Drives Catalog

Catalogs > Drives Catalog > PowerFlex Fan/Pump Applications

PowerFlex Fan/Pump Applications

Introduction Conformity to Standards Drive Description Overview
Catalog Number Explanation Available Packaging Selections Product Selection Factory Installed Options
Catalog Number Explanation

To interpret the meaning of a catalog number, match the values of the catalog number code in positions a, b, c, etc. with the tables labeled a, b, c, etc. below.

21V    D    2P1    A    3    A    Y    N    A    R    C    0    B    N - LR
a    b    c    d    e    f    g    h    i    j    k    l    m    n    o

a
Drive
Code Type
21V PowerFlex 70 Drive
21W PowerFlex 700 Drive

b
Voltage Rating
Code Voltage Ph.
X 208V AC 3
D 480V AC 3
E 600V AC 3

c1
ND Rating
208V, 60Hz Input
Code Amps Frame kW (HP)
4P2 4.8 B 0.75 (1.0)
6P8 7.8 B 1.5 (2.0)
9P6 11 B 2.2 (3.0)
015 17.5 C 4.0 (5.0)
022 25.3 D 5.5 (7.5)
028 32.2 D 7.5 (10)
042 43 D 11 (15)

c2
ND Rating
480V, 60Hz Input
Code Amps Frame kW (HP)
2P1 2.1 B 0.75 (1.0)
3P4 3.4 B 1.5 (2.0)
5P0 5.0 B 2.2 (3.0)
8P0 8.0 B 4.0 (5.0)
011 11 C 5.5 (7.5)
014 14 C 7.5 (10)
022 22 D 11 (15)
027 27 D 15 (20)
034 34 D 18.5 (25)
040 40 D 22 (30)
052 52 E 30 (40)
065 65 E 37 (50)
077 §  77 4 45 (60)
096 §  96 5 55 (75)
125 §  125 5 75 (100)
156 §  156 6 90 (125)
180 §  180 6 110 (150)
248 §  248 6 132 (200)
§ PowerFlex 700 options only.

c3
ND Rating
600V, 60Hz Input
Code Amps Frame kW (HP)
3P9 3.9 B 2.2 (3.0)
6P1 6.1 B 4.0 (5.0)
9P0 9.0 C 5.5 (7.5)
011 11 C 7.5 (10)
017 17 D 11 (15)
022 22 D 15 (20)
027 27 D 18.5 (25)
032 32 D 22 (30)
041 41 E 30 (40)
052 52 E 37 (50)
062 §  62 4 45 (60)
077 §  77 5 55 (75)
099 §  99 5 75 (100)
125 §  125 6 90 (125)
144 §  144 6 110 (150)
§ PowerFlex 700 options only.

d
Enclosure
Code Enclosure
A IP 20, NEMA Type 1

e
HIM
Code Operator Interface
0 Blank Cover
3 Full Numeric LCD
5 Prog. Only LCD

f
Documentation
Code Type
A User Manual

g
Brake IGBT
Code w/Brake IGBT ‡ 
Y Yes
N §  No
‡ Brake IGBT is standard on PowerFlex 70 Frames B, C, D and E, and optional on PowerFlex 700 Frames 4, 5 and 6.
§ PowerFlex 700 options only.

h
Internal Brake Resistor
Code w/Resistor
Y Yes§ 
N No
§ Brake resistor only available for PowerFlex 70: 208V Frames B, C & D, 480V Frames B, C & D, 600V Frames B and C.

i
Emission
Code CE Filter
A Yes
N¬  No
¬ PowerFlex 70 600V ratings only.

j
Comm Slot
Code Version
B BACnet®
C ControlNet™ (Coax)
D DeviceNet™
E EtherNet/IP™
H RS485 HVAC
I Interbus™
L LonWorks®
P PROFIBUS™ DP
Q ControlNet™ (Fiber)
R Remote I/O
S RS485 DF1
N None

k
Control & I/O
Code Control I/O Volts
A§  Standard 24V DC/AC
CT  Enhanced 24V DC
§ PowerFlex 700 options only.
T PowerFlex 70 options only.

l
Feedback
Code Feedback
0 None (PowerFlex 70)
N None (PowerFlex 700)

m
Package
Code Description
A Main Input Disconnect
B 3 Contactor Full Feature Bypass with Disconnect
C 3 Contactor Basic Bypass with Disconnect

n
Reserved

o
Options
Code Description
LR Input Line Reactor Ø 
Ø Only available with Package Code A and B drives 1.0…10 HP @ 208V, 1.0…25 Hp @ 480V and 3.0…25 HP @ 600V.