PowerFlex 753

Click to enlarge - pf753_angl


Designed for general purpose applications, the PowerFlex 753 AC drive offers multiple options and features along with the added benefit of simple integration. The PowerFlex 753 comes standard with built-in I/O making it a cost effective solution ideal for OEMs and system integrators looking to reduce engineering costs, deliver machines to market faster and meet end-user demand for more productive and safer machines.

at a glance …
Ratings
    380…480V:
    600V:
    690V:

0.75…250 kW / 1.0…350 Hp / 2.1…456 A
1.0…300 Hp / 1.7…289 A
7.5…250 kW / 12…263 A
Motor Control
  • V/Hz Control

  • Sensorless Vector Control

  • Vector Control with FORCE Technology
         (with and without encoder)

  • Interior Permanent Magnet with and without encoder
  • Communications Multiple options for industrial networks are available (see Communication Option Kits).
    User Interface HIM (see Human Interface Modules for options)
    Enclosures
  • IP00/IP20, NEMA/UL‚ÄąType Open

  • Flange Mount

  • IP54/NEMA/UL Type 12
  • Safety
  • Safe Torque-Off PLe/SIL3 Cat. 3

  • Safe Speed Monitor PLe/SIL3 Cat. 4
  • Additional
    Features
  • DeviceLogix

  • Predictive Diagnostics

  • Adjustable Voltage Control

  • Three option slots for I/O, feedback, safety, auxiliary control power, communications

  • Indexing

  • Pump Jack and Pump Off for oil well applications

  • Pjump and Traverse for Fibers application

  • Conformal Coating

  • DC Link Choke

  • Automatic Device Configuration ⋆ 
  • Certifications
  • ABS (Frames 2…7, 400/480V AC)

  • ATEX Certified with appropriate options

  • C-Tick

  • c-UL-us

  • CE

  • EPRI/SEMI F47

  • GOST-R (Frames 2…7, 400/480V AC)

  • Lloyd's Register (Frames 2…7, 400/480V AC)

  • RINA (Frames 2...7, 400/480V AC)

  • RoHS compliant materials

  • FS ISO/EN13849-1 (EN954-1) with Safe Torque-Off option
  • Additional Information PowerFlex 750-Series Brochure, publication 750-BR001
    PowerFlex 750-Series Technical Data, publication 750-TD001
    ⋆ Requires Dual-port EtherNet/IP Option Module (Cat. No. 20-750-ENETR), firmware V7, Studio 5000 Logix Designer, and Drive Add-On Profiles Version 4.04 or higher.

    To interpret the meaning of a catalog number, match the values of the catalog number code in positions a, b, c, etc. with the tables labeled a, b, c, etc. below.

    20F   1   A   N   D   248   A   A   0   N   N   N   N   N
    a   b   c   d   e   f1…f2   g   h                        

    a
    Drive
    Code Type
    20F PowerFlex 753

    b
    Future Use

    c
    Input Type
    Code Description Frames
    1 AC Input with Precharge, includes DC Terminals 1…4
    AC Input without Precharge, includes DC Terminals 5
    4 DC Input with Precharge 5…7
    A AC Input with Precharge, no DC Terminals 6…7 ⋆ 
    ⋆ The DC Bus Bar kit (20-750-DCBB1-Fx) is available for Frames 6…7 AC input drives requiring DC bus terminals.

    d
    Enclosure
    Code Description Frames
    R IP20, NEMA/UL Type Open, Frame 1 1
    F §  Flange (NEMA/UL Type 4X/12 back) 2…5
    G IP54, NEMA/UL Type 12 2…7
    N ‡  IP20/IP00, NEMA/UL Type Open 2…7
    § For Frames 6…7 a User Installed Flange Kit is available to convert a Code N drive that provides a NEMA/UL Type 4X/12 back.
    ‡ Frames 2…5 are IP20, Frames 6…7 are IP00.

    e
    Voltage Rating
    Code Voltage
    C 400V AC/540V DC
    D 480V AC/650V DC
    E 600V AC/810V DC
    F 690V AC/932V DC (not UL listed)

    f1
    ND Rating
    400V, 50 Hz Input
    Code Amps kW Frame
    Enclosure Code
    F G N R
    2P1 2.1 0.75 2 2 2 1
    3P5 3.5 1.5
    5P0 5.0 2.2
    8P7 8.7 4
    011 11.5 5.5
    015 15.4 7.5
    022 22 11
    030 30 15 3 3 3
    037 37 18.5
    043 43 22
    060 60 30 4 4 4
    072 72 37 5
    085 85 45 5 5
    104 104 55 6
    140 140 75 §  6
    170 170 90
    205 205 110
    260 260 132 7
    302 302 160 7
    367 367 200
    456 456 250
    § For Frames 6…7 a User Installed Flange Kit is available to convert a Code N drive that provides a NEMA/UL Type 4X/12 back.

    f2
    ND Rating
    480V, 60 Hz Input
    Code Amps Hp Frame
    Enclosure Code
    F G N R
    2P1 2.1 1 2 2 2 1
    3P4 3.4 2
    5P0 5.0 3
    8P0 8.0 5
    011 11 7.5
    014 14 10
    022 22 15
    027 27 20 3 3 3
    034 34 25
    040 40 30
    052 52 40 4 4 4
    065 65 50 5
    077 77 60 5 5
    096 96 75 6
    125 125 100 §  6
    156 156 125
    186 186 150
    248 248 200 7
    302 302 250 7
    361 361 300
    415 415 350
    § For Frames 6…7 a User Installed Flange Kit is available to convert a Code N drive that provides a NEMA/UL Type 4X/12 back.

    f3
    ND Rating
    600V, 60 Hz Input
    Code Amps Hp Frame
    Enclosure Code
    F G N
    1P7 1.7 1 3 3 3
    2P7 2.7 2
    3P9 3.9 3
    6P1 6.1 5
    9P0 9 7.5
    011 11 10
    012 12 10 6 6
    017 17 15 3 3 3
    018 18 15 6 6
    022 22 20 3 3 3
    023 23 20 6 6
    024 24 20
    027 27 25 4 4 4
    028 28 25 6 6
    032 32 30 4 4 4
    033 33 30 6 6
    041 41 40 5 5 5
    042 42 40 6 6
    052 52 50 5 5
    053 53 50 6 6
    063 63 60
    077 77 75
    099 99 100
    125 125 125
    144 144 150
    192 192 200 7 7
    242 242 250
    289 289 300

    f4
    ND Rating
    690V, 50 Hz Input (not UL listed)
    Code Amps kW Frame
    Enclosure Code
    G N
    012 12 7.5 6 6
    015 15 11
    020 20 15
    023 23 18.5
    030 30 22
    034 34 30
    046 46 37
    050 50 45
    061 61 55
    082 82 75
    098 98 90
    119 119 110
    142 142 132
    171 171 160 7 7
    212 212 200
    263 263 250

    g
    Filtering and CM Cap Configuration ♦ 
    Code Filtering Default CM Cap Connection
    A Yes Jumper Removed
    J Yes Jumper Installed
    ♦ 480V drives must select code "A." Jumpers are included for field reconfiguration as desired.

    h
    Dynamic Braking
    Code Internal Resistor ♠  Internal Transistor ▶ 
    A No Yes
    N No No
    ♠ Frames 1…2 only.
    ▶ Standard on Frames 1…5, optional on 6…7.

    The catalog numbers listed below are for base drives in their respective power ratings. Click "Build a Catalog Number" to configure a drive for ordering. For detailed drive information, refer to the PowerFlex 750-Series Technical Data, publication 750-TD001.

    IP00/IP20, NEMA/UL Type Open & 

    380…480V AC, Three-Phase Drives
    480V AC Input 400V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    2.1 2.3 3.2 1 0.5 20F11RD2P1AA0NNNNN 2.1 2.3 3.2 0.75 0.37 20F11RC2P1JA0NNNNN 1
    3.4 3.7 5.1 2 1.5 20F11RD3P4AA0NNNNN 3.5 3.9 5.3 1.5 0.75 20F11RC3P5JA0NNNNN 1
    5 5.5 7.5 3 2 20F11RD5P0AA0NNNNN 5 5.5 7.5 2.2 1.5 20F11RC5P0JA0NNNNN 1
    8 8.8 12 5 3 20F11RD8P0AA0NNNNN 8.7 9.6 13.1 4 2.2 20F11RC8P7JA0NNNNN 1
    11 12.1 16.5 7.5 5 20F11RD011AA0NNNNN 11.5 12.7 17.3 5.5 4 20F11RC011JA0NNNNN 1
    14 15.4 21 10 7.5 20F11RD014AA0NNNNN 15.4 16.9 23.1 7.5 5.5 20F11RC015JA0NNNNN 1
     
    2.1 3.1 3.7 1 1 20F11ND2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20F11NC2P1JA0NNNNN 2
    3.4 5.1 6.1 2 2 20F11ND3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20F11NC3P5JA0NNNNN 2
    5 7.5 9 3 3 20F11ND5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20F11NC5P0JA0NNNNN 2
    8 12 14.4 5 5 20F11ND8P0AA0NNNNN 8.7 13 15.6 4 4 20F11NC8P7JA0NNNNN 2
    11 16.5 19.8 7.5 7.5 20F11ND011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20F11NC011JA0NNNNN 2
    14 (11) 15.4 (16.5) 21 (21) 10 7.5 20F11ND014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20F11NC015JA0NNNNN 2
    22 (14) 24.2 (21) 33 (33) 15 10 20F11ND022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20F11NC022JA0NNNNN 2
    27 (22) 29.7 (33) 40.5 (40.5) 20 15 20F11ND027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20F11NC030JA0NNNNN 3
    34 (27) 37.4 (40.5) 51 (51) 25 20 20F11ND034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20F11NC037JA0NNNNN 3
    40 (34) 44 (51) 60 (61.2) 30 25 20F11ND040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20F11NC043JA0NNNNN 3
    52 (40) 57.2 (60) 78 (78) 40 30 20F11ND052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20F11NC060JA0NNNNN 4
    65 (52) 71.5 (78) 97.5 (97.5) 50 40 20F11ND065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20F11NC072JA0NNNNN 4
    77 (65) 84.7 (97.5) 116 (117) 60 50 20F11ND077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20F11NC085JA0NNNNN 5
    96 (77) 106 (116) 144 (144) 75 60 20F11ND096AA0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20F11NC104JA0NNNNN 5
    125 (96) 138 (144) 188 (188) 100 75 20F1AND125AN0NNNNN 140 (104) 154 (156) 210 (210) 75 55 20F1ANC140JN0NNNNN 6 ♠ 
    156 (125) 172 (188) 234 (234) 125 100 20F1AND156AN0NNNNN 170 (140) 187 (210) 255 (255) 90 75 20F1ANC170JN0NNNNN 6 ♠ 
    186 (156) 205 (234) 279 (281) 150 125 20F1AND186AN0NNNNN 205 (170) 226 (255) 308 (308) 110 90 20F1ANC205JN0NNNNN 6 ♠ 
    248 (186) 273 (279) 372 (372) 200 150 20F1AND248AN0NNNNN 260 (205) 286 (308) 390 (390) 132 110 20F1ANC260JN0NNNNN 6 ♠ 
    302 (248) 332 (372) 453 (453) 250 200 20F1AND302AN0NNNNN 302 (260) 332 (390) 453 (468) 160 132 20F1ANC302JN0NNNNN 7 ♠ 
    361 (302) 397 (453) 542 (544) 300 250 20F1AND361AN0NNNNN 367 (302) 404 (453) 551 (551) 200 160 20F1ANC367JN0NNNNN 7 ♠ 
    415 (361) 457 (542) 623 (650) 350 300 20F1AND415AN0NNNNN 456 (367) 502 (551) 684 (684) 250 200 20F1ANC456JN0NNNNN 7 ♠ 
    & Frames 2…5 are IP20, Frames 6…7 are IP00.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ♠ Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).
    § Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    Frames 3, 4 and 5 are 600V only drives. Frames 6 and 7 are dual voltage drives and can be operated at 600V or 690V AC.
    Important: Frames 3, 4, and 5 must NOT be used in common DC input sharing applications with Frame 6 or larger drives. For details, contact your local Rockwell Automation sales office or Allen-Bradley Distributor.

    DC Bus terminals are not supplied with AC input Frame 6 and 7 drives.


