1336 REGEN Line Regenerative Package
1336 REGEN Line Regeneration Package
|
Standards Compliance
The 1336 REGEN conforms to the following:
| Conformity to: | Standard Product |
| UL Listed | ü |
| CSA Certified (c-UL) | ü |
Description
The 1336 REGEN Line Regeneration Package can be configured to address the needs of two operating modes; the Regenerative DC Bus Supply mode and the Regenerative Brake mode. The selected operating mode will result in different implementation costs and hardware requirements.
In the Regenerative Brake Mode the 1336 REGEN is used to remove braking energy from the DC bus and return it back to the three-phase AC utility. In many regenerative applications, the 1336 REGEN offers an energy-efficient alternative to dynamic brakes and chopper module/resistor combinations.
In the Regenerative DC Bus Supply Mode, the 1336 REGEN supplies both motoring and regenerative current to one or more DC input drives.
When the net power requirements of the attached common bus drives demand motoring power, energy flows from the utility to the common DC bus. When the net power requirements of the attached common bus drives demand regenerative power, energy flows from the common DC bus to the utility.
Catalog Number Explanation
| 1336R | - | VB | 180 | - | AA | - | HAB | |
| a | b | c | d | e ¬ |
| a | |
| Product | |
| Code | Type |
| 1336R | 1336 REGEN |
| b | |||
| Drive Rating | |||
| Code | Input Voltage | Ph. | Hz |
| VB | 380…480V AC | 3 | 50/60 |
| c | |
| Rating | |
| Code | kW (Hp) |
| 048 | 38.4 (48.2) |
| 078 | 62.3 (78.2) |
| 180 | 143.7 (180.4) |
| d | |
| Enclosure | |
| Code | Rating |
| AA | IP 20 (NEMA Type 1) |
| AN | IP 00 (Open) |
| e | |
| HIM | |
| Code | Description |
| HAB | Blank - No Functionality |
| HAP | Programmer Only |
| ¬ IP20 (NEMA Type 1) - Field must be specified. | |
Product Selection
The 1336 REGEN Line Regeneration Package consists of:
- A converter that transforms a three-phase AC input source into a DC output source.
- A precharge unit that limits the inrush current and provides AC line voltage phase and magnitude information to the converter.
When configured as a regenerative brake, a 3% 1321 line reactor will be required to limit current harmonics on the AC line and to provide impedance between the regenerative brake and the attached drives. When configured as a regenerative DC bus supply, a 10% line reactor and an EMI filter/3% reactor combination for high frequency noise attenuation will be required.
The 3 or 10% 1321 line reactor and EMI filter are not included in the line regeneration package and must be ordered separately.
| 1336 REGEN Operating Mode Selection | ||
| Application Requirements | Regen DC Bus Supply Mode | Regen Brake Mode |
| Low Current Harmonics | X | |
| Multiple Drive Applications | X | |
| High Power Factor | ¬ | X |
| Equal Braking and Motoring HP | ¬ | X |
| Less Braking Than Motoring HP | ¬ | X |
| Single Drive Application | ¬ | X |
| Intermittent Braking or Low Braking Duty Cycle | ¬ | X |
| ¬ The Regenerative Bus Supply Mode can also be used for these applications, but will result in a more complex hardware configuration and a higher total system cost. Regenerative Bus Supply operation requires a custom Bulletin 1321 10% line reactor, while Regenerative Brake operation requires a standard Bulletin 1321 3% line reactor. The mode of operation is selected by a parameter setting in the 1336 REGEN Converter. | ||
| 1336 REGEN Frame Designations | ||||
| 1336 REGEN Converter Rating | 1336 REGEN Precharge Rating | |||
| Frame Reference | AC Input kW | Amp Rating | AC Input kW | Amp Rating |
| B | 38.4 | 48.2 | 38.4 | 48.2 |
| C | 62.3 | 78.2 | 62.3 | 78.2 |
| D | 143.7 | 180.4 | 143.7 | 180.4 |
1336 REGEN Brake Example
|
1336 REGEN Bus Supply Example
|
| 1336 REGEN Package (includes Converter & Precharge Module) |
||||
| Frame | Nominal Brake Rating | IP00 (Open) No Enclosure |
IP20 (NEMA Type 1) General Purpose |
|
| Input Amps | Output kW | Code | Code | |
| B | 48.2 | 38.4 | 1336R-VB048-AN | 1336R-VB048-AA |
| C | 78.2 | 62.3 | 1336R-VB078-AN | 1336R-VB078-AA |
| D | 180.4 | 143.7 | 1336R-VB180-AN | 1336R-VB180-AA |
1321 Line Reactors and EMI Filters
Refer to Line Reactor and Filter Selection for 1336 REGEN Package.
