C09…C16 14.5 x 6.5 x 6.1 349 (13.75) 140 (5.5) 7 (0.281)
C23…C30 14.5 x 6.5 x 7.5 349 (13.75) 140 (5.5) 7 (0.281)
C37…C43 14.5 x 6.5 x 7.6 349 (13.75) 140 (5.5) 7 (0.281)
C60…C85 14.5 x 6.5 x 6.5 349 (13.75) 140 (5.5) 7 (0.281)
C95…D180 18 x 10.5 x 6.5 429 (16.875) 242 (9.525) 9.5 (0.375)
D210 23 x 12 x 7.5 538 (21.175) 283 (11.125) 9.5 (0.375)
D250…D300 23 x 12 x 7.5 538 (21.175) 283 (11.125) 9.5 (0.375)
D420 23 x12 x 7.5 538 (21.175) 283 (11.125) 9.5 (0.375)
D630…D860 35 x 17 x 11.3 432 (17.0) 410 (16.125) 9.5 (0.375)
 

Click to enlarge - Enclosure box 1