Catalogs >
Drives Catalog >
PowerFlex Fan/Pump Applications
PowerFlex Fan/Pump Applications
Catalog Number Explanation
To interpret the meaning of a catalog number, match the values of the catalog number code in positions a, b, c, etc. with the tables labeled a, b, c, etc. below.
| 21V
|
|
D
|
|
2P1
|
|
A
|
|
3
|
|
A
|
|
Y
|
|
N
|
|
A
|
|
R
|
|
C
|
|
0
|
|
B
|
|
N
|
-
|
LR
|
| a
|
|
b
|
|
c
|
|
d
|
|
e
|
|
f
|
|
g
|
|
h
|
|
i
|
|
j
|
|
k
|
|
l
|
|
m
|
|
n
|
|
o
|
| a
|
| Drive
|
| Code
|
Type
|
| 21V
|
PowerFlex 70 Drive
|
| 21W
|
PowerFlex 700 Drive
|
| b
|
| Voltage Rating
|
| Code
|
Voltage
|
Ph.
|
| X
|
208V AC
|
3
|
| D
|
480V AC
|
3
|
| E
|
600V AC
|
3
|
| c1
|
| ND Rating
|
| 208V, 60Hz Input
|
| Code
|
Amps
|
Frame
|
kW (HP)
|
| 4P2
|
4.8
|
B
|
0.75 (1.0)
|
| 6P8
|
7.8
|
B
|
1.5 (2.0)
|
| 9P6
|
11
|
B
|
2.2 (3.0)
|
| 015
|
17.5
|
C
|
4.0 (5.0)
|
| 022
|
25.3
|
D
|
5.5 (7.5)
|
| 028
|
32.2
|
D
|
7.5 (10)
|
| 042
|
43
|
D
|
11 (15)
|
| c2
|
| ND Rating
|
| 480V, 60Hz Input
|
| Code
|
Amps
|
Frame
|
kW (HP)
|
| 2P1
|
2.1
|
B
|
0.75 (1.0)
|
| 3P4
|
3.4
|
B
|
1.5 (2.0)
|
| 5P0
|
5.0
|
B
|
2.2 (3.0)
|
| 8P0
|
8.0
|
B
|
4.0 (5.0)
|
| 011
|
11
|
C
|
5.5 (7.5)
|
| 014
|
14
|
C
|
7.5 (10)
|
| 022
|
22
|
D
|
11 (15)
|
| 027
|
27
|
D
|
15 (20)
|
| 034
|
34
|
D
|
18.5 (25)
|
| 040
|
40
|
D
|
22 (30)
|
| 052
|
52
|
E
|
30 (40)
|
| 065
|
65
|
E
|
37 (50)
|
| 077 §
|
77
|
4
|
45 (60)
|
| 096 §
|
96
|
5
|
55 (75)
|
| 125 §
|
125
|
5
|
75 (100)
|
| 156 §
|
156
|
6
|
90 (125)
|
| 180 §
|
180
|
6
|
110 (150)
|
| 248 §
|
248
|
6
|
132 (200)
|
| § PowerFlex 700 options only.
|
| c3
|
| ND Rating
|
| 600V, 60Hz Input
|
| Code
|
Amps
|
Frame
|
kW (HP)
|
| 3P9
|
3.9
|
B
|
2.2 (3.0)
|
| 6P1
|
6.1
|
B
|
4.0 (5.0)
|
| 9P0
|
9.0
|
C
|
5.5 (7.5)
|
| 011
|
11
|
C
|
7.5 (10)
|
| 017
|
17
|
D
|
11 (15)
|
| 022
|
22
|
D
|
15 (20)
|
| 027
|
27
|
D
|
18.5 (25)
|
| 032
|
32
|
D
|
22 (30)
|
| 041
|
41
|
E
|
30 (40)
|
| 052
|
52
|
E
|
37 (50)
|
| 062 §
|
62
|
4
|
45 (60)
|
| 077 §
|
77
|
5
|
55 (75)
|
| 099 §
|
99
|
5
|
75 (100)
|
| 125 §
|
125
|
6
|
90 (125)
|
| 144 §
|
144
|
6
|
110 (150)
|
| § PowerFlex 700 options only.
|
| d
|
| Enclosure
|
| Code
|
Enclosure
|
| A
|
IP 20, NEMA Type 1
|
| e
|
| HIM
|
| Code
|
Operator Interface
|
| 0
|
Blank Cover
|
| 3
|
Full Numeric LCD
|
| 5
|
Prog. Only LCD
|
| f
|
| Documentation
|
| Code
|
Type
|
| A
|
User Manual
|
| g
|
| Brake IGBT
|
| Code
|
w/Brake IGBT
|
| Y
|
Yes
|
| N §
|
No
|
| Brake IGBT is standard on PowerFlex 70 Frames B, C, D and E, and optional on PowerFlex 700 Frames 4, 5 and 6.
|
| § PowerFlex 700 options only.
|
| h
|
| Internal Brake Resistor
|
| Code
|
w/Resistor
|
| Y
|
Yes§
|
| N
|
No
|
| § Brake resistor only available for PowerFlex 70: 208V Frames B, C & D, 480V Frames B, C & D, 600V Frames B and C.
|
| i
|
| Emission
|
| Code
|
CE Filter
|
| A
|
Yes
|
| N¬
|
No
|
| ¬ PowerFlex 70 600V ratings only.
|
| j
|
| Comm Slot
|
| Code
|
Version
|
| B
|
BACnet®
|
| C
|
ControlNet™ (Coax)
|
| D
|
DeviceNet™
|
| E
|
EtherNet/IP™
|
| H
|
RS485 HVAC
|
| I
|
Interbus™
|
| L
|
LonWorks®
|
| P
|
PROFIBUS™ DP
|
| Q
|
ControlNet™ (Fiber)
|
| R
|
Remote I/O
|
| S
|
RS485 DF1
|
| N
|
None
|
| k
|
| Control & I/O
|
| Code
|
Control
|
I/O Volts
|
| A§
|
Standard
|
24V DC/AC
|
| CT
|
Enhanced
|
24V DC
|
| § PowerFlex 700 options only.
|
| T PowerFlex 70 options only.
|
| l
|
| Feedback
|
| Code
|
Feedback
|
| 0
|
None (PowerFlex 70)
|
| N
|
None (PowerFlex 700)
|
| m
|
| Package
|
| Code
|
Description
|
| A
|
Main Input Disconnect
|
| B
|
3 Contactor Full Feature Bypass with Disconnect
|
| C
|
3 Contactor Basic Bypass with Disconnect
|
| o
|
| Options
|
| Code
|
Description
|
| LR
|
Input Line Reactor Ø
|
| Ø Only available with Package Code A and B drives 1.0…10 HP @ 208V, 1.0…25 Hp @ 480V and 3.0…25 HP @ 600V.
|