    600V AC, Three-Phase Drives – IP20, NEMA/UL Type 1
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
    Cont. 1 Min. 3 Sec.
    1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20F11NE1P7AA0NNNNN 3
    2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20F11NE2P7AA0NNNNN 3
    3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20F11NE3P9AA0NNNNN 3
    6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20F11NE6P1AA0NNNNN 3
    9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20F11NE9P0AA0NNNNN 3
    11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20F11NE011AA0NNNNN 3
    17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20F11NE017AA0NNNNN 3
    22 (17) 24 (26) 33 (46) 20 15 20F11NE022AA0NNNNN 3
    27 (22) 30 (33) 41 (59) 25 20 20F11NE027AA0NNNNN 4
    32 (27) 35 (41) 48 (73) 30 25 20F11NE032AA0NNNNN 4
    41 (32) 45 (48) 62 (86) 40 30 20F11NE041AA0NNNNN 5
    52 (41) 57 (62) 78 (111) 50 40 20F11NE052AA0NNNNN 5
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    600…690V AC, Three-Phase Drives – IP00, NEMA/UL Type Open
    600V AC Input 690V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    12 (9.1) 13.2 (13.7) 18 (18) 10 ‡  7.5 20F1ANE012AN0NNNNN 12 (9) 13.2 (13.5) 18 (18) 7.5 5.5 20F1ANF012JN0NNNNN 6 ♠ 
    18 (11.1) 19.8 (16.7) 27 (27) 15 ‡  10 20F1ANE018AN0NNNNN 15 (11.5) 16.5 (17.3) 22.5 (22.5) 11 7.5 20F1ANF015JN0NNNNN 6 ♠ 
    23 (18) 25.3 (27) 34.5 (34.5) 20 ‡  15 20F1ANE023AN0NNNNN 20 (15) 22 (22.5) 30 (30) 15 11 20F1ANF020JN0NNNNN 6 ♠ 
    24 (22) 26.4 (33) 36 (39.6) 20 ‡  20 20F1ANE024AN0NNNNN 23 (20) 25.3 (30) 34.5 (36) 18.5 15 20F1ANF023JN0NNNNN 6 ♠ 
    28 (23) 30.8 (34.5) 42 (42) 25 ‡  20 20F1ANE028AN0NNNNN 30 (23) 33 (34.5) 45 (45) 22 18.5 20F1ANF030JN0NNNNN 6 ♠ 
    33 (28) 36.3 (42) 49.5 (50.4) 30 ‡  25 20F1ANE033AN0NNNNN 34 (30) 37.4 (45) 51 (54) 30 22 20F1ANF034JN0NNNNN 6 ♠ 
    42 (33) 46.2 (49.5) 63 (63) 40 ‡  30 20F1ANE042AN0NNNNN 46 (34) 50.6 (51) 69 (69) 37 30 20F1ANF046JN0NNNNN 6 ♠ 
    53 (42) 58.3 (63) 79.5 (79.5) 50 ‡  40 20F1ANE053AN0NNNNN 50 (46) 55 (69) 75 (82.8) 45 37 20F1ANF050JN0NNNNN 6 ♠ 
    63 (52) 69.3 (78) 94.5 (94.5) 60 50 20F1ANE063AN0NNNNN 61 (50) 67.1 (75) 91.5 (91.5) 55 45 20F1ANF061JN0NNNNN 6 ♠ 
    77 (63) 84.7 (94.5) 116 (116) 75 60 20F1ANE077AN0NNNNN 82 (61) 90.2 (91.5) 123 (123) 75 55 20F1ANF082JN0NNNNN 6 ♠ 
    99 (77) 109 (116) 149 (149) 100 75 20F1ANE099AN0NNNNN 98 (82) 108 (123) 147 (148) 90 75 20F1ANF098JN0NNNNN 6 ♠ 
    125 (99) 138 (149) 188 (188) 125 100 20F1ANE125AN0NNNNN 119 (98) 131 (147) 179 (179) 110 90 20F1ANF119JN0NNNNN 6 ♠ 
    144 (125) 158 (188) 216 (225) 150 125 20F1ANE144AN0NNNNN 142 (119) 156 (179) 213 (214) 132 110 20F1ANF142JN0NNNNN 6 ♠ 
    192 (144) 211 (216) 288 (288) 200 150 20F1ANE192AN0NNNNN 171 (142) 188 (213) 257 (257) 160 132 20F1ANF171JN0NNNNN 7 ♠ 
    242 (192) 266 (288) 363 (363) 250 200 20F1ANE242AN0NNNNN 212 (171) 233 (257) 318 (318) 200 160 20F1ANF212JN0NNNNN 7 ♠ 
    289 (242) 318 (318) 434 (436) 300 250 20F1ANE289AN0NNNNN 263 (212) 289 (289) 395 (395) 250 200 20F1ANF263JN0NNNNN 7 ♠ 
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ‡ Alternate 600V ratings when connected to drives 60 Hp and greater in common DC input applications with uncontrolled front ends.
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♠ Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).

    Flange Mount
    Front = IP20, NEMA/UL Type Open, Back/Heatsink = IP66, NEMA/UL Type 4X


    380…480V AC, Three-Phase Drives
    480V AC Input 400V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    2.1 3.1 3.7 1 1 20F11FD2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20F11FC2P1JA0NNNNN 2
    3.4 5.1 6.1 2 2 20F11FD3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20F11FC3P5JA0NNNNN 2
    5 7.5 9 3 3 20F11FD5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20F11FC5P0JA0NNNNN 2
    8 12 14.4 5 5 20F11FD8P0AA0NNNNN 8.7 13 15.6 4 4 20F11FC8P7JA0NNNNN 2
    11 16.5 19.8 7.5 7.5 20F11FD011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20F11FC011JA0NNNNN 2
    14 (11) 15.4 (16.5) 21 (21) 10 7.5 20F11FD014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20F11FC015JA0NNNNN 2
    22 (14) 24.2 (21) 33 (33) 15 10 20F11FD022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20F11FC022JA0NNNNN 2
    27 (22) 29.7 (33) 40.5 (40.5) 20 15 20F11FD027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20F11FC030JA0NNNNN 3
    34 (27) 37.4 (40.5) 51 (51) 25 20 20F11FD034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20F11FC037JA0NNNNN 3
    40 (34) 44 (51) 60 (61.2) 30 25 20F11FD040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20F11FC043JA0NNNNN 3
    52 (40) 57.2 (60) 78 (78) 40 30 20F11FD052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20F11FC060JA0NNNNN 4
    65 (52) 71.5 (78) 97.5 (97.5) 50 40 20F11FD065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20F11FC072JA0NNNNN 4
    77 (65) 84.7 (97.5) 116 (117) 60 50 20F11FD077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20F11FC085JA0NNNNN 5
    96 (77) 106 (116) 144 (144) 75 60 20F11FD096AA0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20F11FC104JA0NNNNN 5
    Note: Frames 6…7 require a user installed flange kit with an IP00, NEMA/UL Type Open drive.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    § Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    600V AC, Three-Phase Drives
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
    Cont. 1 Min. 3 Sec.
    1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20F11FE1P7AA0NNNNN 3
    2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20F11FE2P7AA0NNNNN 3
    3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20F11FE3P9AA0NNNNN 3
    6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20F11FE6P1AA0NNNNN 3
    9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20F11FE9P0AA0NNNNN 3
    11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20F11FE011AA0NNNNN 3
    17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20F11FE017AA0NNNNN 3
    22 (17) 24 (26) 33 (46) 20 15 20F11FE022AA0NNNNN 3
    27 (22) 30 (33) 41 (59) 25 20 20F11FE027AA0NNNNN 4
    32 (27) 35 (41) 48 (73) 30 25 20F11FE032AA0NNNNN 4
    41 (32) 45 (48) 62 (86) 40 30 20F11FE041AA0NNNNN 5
    52 (41) 57 (62) 78 (111) 50 40 20F11FE052AA0NNNNN 5
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    IP54, NEMA/UL Type 12

    380…480V AC, Three-Phase Drives
    480V AC Input 400V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    2.1 3.1 3.7 1 1 20F11GD2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20F11GC2P1JA0NNNNN 2
    3.4 5.1 6.1 2 2 20F11GD3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20F11GC3P5JA0NNNNN 2
    5 7.5 9 3 3 20F11GD5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20F11GC5P0JA0NNNNN 2
    8 12 14.4 5 5 20F11GD8P0AA0NNNNN 8.7 13 15.6 4 4 20F11GC8P7JA0NNNNN 2
    11 16.5 19.8 7.5 7.5 20F11GD011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20F11GC011JA0NNNNN 2
    14 (11) 15.4 (16.5) 21 (21) 10 7.5 20F11GD014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20F11GC015JA0NNNNN 2
    22 (14) 24.2 (21) 33 (33) 15 10 20F11GD022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20F11GC022JA0NNNNN 2
    27 (22) 29.7 (33) 40.5 (40.5) 20 15 20F11GD027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20F11GC030JA0NNNNN 3
    34 (27) 37.4 (40.5) 51 (51) 25 20 20F11GD034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20F11GC037JA0NNNNN 3
    40 (34) 44 (51) 60 (61.2) 30 25 20F11GD040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20F11GC043JA0NNNNN 3
    52 (40) 57.2 (60) 78 (78) 40 30 20F11GD052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20F11GC060JA0NNNNN 4
    65 (52) 71.5 (78) 97.5 (97.5) 50 40 20F11GD065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20F11GC072JA0NNNNN 5
    77 (65) 84.7 (97.5) 116 (117) 60 50 20F11GD077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20F11GC085JA0NNNNN 5
    96 (77) 106 (116) 144 (144) 75 60 20F1AGD096AN0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20F1AGC104JN0NNNNN 6 ♠ 
    125 (96) 138 (144) 188 (188) 100 75 20F1AGD125AN0NNNNN 140 (104) 154 (156) 210 (210) 75 55 20F1AGC140JN0NNNNN 6 ♠ 
    156 (125) 172 (188) 234 (234) 125 100 20F1AGD156AN0NNNNN 170 (140) 187 (210) 255 (255) 90 75 20F1AGC170JN0NNNNN 6 ♠ 
    186 (156) 205 (234) 279 (281) 150 125 20F1AGD186AN0NNNNN 205 (170) 226 (255) 308 (308) 110 90 20F1AGC205JN0NNNNN 6 ♠ 
    248 (186) 273 (279) 372 (372) 200 150 20F1AGD248AN0NNNNN 260 (205) 286 (308) 390 (390) 132 110 20F1AGC260JN0NNNNN 7 ♠ 
    302 (248) 332 (372) 453 (453) 250 200 20F1AGD302AN0NNNNN 302 (260) 332 (390) 453 (468) 160 132 20F1AGC302JN0NNNNN 7 ♠ 
    361 (302) 397 (453) 542 (544) 300 250 20F1AGD361AN0NNNNN 367 (302) 404 (453) 551 (551) 200 160 20F1AGC367JN0NNNNN 7 ♠ 
    415 (361) 457 (542) 623 (650) 350 300 20F1AGD415AN0NNNNN 456 (367) 502 (551) 684 (684) 250 200 20F1AGC456JN0NNNNN 7 ♠ 
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ♠ Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).
    § Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    Frames 3, 4 and 5 are 600V only drives. Frames 6 and 7 are dual voltage drives and can be operated at 600V or 690V AC.
    Important: Frames 3, 4, and 5 must NOT be used in common DC input sharing applications with Frame 6 or larger drives. For details, contact your local Rockwell Automation sales office or Allen-Bradley Distributor.

    DC Bus terminals are not supplied with AC input Frame 6 and 7 drives.


    600V AC, Three-Phase Drives
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
    Cont. 1 Min. 3 Sec.
    1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20F11GE1P7AA0NNNNN 3
    2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20F11GE2P7AA0NNNNN 3
    3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20F11GE3P9AA0NNNNN 3
    6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20F11GE6P1AA0NNNNN 3
    9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20F11GE9P0AA0NNNNN 3
    11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20F11GE011AA0NNNNN 3
    17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20F11GE017AA0NNNNN 3
    22 (17) 24 (26) 33 (46) 20 15 20F11GE022AA0NNNNN 3
    27 (22) 30 (33) 41 (59) 25 20 20F11GE027AA0NNNNN 4
    32 (27) 35 (41) 48 (73) 30 25 20F11GE032AA0NNNNN 4
    41 (32) 45 (48) 62 (86) 40 30 20F11GE041AA0NNNNN 5
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    600…690V AC, Three-Phase Drives
    600V AC Input 690V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    12 (9.1) 13.2 (13.7) 18 (18) 10 ‡  7.5 20F1AGE012AN0NNNNN 12 (9) 13.2 (13.5) 18 (18) 7.5 5.5 20F1AGF012JN0NNNNN 6 ♠ 
    18 (11.1) 19.8 (16.7) 27 (27) 15 ‡  10 20F1AGE018AN0NNNNN 15 (11.5) 16.5 (17.3) 22.5 (22.5) 11 7.5 20F1AGF015JN0NNNNN 6 ♠ 
    23 (18) 25.3 (27) 34.5 (34.5) 20 ‡  15 20F1AGE023AN0NNNNN 20 (15) 22 (22.5) 30 (30) 15 11 20F1AGF020JN0NNNNN 6 ♠ 
    24 (22) 26.4 (33) 36 (39.6) 20 ‡  20 20F1AGE024AN0NNNNN 23 (20) 25.3 (30) 34.5 (36) 18.5 15 20F1AGF023JN0NNNNN 6 ♠ 
    28 (23) 30.8 (34.5) 42 (42) 25 ‡  20 20F1AGE028AN0NNNNN 30 (23) 33 (34.5) 45 (45) 22 18.5 20F1AGF030JN0NNNNN 6 ♠ 
    33 (28) 36.3 (42) 49.5 (50.4) 30 ‡  25 20F1AGE033AN0NNNNN 34 (30) 37.4 (45) 51 (54) 30 22 20F1AGF034JN0NNNNN 6 ♠ 
    42 (33) 46.2 (49.5) 63 (63) 40 ‡  30 20F1AGE042AN0NNNNN 46 (34) 50.6 (51) 69 (69) 37 30 20F1AGF046JN0NNNNN 6 ♠ 
    53 (42) 58.3 (63) 79.5 (79.5) 50 ‡  40 20F1AGE053AN0NNNNN 50 (46) 55 (69) 75 (82.8) 45 37 20F1AGF050JN0NNNNN 6 ♠ 
    63 (52) 69.3 (78) 94.5 (94.5) 60 50 20F1AGE063AN0NNNNN 61 (50) 67.1 (75) 91.5 (91.5) 55 45 20F1AGF061JN0NNNNN 6 ♠ 
    77 (63) 84.7 (94.5) 116 (116) 75 60 20F1AGE077AN0NNNNN 82 (61) 90.2 (91.5) 123 (123) 75 55 20F1AGF082JN0NNNNN 6 ♠ 
    99 (77) 109 (116) 149 (149) 100 75 20F1AGE099AN0NNNNN 98 (82) 108 (123) 147 (148) 90 75 20F1AGF098JN0NNNNN 6 ♠ 
    125 (99) 138 (149) 188 (188) 125 100 20F1AGE125AN0NNNNN 119 (98) 131 (147) 179 (179) 110 90 20F1AGF119JN0NNNNN 6 ♠ 
    144 (125) 158 (188) 216 (225) 150 125 20F1AGE144AN0NNNNN 142 (119) 156 (179) 213 (214) 132 110 20F1AGF142JN0NNNNN 6 ♠ 
    192 (144) 211 (216) 288 (288) 200 150 20F1AGE192AN0NNNNN 171 (142) 188 (213) 257 (257) 160 132 20F1AGF171JN0NNNNN 7 ♠ 
    242 (192) 266 (288) 363 (363) 250 200 20F1AGE242AN0NNNNN 212 (171) 233 (257) 318 (318) 200 160 20F1AGF212JN0NNNNN 7 ♠ 
    289 (242) 318 (318) 434 (436) 300 250 20F1AGE289AN0NNNNN 263 (212) 289 (289) 395 (395) 250 200 20F1AGF263JN0NNNNN 7 ♠ 
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ‡ Alternate 600V ratings when connected to drives 60 Hp and greater in common DC input applications with uncontrolled front ends.
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♠ Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).

