| Conformity to:
|
Approvals & Standards
|
| UL Listed
|
ü
|
UL 508C
|
| c-UL Listed
|
ü
|
CAN/CSA-C22.2 No. 14-M91
|
| CE Compliant ¬
|
ü
|
EN61800-3, EN50178
|
|
|
| ¬ SCR Bus Supply will meet the essential requirements for CE compliance provided an externally mounted line reactor and HF filter are used.
|
| a
|
| Product
|
| Code
|
Type
|
| 20S
|
SCR Bus Supply T
|
|
|
| T SCR Bus Supply available through Drive Systems only.
|
| e
|
| Documentation & Shipping Carton
|
| Code
|
User Manual
|
Carton
|
| E
|
English
|
Yes
|
| f
|
| Configuration
|
| Code
|
Type
|
| N
|
Stand Alone
|
| M
|
Master (1000A Only) ¬
|
| S
|
Slave (1000A Only) ¬
|
|
|
| ¬ PowerFlex SCR Bus Supply units with Master and Slave configurations are available for 480 & 690 volts, but only with a 1000A output current rating.
|
| PowerFlex SCR Bus Supplies
|
| Voltage
|
Description
|
Cat. No.
|
| 400/480V
|
400A, Stand Alone
|
20SD400NEN
|
| 600A, Stand Alone
|
20SD600NEN
|
| 1000A, Stand Alone
|
20SD1K0NEN
|
| 1000A, Master
|
20SD1K0NEM
|
| 1000A, Slave
|
20SD1K0NES
|
| 600/690V
|
1000A, Stand Alone
|
20SF1K0NEN
|
| 1000A, Master
|
20SF1K0NEM
|
| 1000A, Slave
|
20SF1K0NES
|
|
|
| Input Ratings
|
| Description/Cat.No.
|
20SD400
|
20SD600
|
20SD1K0
|
20SF1K0
|
| Nominal AC Input Voltage:
|
400/480V
|
600/690V
|
| Frequency:
|
47-63 Hz
|
47-63 Hz
|
| Operational AC Input Voltage:
|
187-528V
|
269-759V
|
| Input Current (Max. Cont. RMS):
|
355
|
521
|
843
|
843
|
| Input kVA at Max. Cont. RMS Amps:
|
246/295
|
361/433
|
584/700
|
876/1007
|
| Output Ratings
|
| DC Bus Amps
|
| Continuous:
|
300
|
500
|
800
|
800
|
| 3 Sec. Every Minute:
|
450
|
750
|
1200
|
1200
|
| Max. Continuous DC Bus Amps without Overload:
|
400
|
600
|
1000
|
1000
|
| Power Dissipation - Watts at Max. Continuous Amps:
|
1200
|
1600
|
2700
|
2800
|
| DC Bus Voltage:
|
AC Input
|
Nominal
|
Maximum
|
| 400V
|
540V
|
750V
|
| 480V
|
650V
|
750V
|
| 600V
|
810V
|
1080V
|
| 690V
|
930V
|
1080V
|
|
|
| Specifications Common to All SCR Bus Supply Units
|
| Voltage Tolerance:
|
10% of minimum, +10% of maximum
|
| Frequency Tolerance:
|
47-63 Hz
|
| Displacement Power Factor:
|
0.92 lagging (entire load range)
|
| Efficiency:
|
99.5% at rated amps, nominal line volts.
|
| Line Transients:
|
up to 6000 volts peak per IEEE C62.41-1991
|
| Maximum Short Circuit Current Rating:
|
85 kA
|
| Cooling:
|
Forced ventilation cooled by tangential blower below heat sink.
|
| Blower Power Consumption:
|
200 VA
|
| Cooling Air:
|
600 m3/h
|
| Control Input Specifications
|
| Enable Contactor Coil:
|
Single-Phase 115V AC, 30 VA (pickup), 4.5 VA (hold)
|
| Blower Current Consumption:
|
Single-Phase 115V AC, 50/60 Hz, 1A
|
| Control Output Specifications
|
| Heat Sink Temperature Sensor:
|
Sensor trips if heat sink temperature exceeds maximum temperature.
|
| NC Contact Output Rating (max.):
|
Resistive Rating: 15A at 125V AC, 10A at 250V AC, 7A at 24V DC
|
| Inductive Rating: 10A at 125V AC, 6A at 250V AC
|
| Fuse Trip Indication Micro Switches F1-F11, NC Contact Output Rating (max.):
|
Resistive Rating: 10A at 30 to 250V AC, 8A at 30V DC
|
| Inductive Rating: L/R=25ms, 10A at 30 to 250V AC
|
| Enable Contactor K1, NC Contact Output Rating (max.):
|
Resistive Rating: 10A at 24 to 230V AC, 3A at 30V DC
|
| Inductive Rating: L2.2A at 24 to 230V AC
|
| Permitted Max. Capacitance for Connection to the DC Bus Supply:
|
This is the total DC Bus capacitance sum of the permitted drives to connect.
|
| Approvals and Standards Compliance
|
| The Bus Supply is designed to meet the following specifications:
|
NFPA 70 - US National Electrical Code NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems. NEMA 250 - Enclosures for Electrical Equipment IEC 146 - International Electrical Code.
|
|
UL and cUL Listed to UL508C and CAN/CSA-C22.2
|
|
Marked for all applicable European Directives EMC Directive (89/336/EEC)
|
Emissions: EN 61800-3 Adjustable Speed electrical power drives systems Part 3
|
Immunity: EN 61800-3 Second Environment, Restricted Distribution
|
Low Voltage Directive (73/23/EEC) EN 50178 Electronic Equipment for use in Power Installations
|
| Environmental Specifications
|
| Altitude:
|
1000 m (3300 ft.) max. without derating. Above 1000 m the derating for the output current is 1% per 100 m (330 ft).
|
Ambient Operating Temperature without Derating: Open Type/IP00:
|
0 to 40°C (32 to 104°F) Above 40°C up to 50°C (122°F) maximum temperature the output Amps must be derated by 1% per °C (1.8% per °F).
|
| Storage Temperature (all):
|
40 to 70°C (40 to 158°F)
|
| Relative Humidity:
|
5 to 95% non-condensing
|
| Shock:
|
15G peak for 11ms duration (±1.0 ms)
|
| Vibration:
|
0.152 mm (0.006 in.) displacement, 1G peak
|
|
|
| Unit Type
|
A
|
B
|
C
|
D
|
Weight
|
| 400A
|
535 (21.1)
|
404 (15.9)
|
580 (22.8)
|
276 (10.9)
|
30 kg (66 lb)
|
| 600A
|
740 (29.1)
|
490 (19.3)
|
785 (30.9)
|
276 (10.9)
|
43 kg (95 lb)
|
| 1000A
|
740 (29.1)
|
490 (19.3)
|
785 (30.9)
|
276 (10.9)
|
67 kg (147 lb)
|
|
|
| Dimensions are in millimeters and (inches)
|