Drives Catalog

Catalogs > Drives Catalog > PowerFlex 700S

PowerFlex 700S

Introduction Conformity to Standards Drive Description Catalog Number Explanation
Hardware Control Options Factory Installed Options User Installed Options Drive Application Software
Catalog Number Explanation

20D    D    2P1    A    0    E    Y    N    A    N    A    N    E
a    b    c    d    e    f    g    h    i    j    k    l    m

a
Drive
Code Type
20D PowerFlex 700S

b
Voltage Rating
Code Voltage Ph. Prechg.
B §  240V AC 3
C §  400V AC 3
D §  480V AC 3
E §  §  600V AC 3
F z  690V AC 3
H z  540V DC N
J z  650V DC N
K z  810V DC N
M z  932V DC N
N Ø  325V DC Y
P Ø  540V DC Y
R Ø  650V DC Y
T Ø  810V DC Y
W Ø  932V DC Y
§ Note: CE Certification testing has not been performed on 600V class drives, Frames 1…4.
Ø Frames 5 & 6 Only.
z Frames 5 & up.
§ For DC input on Frames 1…4, use the corresponding AC input code B, C, D, or E.

c1
ND Rating
208/240V, 60Hz Input
Code 208V Amps 240V Amps Hp
4P2 4.8 4.2 1.0
6P8 7.8 6.8 2.0
9P6 11 9.6 3.0
015 17.5 15.3 5.0
022 25.3 22 7.5
028 32.2 28 10
042 48.3 42 15
052 56 52 20
070 78.2 70 25
080 92 80 30
104 120 104 40
130 130 130 50
154 177 154 60
192 221 192 75
260 260 260 100

c2
ND Rating
400V, 50 Hz Input
Code Amps kW
2P1 2.1 0.75
3P5 3.5 1.5
5P0 5.0 2.2
8P7 8.7 4.0
011 11.5 5.5
015 15.4 7.5
022 22 11
030 30 15
037 37 18.5
043 43 22
056 56 30
072 72 37
085 85 45
105 105 55
125 125 55
170 170 90
205 205 110
260 260 132
261 261 132
300 300 160
385 385 200
460 460 250
500 500 250
590 590 315
650 650 355
730 730 400
820 820 450
920 920 500
1K0 1030 560
1K1 1150 630
1K3 1300 710
1K4 1450 800

c3
ND Rating
480V, 60 Hz Input
Code Amps Hp
2P1 2.1 1.0
3P4 3.4 2.0
5P0 5 3.0
8P0 8 5.0
011 11 7.5
014 14 10
022 22 15
027 27 20
034 34 25
040 40 30
052 52 40
065 65 50
077 77 60
096 96 75
125 125 100
156 156 125
180 180 150
248 248 200
261 261 200
300 300 250
385 385 300
460 460 350
500 500 450
590 590 500
650 650 500
730 730 600
820 820 700
920 920 800
1K0 1030 900
1K1 1150 1000
1K3 1300 1200
1K4 1450 1250

c4
ND Rating
600V, 60Hz Input § 
Code Amps Hp
1P7 1.7 1
2P7 2.7 2
3P9 3.9 3
6P1 6.1 5
9P0 9 7.5
011 11 10
017 17 15
022 22 20
027 27 25
032 32 30
041 41 40
052 52 50
062 62 60
077 77 75
099 99 100
125 125 125
144 144 150
170 170 150
208 208 200
261 261 250
325 325 350
385 385 400
416 416 450
460 460 450
502 502 500
590 590 600
650 650 700
750 750 800
820 820 900
920 920 1000
1K0 1030 1100
1K1 1180 1300
1K5 1500 1600
§ Note: CE Certification testing has not been performed on 600V class drives Frames 1…4.

c5
ND Rating
690V, 50 Hz Input § 
Code Amps kW
052 52 45
060 60 55
082 82 75
098 98 90
119 119 110
142 142 132
170 170 160
208 208 200
261 261 250
325 325 315
385 385 355
416 416 400
460 460 450
502 502 500
590 590 560
650 650 630
750 750 710
820 820 800
920 920 900
1K0 1030 1000
1K1 1180 1100
1K5 1500 1500
§ Note: CE Certification testing has not been performed on 600V class drives Frames 1…4.

d
Enclosure
Code Enclosure
A IP20, NEMA Type 1
B §  IP21, NEMA Type 1, MCC
N ª  Open/IP00
ª Frames 9 & up Only.
§ Frames 10-12 Only.

e
HIM
Code Operator Interface
0 Blank Cover
2 Digital LCD
3 Full Numeric LCD
5 Prog. Only LCD
C Full Numeric LCD, Door Mount T 
T Frames 10 & up only.

f
Documentation
Code Documents
E Documentation
N No Documentation

g
Brake
Code w/Brake IGBT ‡ 
Y Yes
N No
‡ Brake IGBT is standard on Frames 1…3 and optional on Frames 4…9 ONLY.

h
Brake Resistor
Code w/Resistor
Y Yes ¬ 
N No
¬ Not available for Frame 3 drives or larger.

i
Emission
Code CE Filter §  CM Choke dv/dt Filter
A v  Yes Yes No
B Ø  Yes No No
E ª  Yes No Yes
N §  No No No
v Frames 1…6 only.
Ø Frames 9…14 only.
ª Frame 14 drives only.
§ For use on a high resistive ground, an ungrounded distribution system, or a B phase grounded distribution system (Frame 9 only).
§ Note: CE Certification testing has not been performed on 600V class drives Frames 1…4.

j
Comm Slot
Code Version
N None
C DPI ControlNet (Coax)
D DPI DeviceNet
E DPI EtherNet/IP
R DPI RIO
S DPI RS-485 DF1
1 DriveLogix ControlNet (Coax)
2 DriveLogix ControlNet Redundant (Coax)
3 DriveLogix ControlNet (Fiber)
4 DriveLogix ControlNet Redundant (Fiber)
5 DriveLogix DeviceNet (Open Conn.)
6 DriveLogix EtherNet/IP

k
Control Options
Code Control Option Logic Expansion Synch-Link Cassette
A Phase II No No Expanded
B Phase II No Yes Expanded
C Phase II Yes No Expanded
D Phase II Yes Yes Expanded
G Phase II N/A No Slim
H Phase II N/A Yes Slim

l
Feedback
Code Option
N z  Standard (Incremental Encoder)
A v  Resolver
B v  Stegmann Hi-Resolution Encoder
C v  Multi-Device Interface
E v  2nd Encoder
S v  Safe-Off (w/2nd Encoder)
v Expanded cassette required.
z One encoder interface is included with the base drive.

m
Additional Config.
Code Description
E Phase II Control
K Phase II DriveLogix5730
L ª  Phase II DriveLogix5730 w/EtherNet/IP
ª This is an embedded EtherNet option that is only available with DriveLogix5730.