    Human Interface Modules
                 
    Click to enlarge - 20him_blank Click to enlarge - 20him_a3 Click to enlarge - 20him_a5 Click to enlarge - 20him_a6 Click to enlarge - 20him_c3s Click to enlarge - 20him_c5s Click to enlarge - 20him_c6s
    Blank Plate 20-HIM-A3 20-HIM-A5 20-HIM-A6 20-HIM-C3S 20-HIM-C5S 20-HIM-C6S

    Human Interface Modules
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    No HIM (Blank Plate), Handheld/Local (Drive Mount) 20-HIM-A0 ü ü ü ü ü ü
    LCD Display, Full Numeric Keypad, Handheld/Local (Drive Mount) 20-HIM-A3 ü ü ü ü ü  
    LCD Display, Programmer Only, Handheld/Local (Drive Mount) 20-HIM-A5 ü ü ü ü ü  
    Enhanced, LCD, Full Numeric Keypad, Handheld/Local (Drive Mount) 20-HIM-A6 ü ü ü ü ü ü § 
    Remote (Panel Mount) LCD Display, Full Numeric Keypad ⋆ ‡  20-HIM-C3S ü ü ü ü ü  
    Remote (Panel Mount) LCD Display, Programmer Only ⋆ ‡  20-HIM-C5S ü ü ü ü ü  
    Enhanced, LCD, Full Numeric Keypad ⋆ ‡  20-HIM-C6S ü ü ü ü ü ü ♦ 
    ⋆ IP66, NEMA Type 4X/12 - For indoor use only.
    ‡ Includes a 1202-C30 interface cable (3 meters) for connection to drive.
    § Select for Frames 2…5 IP54, NEMA/UL Type 12 drives.
    ♦ Select for Frames 6…7 IP54, NEMA/UL Type 12 drives.

    Human Interface Module Accessories
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Bezel Kit for LCD HIMs, NEMA Type 1 ‡  20-HIM-B1 ü ü ü ü ü ü
    PowerFlex HIM Interface Cable, 1 m (39 in) ♣  20-HIM-H10 ü ü ü ü ü ü
    Comm Option Cable Kit (Male-Male)              
    0.33 Meters (1.1 Feet) 1202-C03 ü ü ü ü ü ü
    1 Meter (3.3 Feet) 1202-C10 ü ü ü ü ü ü
    3 Meter (9.8 Feet) 1202-C30 ü ü ü ü ü ü
    9 Meter (29.5 Feet) 1202-C90 ü ü ü ü ü ü
    Cable Kit (Male-Female) ∆               
    0.33 Meters (1.1 Feet) 1202-H03 ü ü ü ü ü ü
    1 Meter (3.3 Feet) 1202-H10 ü ü ü ü ü ü
    3 Meter (9.8 Feet) 1202-H30 ü ü ü ü ü ü
    9 Meter (29.5 Feet) 1202-H90 ü ü ü ü ü ü
    DPI™ Cable Kit with Connectors, Tools and 100 m (328 ft) Cable 1202-CBL-KIT-100M ü ü ü ü ü ü
    DPI Cable Connector Kit 1202-TB-KIT-SET ü ü ü ü ü ü
    DPI/SCANport™ One to Two Port Splitter Cable 1203-S03 ü ü ü ü ü ü
    ‡ Includes a 1202-C30 interface cable (3 meters) for connection to drive.
    ♣ Required only when HIM is used as handheld or remote.
    ∆ Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 Meters (32.8 Feet).

    Communication Option Kits
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    BACnet/IP Option Module 20-750-BNETIP           ü
    BACnet® MS/TP RS485 Communication Adapter 20-COMM-B ü ü ü      
    Coaxial ControlNet™ Option Module 20-750-CNETC           ü
    ControlNet™ Communication Adapter (Coax) 20-COMM-C ü ü ü ü ü ü § 
    ControlNet™ Communication Adapter (Coax) Conformal Coat 20-COMM-C-MX3 ü ü ü ü ü ü § 
    DeviceNet™ Option Module 20-750-DNET           ü
    DeviceNet™ Communication Adapter 20-COMM-D ü ü ü ü ü ü § 
    DeviceNet™ Communication Adapter Conformal Coat 20-COMM-D-MX3 ü ü ü ü ü ü § 
    Dual-port EtherNet/IP Option Module 20-750-ENETR           ü
    EtherNet/IP™ Communication Adapter 20-COMM-E ü ü ü ü ü ü § 
    EtherNet/IP™ Communication Adapter Conformal Coat 20-COMM-E-MX3 ü ü ü ü ü ü § 
    Dual-port EtherNet/IP™ Communication Adapter 20-COMM-ER ü ü ü ü ü  
    HVAC Communication Adapter 20-COMM-H ü ü ü ü ♠  ü ü § 
    CANopen® Communication Adapter 20-COMM-K ü ü ü ü ü ü § 
    LonWorks® Communication Adapter 20-COMM-L ü ü ü     ü § 
    Modbus/TCP Communication Adapter 20-COMM-M ü ü ü ü ü ü § 
    Profibus DPV1 Option Module 20-750-PBUS           ü
    Single-port Profinet I/O Option Module 20-750-PNET           ü ♣ 
    Dual-port Profinet I/O Option Module 20-750-PNET2P           ü ♣ 
    PROFIBUS™ DP Communication Adapter 20-COMM-P ü ü ü ü ü ü § 
    ControlNet™ Communication Adapter (Fiber) 20-COMM-Q ü ü ü ü ü ü § & 
    Remote I/O Communication Adapter ∆  20-COMM-R ü ü ü ü ü ü § 
    Remote I/O Communication Adapter Conformal Coat ∆  20-COMM-R-MX3 ü ü ü ü ü ü § 
    RS485 DF1 Communication Adapter 20-COMM-S ü ü ü ü ü ü § 
    RS485 DF1 Communication Adapter Conformal Coat 20-COMM-S-MX3 ü ü ü ü ü ü § 
    External Communications Kit Power Supply 20-XCOMM-AC-PS1 ü ü ü ü ü ü
    DPI External Communications Kit 20-XCOMM-DC-BASE ü ü ü ü ü ü
    External DPI I/O Option Board ♦  20-XCOMM-IO-OPT1 ü ü ü ü ü ü
    Compact I/O Module (3 Channel) 1769-SM1 ü ü ü ü ü ü
    DriveLogix ControlNet Communication Adapter (Coax) ‡  1788-CNC       ü ü ▶   
    DriveLogix Comm Option, ControlNet Redundant (Coax) ‡  1788-CNCR       ü ü ▶   
    DriveLogix Comm Option, ControlNet (Fiber) ‡  1788-CNF       ü ü ▶   
    DriveLogix Comm Option, ControlNet Redundant (Fiber) ‡  1788-CNFR       ü ü ▶   
    DriveLogix Comm Option, DeviceNet (Open Conn.) ‡  1788-DNBO       ü ü ▶   
    DriveLogix Comm Option, EtherNet/IP (Twisted Pair) ‡  1788-ENBT       ü ü ▶   
    DriveLogix5730 Comm Option, Embedded EtherNet/IP 20D-DL2-ENET0       ü ü ▶   
    ♦ For use only with DPI External Communications Kits 20-XCOMM-DC-BASE.
    ♠ Only Modbus RTU can be used.
    ‡ For use with DriveLogix option only. Requires Logix Expansion Board (20D-DL2-LEB0).
    § Requires a Communication Carrier Card (20-750-20COMM or 20-750-20COMM-F1). Refer to PowerFlex 750-Series Legacy Communication Compatibility for compatibility details.
    ▶ When using a PowerFlex 700S control.
    ∆ This item has Silver Series status. For information, refer to http://www.ab.com/silver.
    & Not supported in Frame 1.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    PowerFlex 750-Series Legacy Communication Compatibility

    Most legacy communication adapters (20-COMM) can be used with the PowerFlex 753/755. However, the restrictions stated below do apply.

    Frame 1 - It is recommended that the 20-750-20COMM-F1 Communication Carrier Card only be installed in Port 4. Port 5 will not be accessible when this module is installed.

    Frames 2 and larger - It is recommended that the 20-750-20COMM Communication Carrier Card be installed in Port 6. Using Port 4 or 5 will make the adjacent left port inaccessible to other option modules and may interfere with network cable connections.


    Adapter Accesses Ports 2, 3 and 6
    for I/O Connections
    (Implicit & Explicit Messaging)
    Accesses Port 7…14 Devices Supports Drive Add On Profiles Supports Asian-Languages ♦ 
    20-COMM-B Not Compatible
    20-COMM-C ü‡  ü v3.001 ♣  ü ∆  ü v3.001 ♣ 
    20-COMM-D Not Compatible
    20-COMM-E ü v4.001 ♣  ü ∆  ü v4.001 ♣ 
    20-COMM-H ü v2.009 §  Not Compatible
    20-COMM-K ü v1.001 ♣ 
    20-COMM-L ü v1.007 ♣ 
    20-COMM-M ü‡  ü v2.001 ♣  Not Compatible ü v2.001 ♣ 
    20-COMM-Q ü‡  ü v3.001 ♣  ü ∆  ü v3.001 ♣ 
    20-COMM-R Not Compatible
    20-COMM-S
    ‡ Controller must be capable of reading/writing 32-bit floating point (REAL) values.
    § Supports all three modes of operation (RTU, P1, N2).
    ♣ Requires this adapter firmware version or higher.
    ∆ Requires firmware version v1.05 or higher of the drive Add On Profiles for Studio 5000 Logix Designer software.
    ♦ Chinese, Japanese, and Korean languages are supported at the time of publication.

    Communication Accessories
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Serial Null Modem Adapter 1203-SNM ü ü ü ü ü ü
    Smart Self-powered Serial Converter (RS232) includes 1203-SFC and 1202-C10 Cables 1203-SSS ü ü ü ü ü ü
    Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables 1203-USB ü ü ü ü ü ü
    ControlNet T-tap straight 1786-TPS           ü
    ControlNet T-tap right angle 1786-TPR       ü ü  
    Communication Carrier Card for PowerFlex 750-Series Frame 1 drives 20-750-20COMM-F1           ü
    Communication Carrier Card for PowerFlex 750-Series Frame 2 or higher drives 20-750-20COMM           ü
      

    I/O Option Kits
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    24V DC Digital Inputs (6) w/Analog I/O (4), Slot A ♠  20C-DA1-A     ü      
    115V AC Digital Inputs (6) w/Analog I/O (4), Slot A ♠  20C-DA1-B     ü      
    115V AC Digital Outputs (3), Slot B ♠  20C-DO1     ü      
    ATEX Option Module with 1 Thermosensor Input Connection (requires 11-Series I/O Module below) 20-750-ATEX           ü § 
    24V DC 11-Series I/O Module with 1 Analog In, 1 Analog Out, 3 Digital In and 2 Relay Outputs 20-750-1132C-2R           ü § 
    24V DC 11-Series I/O Module with 1 Analog In, 1 Analog Out, 3 Digital In, 1 Relay & 2 Transistor Outputs 20-750-1133C-1R2T           ü § 
    115V AC 11-Series I/O Module with 1 Analog In, 1 Analog Out, 3 Digital In and 2 Relay Outputs 20-750-1132D-2R           ü § 
    24V DC 22-Series I/O Module with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs 20-750-2262C-2R           ü § 
    115V AC 22-Series I/O Module with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs 20-750-2262D-2R           ü § 
    24V DC 22-Series I/O Module with 2 Analog In, 2 Analog Out, 6 Digital In, 3 Digital Out, 1 Relay & 2 Transistor Outputs 20-750-2263C-1R2T           ü § 
    ♠ Only one card allowed per slot.
    § I/O option kits are not allowed in CIP motion mode.

    Safety Options
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    DriveGuard Safe Torque-Off 20A-DG01 ü          
    DriveGuard Safe Torque-Off w/2nd Encoder 20D-P2-DG01       ü ü ▶   
    Safe Torque-Off (ATEX capable) ♠  20C-DG1     ü      
    Safe Torque-Off 20-750-S           ü ⋆ 
    Safe Speed Monitor 20-750-S1           ü ⋆ ‡ 
    ♠ Only one card allowed per slot.
    ▶ When using PowerFlex 700S control. This option kit cannot be used on Frame 2 drives, however it is available as a factory installed option.
    ‡ Requires the Dual Incremental Encoder or Universal Feedback Option. Also requires the 20-750-EMCSSM1-F8 EMC Option Kit with Frame 8…9 drives.
    ⋆ Drive can accommodate only one option.

    Feedback Options
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    5V/12V Encoder &  20A-ENC-1 ü          
    12V/5V Encoder 20B-ENC-1   ü     ü  
    12V/5V Encoder with Conformal Coat 20B-ENC-1-MX3   ü        
    Multi-Device Interface ♦  20D-MDI-C2       ü ü ▶   
    2nd Encoder, 5V/12V ♦  20D-P2-ENC0       ü ü ▶   
    Resolver ♦  20D-RES-A1       ü ü ▶   
    Stegmann High Resolution Hyperface Encoder ♦  20D-STEG-B1       ü ü ▶   
    Heidenhain High Resolution EnDat Encoder 20D-HEID-D0       ü ü ▶   
    Incremental Encoder 20-750-ENC-1           ü ♠ 
    Dual Incremental Encoder 20-750-DENC-1           ü ♠ 
    Universal Feedback (includes Stegmann, Heidenhain, SSI, Biss, 5V Incremental) 20-750-UFB-1           ü ⋆ 
    & Works only with PowerFlex 70 Enhanced Control.
    ♦ Requires Expanded Cassette
    # When using a PowerFlex 700 with Vector Control.
    ⋆ PowerFlex 755 only.
    ▶ When using a PowerFlex 700S control.
    ♠ Homing and registration functions are not supported when using this device with Studio 5000 Logix Designer embedded motion instructions. To use these functions, the Universal Feedback Board (20-750-UFB-1) must be used.