User Installed Options
| Human Interface Module Option Kits | ||
| Description | Used with … | Cat. No. |
| IP 20 (NEMA Type 1) HIM | ||
| All Open Chassis and IP 20 (NEMA Type 1) converter ratings | 1201-HAB | |
| 1201-HAP | ||
| Option Cable Kit - Connect to HIM Cradle Port | ||
| All HIMs not mounted on the converter chassis | 1202-H03 | |
| 1202-H10 | ||
| 1202-H30 | ||
| 1202-H90 | ||
| Gasket & Enclosure Kits | |||
| Description | Cat. No. | Cat. No. | |
| Gasket Kits for mounting 1336 REGEN Converter Units in User Supplied IP 54 or 65 (NEMA Type 12 or 4) Encl. | Frame B | 1336-RF4 | |
| Frame C | 1336-RF5 | ||
| Frame D | 1336-RF6 | ||
| Enclosure Kits for 1336 REGEN Converter IP 20 (NEMA Type 1) | Frame B | 1336R-AA4 | |
| Frame C | 1336R-AA5 | ||
| Frame D | 1336R-AA6 | ||
Factory Installed Options
| Interface Options | ||
| Description | Used with … | Cat. Code |
| (Position e) | ||
| Human Interface Module, IP 20 (NEMA Type 1) | ||
| IP 00 (Open) and IP 20 (NEMA Type 1) Drives | -HAB | |
| -HAP | ||
Specifications
| Electrical | |
| AC Input Voltage Range: | 380-480V AC, Three-Phase, +10%/15% Nominal, 48-62Hz 90-115V AC, Single-Phase, ±10% Nominal, 48-62Hz |
| Control Output Specifications | |
| Heat SinkTemperature Sensor Contact Output Rating (max.): |
The two temperature sensors trip if heat temperature exceeds 85°C. Resistive Rating: 15A at 125V AC, 10A at 250V AC, 7A at 24V DC Inductive Rating: 10A at 125V AC, 6A at 250V AC |
| Environmental Specifications | |
| Ambient Operating Temperature: | IP00 (Open): 0-50°C IP20 (NEMA Type 1): 0-40°C |
| Storage Temperature: | All Ratings -40 to +85°C |
| Relative Humidity: | 5 to 95% non-condensing |
| Shock: | 15G peak for 11ms duration (±1.0 ms) |
| Vibration: | 0.152 mm (0.006 in.) displacement, 1G peak |
| ESD Susceptibility, IP20 (NEMA Type 1) Only: | 15 kV |
| Protection | |
| AC Input Overvoltage Trip: | Factory Set to +15% of Nominal Line Voltage |
| Heatsink Over Temperature Trip: | 100° C |
| 1336R Converter Overcurrent Trip: | Software Overcurrent Limit - Factory Set to 192% of AC Input Current Hardware Overcurrent Limit - Factory Set to 245% of AC Input Current |
| Line Transients: | Up to 6000 Volts Peak per ANSI C62.41-1991 |
| Control Logic Noise Immunity: | Showering Arc Transients Up to 1500 Volts Peak |
| Power Ride-Thru: | 6 ms at Full Load |
| Control Logic Ride-Thru: | 0.5 Sec. Minimum, 2 Sec. Typical |
| Protection - Regenerative DC Bus Supply Mode | |
| Bus Overvoltage Trip: | 670V DC at 380V AC Input, 850V DC at 480V AC Input |
| Bus Undervoltage Trip: | 430V DC at 380V AC Input, 520V DC at 480V AC Input |
| Nominal Bus Voltage: | 610V DC at 380V AC Input, 735V DC at 480V AC Input |
| Regenerative DC Bus Supply Operation Only - 380-480V AC Input | ||||||
| Rating | Converter | Converter Heat Sink | Precharge Unit | 10% Line Reactor | Power Line Filter | Package Total |
| 48A | 141W | 820W | 15W | 186W | 173W | 1335W |
| 78A | 193W | 1110W | 29W | 258W | 236W | 1826W |
| 180A | 522W | 2664W | 58W | 474W | 317W | 4035W |
| Regenerative Brake Operation Only - 380-480V AC Input | |||||
| Rating | Converter | Converter Heat Sink | Precharge Unit | 3% Line Reactor | Package Total |
| 48A | 141W | 656W | 15W | 65W | 877W |
| 78A | 193W | 888W | 29W | 84W | 1194W |
| 180A | 522W | 2131W | 58W | 168W | 2879W |
Altitude Derating
|
1336 REGEN Converter Unit Mounting Dimensions
The dimensions and weights provided in the following drawings are for estimating purposes only. Contact your local Rockwell Automation Sales Office if certified drawings are required.
1336 REGEN Converter Unit - Frames B and C
|
1336 REGEN Converter Unit - Frame D
|
1336 REGEN Precharge Unit - Frames B and C
|
1336 REGEN Precharge Unit - Frame D
|