    PowerFlex 700 Control Option Kits
    Control with I/O Factory Installed
    Cat. Code # 
    Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Vector Control - 24V DC with: ▶ 
    60 Hz Maximum NNAD 20B-VECT-C0AD   ü        
    82 Hz Maximum NNAX 20B-VECTB-C0AX   ü        
    Cascading Fan/Pump Control NNAE 20B-VECT-C0AE   ü        
    Pump Off (for Pump Jack) NNBA 20B-VECTB-C0BA   ü        
    Vector Control - 24V DC, Conformal Coat ▶  20B-VECTB-C0-MX3   ü        
    Vector Control - 115V AC ▶  D &  20B-VECTB-D0   ü        
    Vector Control - 115V AC with: ▶ 
    60 Hz Maximum NNAD 20B-VECT-D0AD   ü        
    82 Hz Maximum NNAX 20B-VECTB-D0AX   ü        
    Cascading Fan/Pump Control NNAE 20B-VECT-D0AE   ü        
    Pump Off (for Pump Jack) NNBA 20B-VECT-D0BA   ü        
    Vector Control - 115V AC, Conformal Coat ▶  20B-VECTB-D0-MX3   ü        
    ▶ Vector Control option utilizes DPI Only.
    # This code is entered at the end of the drive catalog number (positions 17…20).
    & This code is entered at position 15 of the drive catalog number.

    PowerFlex 750-Series Option Kits
    Description Frame Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Auxiliary Power Supply 24V Aux Power Supply 2…7 ∆  20-750-APS           ü
    DC Bus Bar Option Kit DC Bus Bars for 380…480V AC drives 6 20-750-DCBB1-F6           ü
    7 20-750-DCBB1-F7           ü
    DC Bus Bars for 600…690V AC drives 6 20-750-DCBB2-F6           ü
    7 20-750-DCBB2-F7           ü
    DC Bus Connection Kit Connects the drive DC bus terminals to the cabinet bus rails. 8…10 20-750-BUS1A-F8           ü
    EMC Option Kit EMC Plate with Core for 380…480V AC drives 1 20-750-EMC1-F1           ü
    2 20-750-EMC1-F2           ü
    3 20-750-EMC1-F3           ü
    EMC Plate with Core for 600V AC drives 3 20-750-EMC3-F3           ü
    EMC Plate with Cores for 380…480V AC drives 4 20-750-EMC1-F4           ü
    5 20-750-EMC1-F5           ü
    EMC Plate with Cores for 600V AC drives 4 20-750-EMC3-F4           ü
    5 20-750-EMC3-F5           ü
    EMC Core for 380…480V AC drives 1 20-750-EMC2-F1           ü
    2 20-750-EMC2-F2           ü
    3 20-750-EMC2-F3           ü
    EMC Core for 600V AC drives 3 20-750-EMC4-F3           ü
    EMC Cores for 380…480V AC drives 4…5 20-750-EMC2-F45           ü
    EMC Cores for 600V AC drives 4 20-750-EMC4-F4           ü
    5 20-750-EMC4-F5           ü
    EMC Plate with Cores for 600…690V AC drives 6 20-750-EMC3-F6           ü
    7 20-750-EMC3-F7           ü
    EMC Plate with Cores for 600…690V AC drives (IP54 Only) 6 20-750-EMC5-F6           ü
    7 20-750-EMC5-F7           ü
    EMC Core – Inverter-mounted output, for 380…690V AC input and DC input drives. 8…10 20-750-EMCCM1-F8           ü
    EMC Core – Cabinet-mounted input, for 380…690V Common DC Input drives only. 8…10 20-750-CBPEMCCM1-F8           ü
    EMC Core – Cabinet-mounted input, for 380…690V AC input drives only. 8…10 20-750-EMCCM1-F9           ü
    EMC Cores – Required when using the Safe Speed Monitor option 20-750-S1 with 380…690V drives. 8…10 20-750-EMCSSM1-F8           ü
    Door Shielding Kit 8…10 20-750-EMCDK1-F10           ü
    Flange Adapter Kit Converts Open Type drive to external heatsink (flange) with NEMA/UL Type 1 integrity backside.
    This kit is for use with IP20, NEMA/UL Type 0 drives and will not provide an air-tight or water-tight seal. Where sealing is required (e.g. contaminated, dirty or wet environments), a drive with an “F” enclosure option must be used.
    2 20-750-FLNG1-F2           ü
    3 20-750-FLNG1-F3           ü
    4 20-750-FLNG1-F4           ü
    5 20-750-FLNG1-F5           ü
    Converts Open Type drive to external heatsink (flange) with NEMA/UL Type 4X/12 integrity backside. 6 20-750-FLNG4-F6           ü
    7 20-750-FLNG4-F7           ü
    L Bus Bar Kit Includes three L-brackets 8…10 20-750-LBRKT1           ü
    NEMA/UL Type 1 Option Kit NEMA/UL Type 1 Kit 1 20-750-NEMA1-F1           ü
    2 20-750-NEMA1-F2           ü
    3 20-750-NEMA1-F3           ü
    4 20-750-NEMA1-F4           ü
    5 20-750-NEMA1-F5           ü
    6 20-750-NEMA1-F6           ü
    7 20-750-NEMA1-F7           ü
    Power Terminal Extension Allows connection of two parallel leads to the AC terminals. 6 20-750-ACTE1-F6           ü
    Power Terminal Guard Provides additional ingress protection on power terminals. 6 20-750-PTG1-F6           ü
    7 20-750-PTG1-F7           ü
    continued

    PowerFlex 750-Series Option Kits (continued)
    Description Frame Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Remote Control POD Mounting Kit Hardware, fiber-optic, and power supply cables to remotely mount the control POD up to 23 m (75 ft) from the drive. 8…10 20-750-RPD1-F8           ü
    Roll-Out Cart A wheeled roll-out cart that facilitates drive installation and removal. Required for Frame 8 and larger drives. 8…10 20-750-CART1-F8           ü
    ∆ Frame 8 and up drives can be powered from an external 24V DC source, a 20-750-APS is not required.

    Other Options
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    115V AC Interface AK-M9-115VAC-1 ü          
    Frame E Flange Gasket AK-M9-GASKET1-E4 ü          
    Service Connection Board ⋆  SK-M9-SCB1 ü          
    Removable I/O Terminal Block SK-G9-TB1-S1   ü        
    Removable Encoder Terminal Block SK-G9-TB1-ENC1   ü        
    Touch Cover - Converts IP00/Open Type drive to IP20/NEMA/UL Type 1. No wiring space provided. 20-OPT-TC     ü      
    Top Hat - Converts IP00/Open Type drive to IP20/NEMA/UL Type 1. Allows for wiring space. 20-OPT-TH     ü      
    Auxiliary Control Power Supply 20-24V-AUX1       ü    
    PowerFlex 700S Phase II Control with Expanded Cassette 20D-P2-CKE1       ü ü ▶   
    PowerFlex 700S Phase II Control with Slim Cassette 20D-P2-CKS1       ü    
    PowerFlex 700S DriveLogix5730 Phase II Control with Expanded Cassette 20D-DL2-CKE1       ü ü ▶   
    PowerFlex 700S DriveLogix5730 Phase II Control with Slim Cassette 20D-DL2-CKS1       ü    
    ⋆ Provides temporary DPI/HIM connection for NEMA/UL Type 1 and Flange drives with cover removed.
    ▶ When using PowerFlex 700S control and Expanded Cassette.

    SynchLink Accessories
    Description ⋆  Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    SynchLink Board 20D-P2-SLB0       ü ü ▶   
    SynchLink Fiber Base Block 1751-SLBA       ü ü ▶   
    SynchLink 4-port Fiber Splitter Block 1751-SL4SP       ü ü ▶   
    SynchLink Fiber Bypass Switch Block 1751-SLBP       ü ü ▶   
    2x3 Meter Fiber Link for Power Monitor/SynchLink 1403-CF003       ü ü ▶   
    2x5 Meter Fiber Link for Power Monitor/SynchLink 1403-CF005       ü ü ▶   
    10 Meter Fiber Link for Power Monitor/SynchLink 1403-CF010       ü ü ▶   
    ⋆ Refer to publication number 1769-SG001 for details on SynchLink.
    ▶ When using PowerFlex 700S control.

    DriveLogix Option Kits
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Logix Expansion board for DriveLogix5730 ♦  20D-DL2-LEB0       ü ü ▶   
    Industrial Compact Flash 64 MB Memory Card for DriveLogix5730 1784-CF64       ü ü ▶   
    ♦ Requires Expanded Cassette.
    ▶ When using PowerFlex 700S control.

    DriveLogix I/O Cables
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    DriveLogix5730 - Compact I/O cable, 3.28 ft. (1 meter), Left Bus Cap♦ ♣  20D-DL2-CL3       ü ü ▶   
    DriveLogix5730 - Compact I/O cable, 3.28 ft. (1 meter), Right Bus Cap ♦ ♣  20D-DL2-CR3       ü ü ▶   
    Logix5000 RS-232 Programming Cable 1756-CP3       ü ü ▶   
    ♦ Requires Expanded Cassette.
    ♣ Refer to Publication 1769-SG001 for details and selection of Compact I/O.
    ▶ When using PowerFlex 700S control.

    PowerFlex 70 Small Duty Internal Dynamic Brake Resistors

    Limited duty resistors mount directly to the back surface of the drive and require no extra panel space. Internal resistors are non-destructive and do not require a resistor overheat external safety circuit.

    PowerFlex 70 AC Drive Small Duty Internal DB Resistor
    Normal Duty⋆ 
    kW (Hp)
    Heavy Duty⋆ 
    kW (Hp)
    Min DB Res
    Ohms ±10%
    Cat. No. Resistance‡ 
    Ohms ±5%
    Continuous Power
    kW
    Max Energy
    kJ
    Max Braking Torque
    % of ND Motor
    Application Type 1 Application Type 2
    Braking Torque
    % of ND Motor
    Duty Cycle Braking Torque
    % of ND Motor
    Duty Cycle
    200…240 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 33 20AB-DB1-A 62 0.048 8.3 307% 100% 25.9% 150% 17.3%
    0.75 (1.0) 0.55 (0.75) 33 20AB-DB1-A 62 0.048 7.3 300% 100% 12.8% 150% 8.5%
    1.5 (2.0) 1.1 (1.5) 33 20AB-DB1-B 62 0.028 0.8 160% 100% 3.7% 150% 2.5%
    2.2 (3.0) 1.5 (2.0) 33 20AB-DB1-B 62 0.028 0.8 109% 100% 2.5% 109% 2.3%
    4.0 (5.0) 3.0 (3.0) 30 20AB-DB1-C 62 0.040 0.8 60% 60% 3.3% N/A N/A
    5.5 (7.5) 4.0 (5.0) 21 20AB-DB1-D 22 0.036 0.9 117% 100% 1.3% 117% 1.1%
    7.5 (10) 5.5 (7.5) 21 20AB-DB1-D 22 0.036 0.9 86% 86% 1.1% N/A N/A
    400…480 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 68 20AD-DB1-A 115 0.048 8.3 320% 100% 25.9% 150% 17.3%
    0.75 (1.0) 0.55 (0.75) 68 20AD-DB1-A 115 0.048 9.0 259% 100% 12.8% 150% 8.5%
    1.5 (2.0) 1.1 (1.5) 68 20AD-DB1-A 115 0.048 2.4 243% 100% 6.4% 150% 4.3%
    2.2 (3.0) 1.5 (2.0) 68 20AD-DB1-B 115 0.028 0.9 206% 100% 2.5% 150% 1.7%
    4.0 (5.0) 3.0 (3.0) 68 20AD-DB1-B 115 0.028 0.9 129% 100% 1.4% 129% 1.1%
    5.5 (7.5) 4.0 (5.0) 74 20AD-DB1-C 115 0.04 0.9 94% 94% 1.5% N/A N/A
    7.5 (10) 5.5 (7.5) 74 20AD-DB1-C 115 0.04 0.9 69% 69% 1.5% N/A N/A
    11 (15) 7.5 (10) 44 20AD-DB1-D 62 0.036 0.8 87% 87% 0.8% N/A N/A
    15 (20) 11 (15) 31 20AD-DB1-D 62 0.036 0.8 64% 64% 0.8% N/A N/A
    500…600 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 117 20AD-DB1-A 115 0.048 8.3 287% 100% 25.9% 150% 17.3%
    0.75 (1.0) 0.55 (0.75) 117 20AD-DB1-A 115 0.048 9.0 263% 100% 12.8% 150% 8.5%
    1.5 (2.0) 1.1 (1.5) 117 20AD-DB1-A 115 0.048 2.4 243% 100% 6.4% 150% 4.3%
    2.2 (3.0) 1.5 (2.0) 117 20AD-DB1-B 115 0.028 0.9 202% 100% 2.5% 150% 1.7%
    4.0 (5.0) 3.0 (3.0) 80 20AD-DB1-B 115 0.028 0.9 193% 100% 1.4% 150% 0.9%
    5.5 (7.5) 4.0 (5.0) 80 20AD-DB1-C 115 0.04 0.9 147% 100% 1.5% 147% 1.0%
    7.5 (10) 5.5 (7.5) 80 20AD-DB1-C 115 0.04 0.9 108% 100% 1.1% 108% 1.0%
    11 (15) 7.5 (10) 48 N/A N/A N/A N/A N/A N/A N/A N/A N/A
    15 (20) 11 (15) 48 N/A N/A N/A N/A N/A N/A N/A N/A N/A
    ⋆ Duty cycle listed is based on full speed to zero speed deceleration. For constant regen at full speed, duty cycle capability is half of what is listed. Application Type 1 represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
    ‡ Always check resistor Ohms against minimum resistance for drive being used.

    PowerFlex 70 Medium Duty External Dynamic Brake Resistors

    These resistors provide a larger duty cycle capability than the internal type. Includes an internal thermal switch for use in external safety circuit.

    PowerFlex 70 AC Drive Medium Duty External DB Resistor
    Normal Duty⋆ 
    kW (Hp)
    Heavy Duty⋆ 
    kW (Hp)
    Min DB Res
    Ohms ±10%
    Cat. No. Resistance‡ 
    Ohms ±5%
    Continuous Power
    kW
    Max Energy
    kJ
    Max Braking Torque
    % of ND Motor
    Application Type 1 Application Type 2
    Braking Torque
    % of ND Motor
    Duty Cycle Braking Torque
    % of ND Motor
    Duty Cycle
    200…240 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 33 AK-R2-091P500 91 0.086 17 293% 100% 46% 150% 31%
    0.75 (1.0) 0.55 (0.75) 33 AK-R2-091P500 91 0.086 17 218% 100% 23% 150% 15%
    1.5 (2.0) 1.1 (1.5) 33 AK-R2-091P500 91 0.086 17 109% 100% 11% 109% 11%
    2.2 (3.0) 1.5 (2.0) 33 AK-R2-047P500 47 0.166 33 144% 100% 15% 144% 11%
    4.0 (5.0) 3.0 (3.0) 30 AK-R2-047P500 47 0.166 33 79% 79% 11% N/A N/A
    5.5 (7.5) 4.0 (5.0) 23 AK-R2-030P1K2 30 0.26 52 90% 90% 10% N/A N/A
    7.5 (10) 5.5 (7.5) 23 AK-R2-030P1K2 30 0.26 52 66% 66% 10% N/A N/A
    400…480 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 68 AK-R2-360P500 360 0.086 17 305% 100% 47% 150% 31%
    0.75 (1.0) 0.55 (0.75) 68 AK-R2-360P500 360 0.086 17 220% 100% 23% 150% 15%
    1.5 (2.0) 1.1 (1.5) 68 AK-R2-360P500 360 0.086 17 110% 100% 12% 110% 11%
    2.2 (3.0) 1.5 (2.0) 68 AK-R2-120P1K2 120 0.26 52 197% 100% 24% 150% 16%
    4.0 (5.0) 3.0 (3.0) 68 AK-R2-120P1K2 120 0.26 52 124% 100% 13% 124% 10%
    5.5 (7.5) 4.0 (5.0) 74 AK-R2-120P1K2 120 0.26 52 90% 90% 10% N/A N/A
    7.5 (10) 5.5 (7.5) 74 AK-R2-120P1K2 120 0.26 52 66% 66% 10% N/A N/A
    11 (15) §  7.5 (10) §  44 §  60 0.52 104 90% 90% 10% N/A N/A
    15 (20) §  11 (15) §  31 §  60 0.52 104 66% 66% 10% N/A N/A
    500…600 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 117 AK-R2-360P500 360 0.086 17 274% 100% 46% 150% 31%
    0.75 (1.0) 0.55 (0.75) 117 AK-R2-360P500 360 0.086 17 251% 100% 23% 150% 15%
    1.5 (2.0) 1.1 (1.5) 117 AK-R2-360P500 360 0.086 17 172% 100% 11% 150% 8%
    2.2 (3.0) 1.5 (2.0) 117 AK-R2-120P1K2 120 0.26 52 193% 100% 24% 150% 16%
    4.0 (5.0) 3.0 (3.0) 80 AK-R2-120P1K2 120 0.26 52 185% 100% 13% 150% 9%
    5.5 (7.5) 4.0 (5.0) 80 AK-R2-120P1K2 120 0.26 52 141% 100% 9% 141% 7%
    7.5 (10) 5.5 (7.5) 80 AK-R2-120P1K2 120 0.26 52 103% 100% 7% 103% 7%
    11 (15) §  7.5 (10) §  48 §  60 0.52 104 141% 100% 9% 141% 7%
    15 (20) §  11 (15) §  48 §  60 0.52 104 103% 100% 7% 103% 7%
    ⋆ Duty cycle listed is based on full speed to zero speed deceleration. For constant regen at full speed, duty cycle capability is half of what is listed. Application Type 1 represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
    ‡ Always check resistor Ohms against minimum resistance for drive being used.
    § For 11 and 15 kW (15 and 20 Hp) applications, use two 7.5 kW (10 Hp) size resistors wired in parallel.

    Internal Dynamic Brake Resistor Kits

    These resistors have a limited duty cycle. Refer to the PowerFlex Dynamic Braking Selection Guide to determine if an internal resistor will be sufficient for your application. An external resistor may be required.

    Drive Input Voltage Brake Resistance Frame Cat. No. Used with PowerFlex Drive
    W 70 700 700H 700S 700L 753/755
    208…240V AC 62 0 20BB-DB1-0   ü   ü    
    62 1 (except 7.5 Hp) 20BB-DB1-1   ü   ü    
    22 1 (7.5 Hp) 20BB-DB2-1   ü   ü    
    22 2 20BB-DB1-2   ü   ü    
    380…600V AC 115 0 20BD-DB1-0   ü   ü    
    115 1 20BD-DB1-1   ü   ü    
    68 2 20BD-DB1-2   ü   ü    
    115 1 (1…3 Hp) 20-750-DB1-D1           ü
    62 1 (5…10 Hp) 20-750-DB1-D1A           ü
    62 2 20-750-DB1-D2           ü
      

    Terminators
    Description ‡  Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    for use with 3.7 kW (5 Hp) & below drives 1204-TFA1 ü ü   ü ü ü
    for use with 1.5 kW (2 Hp) & up drives 1204-TFB2 ü ü ü ü ü ü
    ‡ Refer to Appendix A of publication Drives-IN001 for selection information.

    Reflected Wave Reduction Modules w/Common Mode Choke
    Description ‡  Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    17A with Common Mode Choke 1204-RWC-17-A ü ü ü ü   ü
    ‡ Refer to Appendix A of publication Drives-IN001 for selection information.

    Reflected Wave Reduction Modules
    Voltage ND kW ND Hp Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    380…480V AC 4 5 1321-RWR8-DP ü ü   ü   ü
    5.5 7.5 1321-RWR12-DP ü ü   ü   ü
    7.5 10 1321-RWR18-DP ü ü   ü   ü
    11 15 1321-RWR25-DP ü ü   ü   ü
    15 20 1321-RWR35-DP ü ü   ü   ü
    18.5 25 1321-RWR35-DP ü ü   ü   ü
    22 30 1321-RWR45-DP ü ü   ü   ü
    30 40 1321-RWR55-DP ü ü   ü   ü
    37 50 1321-RWR80-DP ü ü   ü   ü
    45 60 1321-RWR80-DP   ü   ü   ü
    55 75 1321-RWR100-DP   ü   ü   ü
    75 100 1321-RWR130-DP   ü   ü   ü
    1321-RWR160-DP       ü    
    90 125 1321-RWR160-DP   ü   ü   ü
    110 150 1321-RWR200-DP   ü   ü   ü
    149 200 1321-RWR250-DP   ü ü ü   ü
    1321-RWR320-DP       ü    
    187 250 1321-RWR320-DP   ü ü ü   ü
    500…600V AC 4 5 1321-RWR8-EP ü ü   ü   ü
    5.5 7.5 1321-RWR8-EP       ü    
    1321-RWR12-EP ü ü       ü
    7.5 10 1321-RWR12-EP ü ü   ü    
    1321-RWR18-EP           ü
    11 15 1321-RWR18-EP ü ü   ü    
    1321-RWR25-EP           ü
    15 20 1321-RWR25-EP ü ü   ü    
    1321-RWR35-EP           ü
    18.5 25 1321-RWR25-EP       ü    
    1321-RWR35-EP ü ü       ü
    22 30 1321-RWR35-EP ü ü   ü    
    1321-RWR45-EP           ü
    30 40 1321-RWR45-EP ü ü   ü    
    1321-RWR55-EP           ü
    37 50 1321-RWR55-EP ü ü   ü    
    1321-RWR80-EP           ü
    45 60 1321-RWR80-EP   ü   ü   ü
    55 75 1321-RWR80-EP   ü   ü    
    1321-RWR100-EP           ü
    75 100 1321-RWR100-EP   ü   ü    
    1321-RWR130-EP           ü
    90 125 1321-RWR130-EP   ü   ü    
    1321-RWR160-EP           ü
    110 150 1321-RWR160-EP   ü   ü    
    1321-RWR200-EP       ü   ü
    149 200 1321-RWR200-EP       ü    
    1321-RWR250-EP           ü
      

    1492 Wiring System Modules and Cables

    Wiring System Modules and Cables provide an easy means to extend drive control wiring. A pre-wired cable (available in various lengths) plugs into the appropriate drive I/O terminal block. The remaining cable end plugs into the Wiring Module which provides a terminal block for direct I/O connection. See publication 1492-TD008 for detailed information.

    1492 Wiring Module and Cable Selection
    Drive I/O Wiring Module Description Wiring Module Cat. No. PowerFlex 700H Cable (see below) PowerFlex 700S Cable (see below) Used with PowerFlex Drive
    Fixed Terminal Block Removable Terminal Block 70 700 700H 700S 700L 753/755
    Analog I/O (TB1) 6 Channel Isolated - 3 Terminals/Ch. 1492-AIFM6S-3 1492-RAIFM6S-3 1492-ACABxxxZ7H 1492-ACABxxxZ7S     ü ü    
    DC Discrete Digital I/O (TB2) Standard,
    264V AC/DC
    1492-IFM20F 1492-RIFM20F 1492-CABxxxA7H 1492-CABxxxA7S     ü ü    
    Narrow Standard,
    132V AC/DC
    1492-IFM20FN 1492-RIFM20FN 1492-CABxxxA7H 1492-CABxxxA7S     ü ü    
    Extra Terminals
    (2 per I/O), 264V AC/DC
    1492-IFM20F-2 1492-RIFM20F-2 1492-CABxxxA7H 1492-CABxxxA7S     ü ü    
    AC Discrete Digital I/O (20C-DA1-B & 20C-DO1) Standard,
    264V AC/DC
    1492-IFM20F 1492-RIFM20F 1492-CABxxxB7H 1492-CABxxxB7H     ü      
    Narrow Standard,
    132V AC/DC
    1492-IFM20FN 1492-RIFM20FN 1492-CABxxxB7H 1492-CABxxxB7H     ü      
    Extra Terminals
    (2 per I/O), 264V AC/DC
    1492-IFM20F-2 1492-RIFM20F-2 1492-CABxxxB7H 1492-CABxxxB7H     ü      
    Encoder 2 Channel Encoder Input - 4 Outputs 1492-AIFMCE4 1492-ACABxxxX7S 1492-ACABxxxX7S       ü    
    2 Channel Fused Encoder Input - 4 Fused Outputs 1492-AIFMCE4-F 1492-ACABxxxX7S 1492-ACABxxxX7S       ü    
      

    1492 Pre-Wired Cable Assemblies
    Description PowerFlex 700H Cat. No. PowerFlex 700S Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Pre-Wired Cable for Analog I/O
    0.5 Meter (1.6 Feet) 1492-ACAB005Z7H 1492-ACAB005Z7S     ü ü    
    1.0 Meter (3.3 Feet) 1492-ACAB010Z7H 1492-ACAB010Z7S     ü ü    
    2.5 Meters (8.2 Feet) 1492-ACAB025Z7H 1492-ACAB025Z7S     ü ü    
    5.0 Meters (16.4 Feet) 1492-ACAB050Z7H 1492-ACAB050Z7S     ü ü    
    Pre-Wired Cable for Discrete DC I/O
    0.5 Meter (1.6 Feet) 1492-CAB005A7H 1492-CAB005A7S     ü ü    
    1.0 Meter (3.3 Feet) 1492-CAB010A7H 1492-CAB005A7S     ü ü    
    2.5 Meters (8.2 Feet) 1492-CAB025A7H 1492-CAB025A7S     ü ü    
    5.0 Meters (16.4 Feet) 1492-CAB050A7H 1492-CAB050A7S     ü ü    
    Pre-Wired Cable for Discrete AC I/O
    0.5 Meter (1.6 Feet) 1492-CAB005B7H     ü      
    1.0 Meter (3.3 Feet) 1492-CAB010B7H     ü      
    2.5 Meters (8.2 Feet) 1492-CAB025B7H     ü      
    5.0 Meters (16.4 Feet) 1492-CAB050B7H     ü      
    Pre-Wired Cable for Encoder
    0.5 Meter (1.6 Feet) 1492-ACAB005X7S       ü    
    1.0 Meter (3.3 Feet) 1492-ACAB010X7S       ü    
    2.5 Meters (8.2 Feet) 1492-ACAB025X7S       ü    
    5.0 Meters (16.4 Feet) 1492-ACAB050X7S       ü    
     

    Isolation Transformers - IP32, NEMA/UL Type 3R Standalone, 4…6% Nominal Impedance
           
      Click to enlarge - xfmr_sch1 Click to enlarge - xfmr_sch2  
      Diagram 1 Diagram 2  

    Motor Rating Wiring Diagram 240V, 60 Hz, Three-Phase Primary & 240V Secondary ⋆  460V, 60 Hz, Three-Phase Primary & 460V Secondary 575V, 60 Hz, Three-Phase Primary & 575V Secondary ⋆  Used with PowerFlex Drive
    kW Hp Cat. No. Cat. No. Cat. No. 70 700 700H 700S 700L 753/755
    0.25 0.33 1 1321-3TW005-AA 1321-3TW005-BB ü ü   ü    
    0.37 0.5 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü    
    0.55 0.75 1 1321-3TW005-AA 1321-3TW005-BB ü ü   ü    
    0.75 1 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü   ü
    1.1 1.5 1 1321-3TW005-AA 1321-3TW005-BB ü ü   ü    
    1.5 2 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü   ü
    2.2 3 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü   ü
    22 30 2 1321-3TW040-AA 1321-3TW040-BB 1321-3TW040-CC ü ü   ü   ü
    30 40 2 1321-3TW051-AA 1321-3TW051-BB 1321-3TW051-CC ü ü   ü   ü
    37 50 2 1321-3TH063-AA 1321-3TH063-BB 1321-3TH063-CC ü ü   ü   ü
    45 60 2 1321-3TH075-AA 1321-3TH075-BB 1321-3TH075-CC   ü   ü   ü
    55 75 2 1321-3TH093-AA 1321-3TH093-BB 1321-3TH093-CC   ü   ü   ü
    75 100 2 1321-3TH118-BB 1321-3TH118-CC   ü   ü   ü
    90 125 2 1321-3TH145-BB 1321-3TH145-CC   ü   ü   ü
    110 150 2 1321-3TH175-BB 1321-3TH175-CC   ü ü ü   ü
    149 200 2 1321-3TH220-BB 1321-3TH220-CC   ü ü ü   ü
    187 250 2 1321-3TH275-BB 1321-3TH275-CC   ü ü     ü
    224 300 2 1321-3TH330-BB 1321-3TH330-CC   ü ü     ü
    224 300 1 1321-3TH330-CC           ü
    261 350 1 1321-3TH440-BB 1321-3TH440-CC   ü ü     ü
    298 400 1 1321-3TH440-BB 1321-3TH440-CC   ü ü      
    298 400 1 1321-3TH440-BB 1321-3TH550-CC           ü
    336 450 1 1321-3TH550-BB 1321-3TH550-CC   ü ü     ü
    373 500 1 1321-3TH550-BB 1321-3TH550-CC   ü ü      
    373 500 1 1321-3TH550-BB 1321-3TH660-CC           ü
    410 550 1 1321-3TH660-CC           ü
    448 600 1 1321-3TH660-BB 1321-3TH660-CC   ü ü      
    448 600 1 1321-3TH660-BB 1321-3TH770-CC           ü
    485 650 1 1321-3TH770-CC   ü ü      
    522 700 1 1321-3TH770-BB 1321-3TH770-CC   ü ü     ü
    597 800 1 1321-3TH880-BB 1321-3TH880-CC           ü
    671 900 900 kVA ‡  950 kVA ‡            ü
    709 950 1000 kVA ‡            ü
    746 1000 1000 kVA ‡  1100 kVA ‡            ü
    821 1100 1200 kVA ‡            ü
    895 1200 1200 kVA ‡            ü
    933 1250 1200 kVA ‡            ü
    1007 1350 1300 kVA ‡            ü
    1119 1500 1500 kVA ‡  1500 kVA ‡            ü
    1492 2000 2000 kVA ‡            ü
    ⋆ Not applicable for the PowerFlex 755.
    ‡  1321 Isolation Transformer solution is not available. Approximate drive kVA is listed.

    Input and Output Reactors - 200…240V, 50/60 Hz, Three-Phase, 3% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R2-D 1321-3RA2-D 1321-3R2-D 1321-3RA2-D ü ü   ü    
    0.37 0.5 Normal 1321-3R2-D 1321-3RA2-D 1321-3R2-D 1321-3RA2-D ü ü   ü    
    0.55 0.75 Heavy 1321-3R4-A 1321-3RA4-A 1321-3R4-A 1321-3RA4-A ü ü   ü    
    0.75 1 Normal 1321-3R4-A 1321-3RA4-A 1321-3R4-A 1321-3RA4-A ü ü   ü    
    1.1 1.5 Heavy 1321-3R8-B 1321-3RA8-B 1321-3R8-A 1321-3RA8-A ü ü   ü    
    1.5 2 Normal 1321-3R8-A 1321-3RA8-A 1321-3R8-A 1321-3RA8-A ü ü   ü    
    Heavy 1321-3R8-A 1321-3RA8-A 1321-3R12-A 1321-3RA12-A ü ü   ü    
    2.2 3 Normal 1321-3R12-A 1321-3RA12-A 1321-3R12-A 1321-3RA12-A ü ü   ü    
    Heavy 1321-3R12-A 1321-3RA12-A 1321-3R18-A 1321-3RA18-A ü ü   ü    
    4 5 Normal 1321-3R18-A 1321-3RA18-A 1321-3R18-A 1321-3RA18-A ü ü   ü    
    Heavy 1321-3R18-A 1321-3RA18-A 1321-3R25-A 1321-3RA25-A ü ü   ü    
    5.5 7.5 Normal 1321-3R25-A 1321-3RA25-A 1321-3R25-A 1321-3RA25-A ü ü   ü    
    Heavy 1321-3R25-A 1321-3RA25-A 1321-3R35-A 1321-3RA35-A ü ü   ü    
    7.5 10 Normal 1321-3R35-A 1321-3RA35-A 1321-3R35-A 1321-3RA35-A ü ü   ü    
    Heavy 1321-3R35-A 1321-3RA35-A 1321-3R45-A 1321-3RA45-A ü ü   ü    
    11 15 Normal 1321-3R45-A 1321-3RA45-A 1321-3R45-A 1321-3RA45-A ü ü   ü    
    Heavy 1321-3R45-A 1321-3RA45-A 1321-3R55-A 1321-3RA55-A ü ü   ü    
    15 20 Normal 1321-3R55-A 1321-3RA55-A 1321-3R55-A 1321-3RA55-A ü ü   ü    
    Heavy 1321-3R55-A 1321-3RA55-A 1321-3R80-A 1321-3RA80-A ü ü   ü    
    18.5 25 Normal 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A ü ü   ü    
    Heavy 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A   ü   ü    
    22 30 Normal 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A   ü   ü    
    Heavy 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A   ü   ü    
    30 40 Normal 1321-3R100-A 1321-3RA100-A 1321-3R100-A 1321-3RA100-A   ü   ü    
    Heavy 1321-3R100-A 1321-3RA100-A 1321-3R100-A 1321-3RA100-A   ü   ü    
    37 50 Normal 1321-3R130-A 1321-3RA130-A 1321-3R130-A 1321-3RA130-A   ü   ü    
    Heavy 1321-3R130-A 1321-3RA130-A 1321-3R130-A 1321-3RA130-A   ü   ü    
    45 60 Normal 1321-3R160-A 1321-3RA160-A 1321-3R160-A 1321-3RA160-A   ü   ü    
    Heavy 1321-3R160-A 1321-3RA160-A 1321-3R160-A 1321-3RA160-A   ü   ü    
    55 75 Normal 1321-3R200-A 1321-3RA200-A 1321-3R200-A 1321-3RA200-A   ü   ü    
    Heavy 1321-3R200-A 1321-3RA200-A 1321-3R200-A 1321-3RA200-A   ü   ü    
    75 100 Normal 1321-3RB250-A 1321-3RAB250-A 1321-3RB250-A 1321-3RAB250-A   ü   ü    
    ‡ Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD rated output currents.

    Input and Output Reactors - 200…240V, 50/60 Hz, Three-Phase, 5% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü    
    0.37 0.5 Normal 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü    
    0.55 0.75 Heavy 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B ü ü   ü    
    0.75 1 Normal 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B ü ü   ü    
    1.1 1.5 Heavy 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B ü ü   ü    
    1.5 2 Normal 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B ü ü   ü    
    Heavy 1321-3R8-B 1321-3RA8-B 1321-3R12-B 1321-3RA12-B ü ü   ü    
    2.2 3 Normal 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B ü ü   ü    
    Heavy 1321-3R12-B 1321-3RA12-B 1321-3R18-B 1321-3RA18-B ü ü   ü    
    4 5 Normal 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B ü ü   ü    
    Heavy 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B ü ü   ü    
    5.5 7.5 Normal 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü    
    Heavy 1321-3R25-B 1321-3RA25-B 1321-3R35-B 1321-3RA35-B ü ü   ü    
    7.5 10 Normal 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü    
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B ü ü   ü    
    11 15 Normal 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B ü ü   ü    
    Heavy 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B ü ü   ü    
    15 20 Normal 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B ü ü   ü    
    Heavy 1321-3R55-B 1321-3RA55-B 1321-3R80-B 1321-3RA80-B ü ü   ü    
    18.5 25 Normal 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    22 30 Normal 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    30 40 Normal 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü    
    Heavy 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü    
    37 50 Normal 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü    
    Heavy 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü    
    45 60 Normal 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü    
    Heavy 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü    
    55 75 Normal 1321-3R200-B 1321-3RA200-B 1321-3R200-B 1321-3RA200-B   ü   ü    
    Heavy 1321-3R200-B 1321-3RA200-B 1321-3R200-B 1321-3RA200-B   ü   ü    
    75 100 Normal 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B   ü   ü    
    ‡ Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD rated output currents.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 3% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-C 1321-3RA1-C 1321-3R2-B 1321-3RA2-B ü ü   ü    
    0.37 0.5 Normal 1321-3R1-C 1321-3RA1-C 1321-3R2-B 1321-3RA2-B ü ü   ü    
    0.55 0.75 Heavy 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü    
    0.75 1 Normal 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü   ü
    1.1 1.5 Heavy 1321-3R4-C 1321-3RA4-C 1321-3R4-B 1321-3RA4-B ü ü   ü   ü
    1.5 2 Normal 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B ü ü   ü   ü
    Heavy 1321-3R4-B 1321-3RA4-B 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    2.2 3 Normal 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    Heavy 1321-3R8-C 1321-3RA8-C 1321-3R8-B 1321-3RA8-B ü ü   ü   ü
    4 5 Normal 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B ü ü   ü   ü
    Heavy 1321-3R8-B 1321-3RA8-B 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    5.5 7.5 Normal 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    Heavy 1321-3R12-B 1321-3RA12-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    7.5 10 Normal 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    Heavy 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    11 15 Normal 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    Heavy 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    15 20 Normal 1321-3R35-B 1321-3RA35-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    18.5 25 Normal 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    22 30 Normal 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    Heavy 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    30 40 Normal 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    Heavy 1321-3R55-B 1321-3RA55-B 1321-3R80-B 1321-3RA80-B ü ü   ü   ü
    37 50 Normal 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B ü ü   ü   ü
    Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    55 75 Normal/Heavy 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü   ü
    75 100 Normal/Heavy 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü   ü
    90 125 Normal/Heavy 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü   ü
    110 150 Normal 1321-3R200-B 1321-3RA200-B 1321-3R200-C 1321-3RA200-C   ü ü ü   ü
    Heavy 1321-3R200-B 1321-3RA200-B 1321-3R200-C 1321-3RA200-C   ü   ü   ü
    Heavy 1321-3R200-B 1321-3RA200-B     ü      
    200 Normal/Heavy 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B           ü
    132 Normal/Heavy 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B           ü
    149 200 Normal 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B   ü ü ü    
    Heavy 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B   ü ü ü    
    160 250 Normal/Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B           ü
    187 250 Normal/Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B   ü ü      
    200 300 Normal 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü ü     ü
    Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü ü     ü
    350 Normal/Heavy 1321-3R500-B 1321-3R500-B 1321-3R500-B 1321-3R500-B           ü
    250 Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    261 350 Normal 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü        
    Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü ü      
    Normal 1321-3R500-B 1321-3RA500-B     ü      
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two output reactors wired in parallel.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 3% Impedance (continued)
    kW Hp Duty ♦  Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    400 Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    280 400 Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B   ü        
    315 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    450 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    336 450 Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B   ü ü      
    355 Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    500 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    373 500 Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B   ü ü      
    400 Light/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    Normal 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    600 Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    448 600 Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B   ü ü      
    Heavy 1321-3R750-B 1321-3RA750-B     ü      
    Heavy 1321-3R750-B 1321-3RA750-B 1321-3R600-B 1321-3RA600-B   ü        
    450 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    650 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    700 Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    522 700 Normal 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B   ü        
    Normal/Heavy 1321-3RB400-B 1321-3RB400-B     ü §       
    750 Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    500 Normal/Heavy 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    500 800 Normal/Heavy 1321-3R500-B 1321-3RA500-B     ü §       
    800 Light/Normal/Heavy 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    560 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    630 900 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    Normal 1321-3R500-B 1321-3RA500-B     ü §       
    Heavy 1321-3R600-B 1321-3RA600-B     ü §       
    710 1000 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    746 1000 Normal 1321-3R600-B 1321-3RA600-B     ü §       
    Heavy 1321-3R750-B 1321-3RA750-B     ü §       
    800 1100 Light/Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü § 
    850 Light/Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü § 
    895 1200 Normal 1321-3R750-B 1321-3RA750-B     ü §       
    900 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü § 
    1250 Light/Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü § 
    933 1250 Normal 1321-3R750-B 1321-3RA750-B     ü §       
    1350 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü § 
    1500 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    1000 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    2000 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    1400 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.
    ♦ Light Duty refers to PowerFlex 755 drives only.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 5% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-B 1321-3RA1-B 1321-3R2-C 1321-3RA2-C ü ü   ü    
    0.37 0.5 Normal 1321-3R1-B 1321-3RA1-B 1321-3R2-C 1321-3RA2-C ü ü   ü    
    0.55 0.75 Heavy 1321-3R2-C 1321-3RA2-C 1321-3R2-B 1321-3RA2-B ü ü   ü    
    0.75 1 Normal 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B ü ü   ü   ü
    1.1 1.5 Heavy 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    1.5 2 Normal 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    Heavy 1321-3R4-D 1321-3RA4-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    2.2 3 Normal 1321-3R8-D 1321-3RA8-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    Heavy 1321-3R8-D 1321-3RA8-D 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    4 5 Normal 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    Heavy 1321-3R8-C 1321-3RA8-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    5.5 7.5 Normal 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    Heavy 1321-3R12-C 1321-3RA12-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    7.5 10 Normal 1321-3R18-C 1321-3RA18-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    Heavy 1321-3R18-C 1321-3RA18-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    11 15 Normal/Heavy 1321-3R25-C 1321-3RA25-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    15 20 Normal 1321-3R35-C 1321-3RA35-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    18.5 25 Normal 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    22 30 Normal 1321-3R45-C 1321-3RA45-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    Heavy 1321-3R45-C 1321-3RA45-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    30 40 Normal 1321-3R55-C 1321-3RA55-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    Heavy 1321-3R55-C 1321-3RA55-C 1321-3R80-C 1321-3RA80-C ü ü   ü   ü
    37 50 Normal 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C ü ü   ü   ü
    Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    55 75 Normal/Heavy 1321-3R100-C 1321-3RA100-C 1321-3R100-C 1321-3RA100-C   ü   ü   ü
    75 100 Normal/Heavy 1321-3R130-C 1321-3RA130-C 1321-3R130-C 1321-3RA130-C   ü   ü   ü
    90 125 Normal/Heavy 1321-3R160-C 1321-3RA160-C 1321-3R160-C 1321-3RA160-C   ü   ü   ü
    110 150 Normal 1321-3R200-C 1321-3RA200-C 1321-3R200-C 1321-3RA200-C   ü   ü   ü
    Heavy 1321-3R200-C 1321-3RA200-C 1321-3R200-C 1321-3RA200-C   ü ü ü   ü
    Heavy 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C     ü ü ♣     
    200 Normal/Heavy 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C           ü
    132 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    149 200 Normal 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C   ü   ü ∆     
    Heavy 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C   ü ü ü    
    160 250 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    187 250 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C   ü ü      
    300 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    200 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    224 300 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C   ü ü      
    350 Normal/Heavy 1321-3R500-C 1321-3R500-C 1321-3R500-C 1321-3R500-C           ü
    250 Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    261 350 Normal 1321-3R500-C 1321-3RA500-C 1321-3RB400-C 1321-3RAB400-C   ü        
    Normal 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C     ü      
    Heavy 1321-3R500-C 1321-3RA500-C 1321-3RB400-C 1321-3RAB400-C   ü ü      
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ♣ For use with 300A PowerFlex 700S.
    ∆ For use with 248A and 261A PowerFlex 700S.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 5% Impedance (continued)
    kW Hp Duty ♦  Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    400 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    298 400 Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C   ü        
    315 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    336 450 Normal/Heavy 1321-3RA600-C 1321-3RA600-C 1321-3R500-C 1321-3RA500-C   ü ü      
    450 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    355 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    373 500 Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C   ü ü      
    500 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    400 Light/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    Normal 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    448 600 Normal/Heavy 1321-3R750-E 1321-3RA750-E 1321-3R750-E 1321-3RA750-E   ü        
    600 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    450 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    500 Normal/Heavy 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    522 600 Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C     ü ⋆       
    650 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    700 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    522 700 Normal 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C   ü        
    Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    671 700 Heavy 1321-3RB400-C 1321-3RAB400-C     ü §       
    750 Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    800 Light/Normal/Heavy 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    560 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    597 800 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    630 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    746 800 Heavy 1321-3R500-C 1321-3RA500-C     ü §       
    900 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    671 900 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    Heavy 1321-3RA600-C 1321-3RA600-C     ü §       
    710 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    1000 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    746 1000 Normal 1321-3RA600-C 1321-3RA600-C     ü §       
    Heavy 1321-3R750-C 1321-3RA750-C     ü § ⋆       
    1100 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    800 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    850 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    895 1200 Normal 1321-3R750-C 1321-3RA750-C     ü § ⋆       
    1250 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    900 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü § 
    933 1250 Normal 1321-3R750-C 1321-3RA750-C     ü §       
    1350 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü § 
    1500 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    1000 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    2000 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    1400 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ⋆ 4% impedance.
    § Requires two output reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.
    ♦ Light Duty refers to PowerFlex 755 drives only.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 3% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-C 1321-3RA1-C 1321-3R1-B 1321-3RA1-B ü          
    0.37 0.5 Normal 1321-3R1-C 1321-3RA1-C 1321-3R1-B 1321-3RA1-B ü          
    Heavy 1321-3R1-C 1321-3RA1-C 1321-3R2-B 1321-3RA2-B   ü   ü    
    0.55 0.75 Heavy 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B ü          
    0.75 1 Normal 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B ü ü   ü   ü
    Heavy 1321-3R2-B 1321-3RA2-B 1321-3R4-D 1321-3RA4-D   ü   ü   ü
    1.1 1.5 Heavy 1321-3R2-A 1321-3RA2-A 1321-3R4-D 1321-3RA4-D ü          
    1.5 2 Normal 1321-3R4-C 1321-3RA4-C 1321-3R4-D 1321-3RA4-D ü          
    Heavy 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C ü         ü
    Normal 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D   ü   ü   ü
    Heavy 1321-3R4-D 1321-3RA4-D 1321-3R4-C 1321-3RA4-C   ü   ü   ü
    2.2 3 Normal 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C ü ü   ü   ü
    Heavy 1321-3R4-C 1321-3RA4-C 1321-3R8-C 1321-3RA8-C ü ü   ü    
    4 5 Normal 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    Heavy 1321-3R8-C 1321-3RA8-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    5.5 7.5 Normal 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    Heavy 1321-3R12-C 1321-3RA12-C 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    7.5 10 Normal 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    Heavy 1321-3R12-B 1321-3RA12-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    11 15 Normal 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    Heavy 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    15 20 Normal 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    Heavy 1321-3R25-B 1321-3RA25-B 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    18.5 25 Normal 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    22 30 Normal 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    30 40 Normal 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    Heavy 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    37 50 Normal 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    Heavy 1321-3R55-B 1321-3RA55-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    55 75 Normal/Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    75 100 Normal/Heavy 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü   ü
    90 125 Normal/Heavy 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü   ü
    110 150 Normal 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü   ü
    Normal/Heavy 1321-3R200-C 1321-3RA200-C     ü      
    132 Heavy 1321-3RB250-C 1321-3RAB250-C     ü      
    149 200 Normal/Heavy 1321-3R200-B 1321-3RA200-B     ü      
    160 Normal/Heavy 1321-3RB250-C 1321-3RAB250-C     ü      
    187 250 Normal/Heavy 1321-3RB250-B 1321-3RAB250-B     ü      
    300 Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B           ü
    200 Normal 1321-3RB250-C 1321-3RAB250-C     ü      
    Heavy 1321-3RB320-C 1321-3RAB320-C     ü      
    Heavy 1321-3R250-B 1321-3RA250-B 1321-3R250-B 1321-3RA250-B           ü
    350 Light/Normal/Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    250 Normal 1321-3RB320-C 1321-3RAB320-C     ü      
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü      
    Normal/Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B           ü
    261 350 Normal/Heavy 1321-3RB320-B 1321-3RAB320-B     ü      
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 3% Impedance (continued)
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    298 400 Normal/Heavy 1321-3RB400-B 1321-3RAB400-B     ü      
    400 Light/Normal/Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    300 Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    450 Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    315 Normal 1321-3RB400-C 1321-3RAB400-C     ü      
    Heavy 1321-3R500-C 1321-3RA500-C     ü      
    Light/Normal 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    336 450 Normal 1321-3RB400-B 1321-3RAB400-B     ü      
    Normal 1321-3R500-B 1321-3RA500-B     ü      
    Heavy 1321-3RB400-B 1321-3RAB400-B     ü      
    500 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    355 Normal 1321-3R500-C 1321-3RA500-C     ü      
    Heavy 1321-3R600-C 1321-3RA600-C     ü      
    Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    373 500 Normal/Heavy 1321-3R500-B 1321-3RA500-B     ü      
    550 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    375 Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    400 Normal 1321-3R500-C 1321-3RA500-C     ü      
    Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    448 600 Normal 1321-3R600-B 1321-3RA600-B     ü      
    600 Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    450 Normal/Heavy 1321-3R600-C 1321-3RA600-C     ü      
    Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    485 650 Heavy 1321-3RB320-B 1321-3RAB320-B     ü §       
    500 Normal 1321-3R600-C 1321-3RA600-C     ü      
    Heavy 1321-3R750-C 1321-3RA750-C     ü      
    Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    522 700 Normal 1321-3RB320-B 1321-3RAB320-B     ü §       
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü §       
    700 Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    530 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    560 Normal 1321-3R750-C 1321-3RA750-C     ü      
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü §       
    Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    750 Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    597 800 Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    800 Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    630 Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    Heavy 1321-3R500-C 1321-3RA500-C     ü §       
    Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    671 900 Normal 1321-3RB400-B 1321-3RAB400-B     ü §       
    Heavy 1321-3R1000-C 1321-3RA1000-C     ü      
    900 Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    710 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    950 Light/Normal 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    746 1000 Normal 1321-3R1000-C 1321-3RA1000-C     ü      
    Heavy 1321-3R1000-B 1321-3RA1000-B     ü      
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two reactors wired in parallel.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 3% Impedance (continued)
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    750 Normal 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    800 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    Heavy 1321-3R600-C 1321-3RA600-C     ü §       
    Light/Normal/Heavy 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    1000 Light/Normal 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    821 1100 Normal 1321-3R1000-B 1321-3RA1000-B     ü      
    Heavy 1321-3R600-B 1321-3RA600-B     ü §       
    1100 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    850 Light 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    900 Normal/Heavy 1321-3R600-C 1321-3RA600-C     ü §       
    Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    970 1300 Normal 1321-3R600-B 1321-3RA600-B     ü §       
    1000 Normal 1321-3R600-C 1321-3RA600-C     ü §       
    Heavy 1321-3R750-C 1321-3RA750-C     ü §       
    Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    1100 Normal 1321-3R750-C 1321-3RA750-C     ü §       
    Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    1200 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    1500 Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    1500 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 5% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-A 1321-3RA1-A 1321-3R1-B 1321-3RA1-B ü          
    0.37 0.5 Normal 1321-3R1-B 1321-3RA1-B 1321-3R1-B 1321-3RA1-B ü          
    0.37 0.5 Heavy 1321-3R1-B 1321-3RA1-B 1321-3R2-C 1321-3RA2-C   ü   ü    
    0.55 0.75 Heavy 1321-3R2-C 1321-3RA2-C 1321-3R2-C 1321-3RA2-C ü          
    0.75 1 Normal 1321-3R2-C 1321-3RA2-C 1321-3R2-C 1321-3RA2-C ü ü   ü   ü
    Heavy 1321-3R2-C 1321-3RA2-C 1321-3R4-D 1321-3RA4-D   ü   ü   ü
    1.1 1.5 Heavy 1321-3R2-B 1321-3RA2-B 1321-3R4-D 1321-3RA4-D ü ü   ü    
    1.5 2 Normal/Heavy 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    2.2 3 Normal 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    Heavy 1321-3R4-D 1321-3RA4-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    4 5 Normal 1321-3R8-D 1321-3RA8-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    Heavy 1321-3R8-D 1321-3RA8-D 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    5.5 7.5 Normal/Heavy 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    7.5 10 Normal 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    Heavy 1321-3R12-C 1321-3RA12-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    11 15 Normal 1321-3R18-C 1321-3RA18-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    Heavy 1321-3R18-C 1321-3RA18-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    15 20 Normal 1321-3R25-C 1321-3RA25-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    Heavy 1321-3R25-C 1321-3RA25-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    18.5 25 Normal/Heavy 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    22 30 Normal 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    30 40 Normal 1321-3R45-C 1321-3RA45-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    Heavy 1321-3R45-C 1321-3RA45-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    37 50 Normal 1321-3R55-C 1321-3RA55-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    Heavy 1321-3R55-C 1321-3RA55-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    55 75 Normal/Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    75 100 Normal/Heavy 1321-3R100-C 1321-3RA100-C 1321-3R100-C 1321-3RA100-C   ü   ü   ü
    90 125 Normal/Heavy 1321-3R130-C 1321-3RA130-C 1321-3R130-C 1321-3RA130-C   ü   ü   ü
    110 150 Normal 1321-3R160-C 1321-3RA160-C 1321-3R160-C 1321-3RA160-C   ü   ü   ü
    Heavy 1321-3R160-C 1321-3RA160-C     ü ⋆       
    Normal 1321-3R200-C 1321-3RA200-C     ü ∆       
    149 200 Normal 1321-3R200-B 1321-3RA200-B     ü ⋆       
    Heavy 1321-3R200-C 1321-3RA200-C     ü ⋆       
    187 250 Normal/Heavy 1321-3RB250-C 1321-3RAB250-C     ü ⋆       
    300 Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    200 Heavy 1321-3R250-C 1321-3RA250-C 1321-3R250-C 1321-3RA250-C           ü
    350 Light/Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    250 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    261 350 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C     ü ⋆       
    400 Light/Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    298 400 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C     ü ⋆       
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ⋆ 4% impedance.
    ∆ 3% impedance.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 5% Impedance (continued)
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    300 Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    315 Light/Normal 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    450 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    336 450 Normal 1321-3R500-C 1321-3RA500-C     ü ⋆       
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü      
    500 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    355 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    373 500 Normal/Heavy 1321-3R500-C 1321-3RA500-C     ü      
    550 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    375 Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    400 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    448 600 Normal 1321-3R600-C 1321-3RA600-C     ü ⋆       
    600 Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    450 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    485 650 Heavy 1321-3RB320-C 1321-3RAB320-C     ü ⋆ §       
    500 Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    522 700 Normal 1321-3RB320-C 1321-3RAB320-C     ü ⋆ §       
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü ⋆ §       
    700 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    530 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    750 Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    560 Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    597 800 Normal 1321-3RB400-C 1321-3RAB400-C     ü ⋆ §       
    800 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    630 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    671 900 Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    Heavy 1321-3R500-C 1321-3RA500-C     ü ⋆ §       
    900 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    950 Light/Normal 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    710 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    746 1000 Normal 1321-3R500-C 1321-3RA500-C     ü ⋆ §       
    Heavy 1321-3R1000-C 1321-3RA1000-C     ü ⋆       
    750 Normal 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    1000 Light/Normal 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    800 Light/Normal/Heavy 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    821 1100 Normal 1321-3R1000-C 1321-3RA1000-C     ü ⋆       
    Heavy 1321-3R600-C 1321-3RA600-C     ü ⋆ §       
    1100 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    850 Light 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    900 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    970 1300 Normal 1321-3R600-C 1321-3RA600-C     ü ⋆ §       
    1000 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    1100 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    1200 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    1500 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    1500 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ⋆ 4% impedance.
    § Requires two output reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.

    For details, refer to the PowerFlex 750-Series Technical Data.

    Certifications
    ABS (Frames 2…7, 400/480V AC) American Bureau of Shipping Certificate 11-HS743429-PDA
    C-Tick Australian Communications and Media Authority
    In conformity with the following:
        Radiocommunications Act: 1992
        Radiocommunications Standard: 2008
        Radiocommunications Labelling Notice: 2008
    Standards applied:
        EN 61800-3:2004
    c-UL-us Listed to UL508C and CAN/CSA-C22.2 No. 14-05.
    CE In conformity with the following European Directives:
        EMC Directive (2004/108/EC)
        Low Voltage Directive (2006/95/EC)
    Standards applied:
        EN 61800-3:2004
        EN 61800-5-1:2007
    EPRI/SEMI F47 Electric Power Research Institute
    Certified compliant with the following standards:
        SEMI F47
        IEC 61000-4-34
    GOST-R (Frames 2…7, 400/480V AC) Russian GOST-R Certificate no.
        POCC US.ME92.H00040
    Lloyds Register (Frames 2…7, 400/480V AC) Lloyd’s Register Type Approval Certificate 11/60008
    RINA (Frames 2…7, 400/480V AC) RINA Certificate ELE349811CS
    TÜV TÜV Rheinland
    Certification applies to 20-750-S and 20-750-S1 Safety Options when installed in drive.
    Standards applied:
        EN 61800-3:2004
        EN 61800-5-1:2007
        EN ISO 13849-1:2008
        EN ISO 13849-2:2003
        EN 61800-5-2:2007
        EN 61508 PARTS 1-7:2000
        EN 62061:2005
        EN 60204-1:2006

    Environmental Specifications
    Category Specification
    Altitude:
        Based on Load:
        Based on Voltage:

    Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001) for Derating Guidelines.
    System & Ground Configuration
    Center Grounded (Y Neutral) w/Solid Ground


    Ungrounded, Impedance Grounded, or Corner Grounded
    Overvoltage Category (1)
    II (2)
    III (3)

    II (2)
    III (3)
    Altitude Limit at 400/480V AC (2) (5)
    9000 m above sea level (3)
    4800 m above sea level

    4800 m above sea level
    2000 m above sea level
    Altitude Limit at 600V AC (2) (5)
    7500 m above sea level (3)
    4800 m above sea level

    7500 m above sea level (3)
    4800 m above sea level
    Altitude Limit at 690V AC (2) (5)
    7500 m above sea level (3)
    4800 m above sea level

    4800 m above sea level
    2000 m above sea level
    Notes: Based on EN61800-5-1 (Electro-thermal Safety Standard for drives)
    (1) Overvoltage Categories:
    Category II (Isolation Transformer Level) - Typically two levels of isolation or protection from outdoor power lines.
    Category III (Most Common) Distribution Level Inside a Building - Typically one level of isolation or protection from outdoor power lines.

    (2) Excluding failure from cosmic radiation. Cosmic radiation will increase rate of IGBT malfunction at altitudes greater than 3000 m above sea level. Concrete walls and ceilings or concrete walls and large bottles of water overhead are examples of ways to shield against cosmic radiation.

    (3) Drive is limited to a maximum of 4800 m thermally. Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001) for Derating Guidelines.

    (4) In CE installations, Frame 1 does not support ungrounded or corner grounded configurations.

    (5) Frame 1 drives are limited to a maximum of 2000 m thermally. Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001) for Derating Guidelines.
    Maximum Surrounding Air Temperature




    Flange Mount, Front


    Flange Mount, Back/Heat Sink

    Stand-alone/Wall Mount
    IP20, NEMA/UL Open Type:
    IP00, NEMA/UL Open Type:
    IP20, NEMA/UL Type 1 (w/Hood):
    IP20, NEMA/UL Type 1 (w/Label):

    IP20, NEMA/UL Open Type:
    IP00, NEMA/UL Open Type:

    IP66, NEMA/UL Type 4X:

    IP54, NEMA/UL Type 12:
    Frame 1…5, All Ratings:
    Frame 6…7, All Ratings:
    Frame 1…5, All Ratings:
    Frame 6…7, All Ratings:

    Frame 2…5, All Ratings:
    Frame 6…7, All Ratings:

    Frame 2…7, All Ratings:

    Frame 2…7, All Ratings:
    0…50 °C (32…122 °F)
    0…50 °C (32…122 °F)
    0…40 °C (32…104 °F)
    0…40 °C (32…104 °F)

    0…50 °C (32…122 °F)
    0…50 °C (32…122 °F)

    0…40 °C (32…104 °F)

    0…40 °C (32…104 °F)
    Storage Temperature (All Const.): -40…70 °C (-40…158 °F)
    Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
    UV Radiation The HIM and IP54, NEMA/UL Type 12 drive plastics are not UV rated.
    Relative Humidity: 5 to 95% non-condensing
    Shock: Operating
        Frame 1…6:
        Frame 7:

    15 g peak for 11 ms duration (±1.0 ms)
    10 g peak for 11 ms duration (±1.0 ms)
    Packaged for Shipment
        Frame 1…2:
        Frame 3…4:
        Frame 5:
        Frame 6…7:

    381 mm (15 in.) drop height
    330 mm (13 in.) drop height
    305 mm (12 in.) drop height
    Meets International Safe Transit Association (ISTA) test procedure 2B
    Vibration: Operating
        Frame 1…2:
        Frame 3…5:
        Frame 6…7:

    1.000 mm (0.040 in.) displacement, 2 g peak
    1.000 mm (0.040 in.) displacement, 1.5 g peak
    1.000 mm (0.040 in.) displacement, 1 g peak
    Packaged for Shipment - Sinusoidal Loose Load
        Frame 1…5:
        Frame 6…7:

    20.0 mm (0.8 in.) peak to peak, 2…5.186 Hz; 1.1 g peak from 5.186…20 Hz
    Meets ISTA 2B packaging standards
    Random Secured
        Frame 1…5:





        Frame 6…7:
    Frequency (Hz)/PSD (g2/Hz)
    1/0.00005
    4/0.01
    16/0.01
    40/0.001
    80/0.001
    200/0.00001
    Meets International Safe Transit Association (ISTA) test procedure 2B
    Required Airflow:
        Frame 1…2:
        Frame 3:
        Frame 4:
        Frame 5:
        Frame 6:
        Frame 7:
    Total Fan Air Flow
    0.024 CMS (50 CFM)
    0.038 CMS (80 CFM)
    0.151 CMS (320 CFM)
    0.245 CMS (520 CFM)
    0.238 CMS (504CFM)
    0.357 CMS (756 CFM)
    Sound:
        Frame 1…2:
        Frame 3:
        Frame 4:
        Frame 5:
        Frame 6:
        Frame 7:
    Sound Level
    63 dB
    64 dB
    72 dB
    77 dB
    73 dB
    74 dB
    (Sound pressure is measured at 2 m)
    Surrounding Environment Pollution Degree
        Pollution Degree 1 & 2:
        Pollution Degree 3 & 4:

    All enclosures acceptable.
    Enclosure that meets or exceeds IP54, NEMA/UL Type 12 required.

    Technical Specifications
    Category Specification Motor Voltage
    380…400V 480V 600V 690V
    Protection AC Input Overvoltage Trip: 576V AC 576V AC 825V AC 825V AC
    AC Input Undervoltage Trip: 250V AC 300V AC 400V AC 400V AC
    Bus Overvoltage Trip: 815V DC 815V DC 1167V DC 1167V DC
    Bus Undervoltage Shutoff: 200V DC 200V DC 200V DC (Frames 3…7) 200V DC (Frames 6…7)
    Nominal Bus Voltage: 540V DC 648V DC 810V DC 932V DC
    Drive Overcurrent Trip
        Software Overcurrent Limit:
        Instantaneous Current Limit:
        Hardware Overcurrent Limit:

    200% of drive rated
    100% of 3 sec. rating (158…210%)
    143% of 3 sec. rating (215…287%)
    Line transients: up to 6000 volts peak per IEEE C62.41-1991
    Control Logic Noise Immunity: Showering arc transients up to 1500V peak
    Power Ride-Thru: 15 milliseconds at full load
    Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
    Ground Fault Trip: Phase-to-ground on drive output
    Short Circuit Trip: Phase-to-phase on drive output
    Electrical AC Input Voltage Tolerance: Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001)
    Frequency Tolerance: 47…63 Hz
    Input Phases: Three-phase input provides full rating for all drives. Single-phase operation on Frames 1…7 provides up to 50% of rated current at 25 °C (77 °F) surrounding temperature.
    DC Input Voltage Tolerance: ±10% of Nominal Bus Voltage (above)
    Displacement Power Factor: 0.98 across entire speed range
    DC Link Impedance: Greater than or equal to 5%
    Efficiency: 97.5% at rated amps, nominal line volts
    Maximum Short Circuit Rating: 200,000 Amps RMS symmetrical (20F & 20G drives only)
    Actual Short Circuit Rating: Determined by AIC rating of installed fuse/circuit breaker
    Drive to Motor Power Ratio
        Minimum:
        Maximum:

    Recommended not less than 1:2 ratio
    Recommended not greater than 2:1 ratio
    Brake IGBT Rating: 100% of motor rated torque
    Control POD Current Draw: 5A
    Digital Inputs
        Nominal:
        Maximum:
        High State:
        Low State:
    DC
    24V DC
    30V DC
    20…24V DC
    0…5V DC
    AC
    120V AC
    132V AC
    100…132V AC
    0…30V AC
    Battery: User installed CR1220 lithium coin cell battery provides power to the real time clock (optional, not supplied). Preserves the clock setting in the event power to the drive is lost or cycled. Approximate life is 4.5 years with dive unpowered, or lifetime if drive is powered.
    Control Method: Sine coded PWM with programmable carrier frequency. Ratings apply to all drives.
    Carrier Frequency
        Default Settings:


        Settings:


    Frame 1…4: 4 kHz
    Frame 5…7: 2 kHz

    Frame 1…6: 2, 4, 8, 12 kHz
    Frame 7: 2, 4, 8 kHz
    Output Voltage Range: 0 to rated motor voltage
    Output Frequency Range: 0…325 Hz at 2 kHz carrier, 0…650 Hz at 4 kHz carrier
    Frequency Accuracy
        Digital Input:
        Analog Input:

    Within ±0.01% of set output frequency
    Within ±0.4% of maximum output frequency
    Frequency Control: Speed regulation - with Slip Compensation (V/Hz & Sensorless Vector modes)
    0.5% of base speed across 40:1 speed range, 40:1 operating range
    Speed Control: Without feedback (Flux Vector mode), 0.1% of base speed across 100:1 speed range, 120:1 operating range, 50 rad/sec bandwidth
    With feedback (Flux Vector mode), 0.001% of base speed across 100:1 speed range, 1000:1 operating range, 190 rad/sec bandwidth
    Torque Regulation: Without feedback (Flux Vector mode), ±5%, 600 rad/sec bandwidth
    With feedback (Flux Vector mode), ±2%, 2500 rad/sec bandwidth
    Selectable Motor Control: - Standard V/Hz with full custom capability
    - Sensorless Vector with full tuning
    - Flux Vector with and without a feedback device
    - Induction motor control
    - Surface mount permanent magnet motor control with encoder feedback (Frames 1…7)
    - Surface mount permanent magnet motor control without encoder feedback (Frames 1…7)
    - Internal permanent magnet motor control with encoder feedback (Frames 1…7)
    Stop Modes: Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold, Fast Braking, and Current Limit Stop.
    Accel/Decel: Two independently programmable accel and decel times. Each time may be programmed from 0 to 3600 seconds in 0.1 second increments (0 to motor nameplate speed).
    S Curve Time: Adjustable from 0 to 100% of ramp time (normal duty rating).
    Intermittent Overload:
        Normal Duty

        Heavy Duty

    110% Overload capability for up to 1 minute out of 10 minutes
    150% Overload capability for up to 3 seconds out of 60 seconds
    150% Overload capability for up to 1 minute out of 10 minutes
    180% Overload capability for up to 3 seconds out of 60 seconds
    Current Limit Capability: Proactive Current Limit programmable from 20 to 160% of rated output current. Independently programmable proportional and integral gain.
    Electronic Motor Overload Protection: Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C File E59272.
      

    For detailed dimensions, refer to the PowerFlex 750-Series Technical Data.

    Dimensions are in mm (in.) - weights are in kg (lb)

    Click to enlarge - dim_outline


    IP00/IP20, NEMA/UL Type Open
    Frame H W D Weight
    1 400.5 (15.77) 110.0 (4.33) 211.0 (8.31) 6.00 (12.75)
    2 424.2 (16.70) 134.5 (5.30) 212.0 (8.35) 7.80 (17.2)
    3 454.0 (17.87) 190.0 (7.48) 212.0 (8.35) 11.80 (26.1)
    4 474.0 (18.66) 222.0 (8.74) 212.0 (8.35) 13.60 (30.0)
    5 550.0 (21.65) 270.0 (10.63) 212.0 (8.35) 20.40 (45.0)
    6 665.5 (26.20) 308.0 (12.13) 346.4 (13.64) 38.60 (85.0)
    7 881.5 (34.70) 430.0 (16.93) 349.6 (13.76) 72.60…108.90 (160.0…240.0)




    Click to enlarge - dim_outline_flng


    Flange Mount
    Frame H W D1 D2 Weight ⋆ 
    2 481.8 (18.97) 206.2 (8.12) 148.3 (5.84) 63.7 (2.51) 8.00 (17.0)
    3 515.0 (20.28) 260.0 (10.24) 127.4 (5.02) 84.6 (3.33) 12.00 (26.0)
    4 535.0 (21.06) 292.0 (11.50) 127.4 (5.02) 84.6 (3.33) 14.00 (30.0)
    5 611.0 (24.06) 340.0 (13.39) 127.4 (5.02) 84.6 (3.33) 20.00 (45.0)
    6 665.5 (26.20) 308.0 (12.13) 208.4 (8.20) 138.0 (5.43) 38.00 (84.0)
    7 875.0 (34.45) 430.0 (16.93) 208.4 (8.20) 138.0 (5.43) 96.00 (212.0)
    ⋆ Weights are approximate. Refer to the PowerFlex 750-Series Technical Data for detailed weight information.




    Click to enlarge - dim_outline


    IP54, NEMA/UL Type 12
    Frame H W D Weight ⋆ 
    2 543.2 (21.39) 215.3 (8.48) 222.2 (8.75) 8.00 (17.0)
    3 551.0 (21.69) 268.0 (10.55) 220.1 (8.67) 12.00 (26.0)
    4 571.0 (22.48) 300.0 (11.81) 220.1 (8.67) 14.00 (30.0)
    5 647.0 (25.47) 348.0 (13.70) 220.1 (8.67) 20.00 (45.0)
    6 1298.3 (51.11) 609.4 (23.99) 464.7 (18.30) 91.00 (200.0)
    7 1614.0 (63.54) 609.4 (23.99) 464.7 (18.30) 162.00 (357.0)
    ⋆ Weights are approximate. Refer to the PowerFlex 750-Series Technical Data for detailed weight information.