IP30/NEMA 1/UL Type 1 Conversion Kit
Description Drive Frame Cat. No.
Converts IP20 drive to IP30, NEMA/UL Type 1 enclosure. Includes conduit box, mounting screws and plastic top panel. B 22-JBAB
C 22-JBAC
Converts IP20 drive to IP30, NEMA/UL Type 1 enclosure. Includes communication option conduit box, mounting screws and plastic top panel. B 22-JBCB
C 22-JBCC

Human Interface Module Option Kits and Accessories
Description Cat. No.
Remote (Panel Mount) LCD Display, Digital Speed Control, CopyCat Capable. IP66 (NEMA/UL Type 4X/12) Indoor Use Only. Includes 2.0 meter cable. 22-HIM-C2S ¬ 
Remote Handheld, LCD Display, Full Numeric Keypad, Digital Speed Control, CopyCat Capable. IP30 (NEMA/UL Type 1). Includes 1.0 meter cable. Panel mount with optional Bezel Kit. 22-HIM-A3
Remote Handheld, Wireless Interface Module with Bluetooth® Technology. IP30 (NEMA/UL Type 1). Panel Mount with optional Bezel Kit. 22-WIM-N1
Remote (Panel Mount), Wireless Interface Module with Bluetooth Technology. IP66 (NEMA/UL Type 4X/12) Indoor Use Only. 22-WIM-N4S
Bezel Kit. Panel Mount for LCD Display, Remote Handheld Unit. IP30 (NEMA/UL Type 1). Includes a 22-RJ45CBL-C20 cable. 22-HIM-B1
DSI HIM Cable (DSI HIM to RJ45 cable)  
1.0 Meter (3.3 Feet)
22-HIM-H10
2.9 Meter (9.51 Feet)
22-HIM-H30
  
¬ The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement.

Spare Parts
Description Cat. No.
Fan Replacement Kit - Frame B, 1 Fan SK-U1-FAN1-B1
Fan Replacement Kit - Frame B, 2 Fans SK-U1-FAN2-B1
Fan Replacement Kit - Frame C, 1 Fan SK-U1-FAN1-C1
Fan Replacement Kit - Frame C, 1 Fan, 15 Hp SK-U1-FAN1-C2
Frame B Cover with Power Terminal Guard SK-U1-DCVR3-B1
Frame C Cover with Power Terminal Guard SK-U1-DCVR3-C1
Encoder Terminal Cover (All Frames) SK-U1-DCVR4-EN
  

Terminators
Description ª  Cat. No.
for use with 3.7 kW (5 Hp) & below drives 1204-TFA1
for use with 1.5 kW (2 Hp) & up drives 1204-TFB2
  
ª Refer to Appendix A of publication DRIVES-IN001 for selection information.

Reflected Wave Reduction Modules w/Common Mode Choke
Description ª  Cat. No.
17A with Common Mode Choke 1204-RWC-17-A
  
ª Refer to Appendix A of publication DRIVES-IN001 for selection information.

Reflected Wave Reduction Modules
Voltage Drive Cat. No. ND Hp Cat. No.
480V AC 22D-D6P0 3 1321-RWR8-DP
22D-D010 5 1321-RWR12-DP
22D-D012 7.5 1321-RWR18-DP
22D-D017 10 1321-RWR18-DP
22D-D024 15 1321-RWR25-DP
600V AC 22D-E6P6 5 1321-RWR8-EP
22D-E9P9 7.5 1321-RWR12-EP
22D-D012 10 1321-RWR18-EP
22D-D019 15 1321-RWR25-EP
  

Communication Option Kits
Description Cat. No.
Serial Converter Module (RS485 to RS232)
Provides serial communication via DF1 protocol for use with DriveExplorer and DriveExecutive™ software. Includes DSI to RS232 serial converter, 1203-SFC serial cable, 22-RJ45CBL-C20 cable, and DriveExplorer Lite CD.
22-SCM-232
Serial Cable
2.0 meter with a locking low profile connector. Connects the serial converter to a 9-pin sub-miniature D female computer connector.
1203-SFC
Serial Null Modem Adapter
Use when connecting the serial converter to DriveExplorer on a handheld PC.
1203-SNM
Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables 1203-USB
DSI Cable
2.0 meter RJ45 to RJ45 cable, male to male connectors.
22-RJ45CBL-C20
Splitter Cable
RJ45 one to two port splitter cable.
AK-U0-RJ45-SC1
Terminating Resistors
120 Ohm resistor embedded in an RJ45 connector (2 pieces).
AK-U0-RJ45-TR1
Terminal Block
RJ45 two position terminal block (6 pieces) with two 120 Ohm terminating resistors (loose).
AK-U0-RJ45-TB2P
DSI External Communications Kit
External mounting kit for 22-COMM Communication Adapters.
22-XCOMM-DC-BASE
External Communications Kit Power Supply
Optional 100…240V AC Power Supply for External DSI Communications Kit.
20-XCOMM-AC-PS1
ControlNet™ Communication Adapter §  22-COMM-C
DeviceNet™ Communication Adapter §  22-COMM-D
EtherNet/IP™ Communication Adapter §  22-COMM-E
LonWorks® Communication Adapter §  22-COMM-L
PROFIBUS™ DP Communication Adapter §  22-COMM-P
Compact I/O Module (3 Channel) 1769-SM2
Communication Adapter Cover
Houses the Communication Adapter for B & C Frame drives. Note: Cover adds 25 mm (0.98 in.) to the overall depth of the drive.
 
Frame B Drive
22D-CCB § 
Frame C Drive
22D-CCC § 
  
§ If NEMA 1/IP30 is required, a 22-JBCB (Frame B drives) or 22-JBCC (Frame C drives) must also be ordered.
§ Requires a Communication Adapter Cover when used with Frame B and C drives (Ordered Separately).

PC Programming Software
Description
DriveTools™ SP Software ª 
DriveExplorer™ Software (Lite/Full) ª v 
 
ª Set-up wizards are available for use with DriveTools SP and DriveExplorer (Lite/Full) only.
v DriveExplorer Lite is available for free download at: http://www.ab.com/drives/driveexplorer/free_download.html.

Other Options
Description Cat. No.
DriveGuard Safe Torque-Off Board (Series B) 20A-DG01
  

Dynamic Brake Resistors
Drive Ratings Minimum Resistance Cat. No.¬ 
Input Voltage kW Hp W
240V 50/60 Hz
3-Phase
0.4 0.5 48 AK-R2-091P500
0.75 1.0 48 AK-R2-091P500
1.5 2.0 48 AK-R2-091P500
2.2 3.0 32 AK-R2-047P500
3.7 5.0 19 AK-R2-047P500
5.5 7.5 13 AK-R2-030P1K2
7.5 10 10 AK-R2-030P1K2
480V 50/60 Hz
3-Phase
0.4 0.5 97 AK-R2-360P500
0.75 1.0 97 AK-R2-360P500
1.5 2.0 97 AK-R2-360P500
2.2 3.0 97 AK-R2-120P1K2
4.0 5.0 77 AK-R2-120P1K2
5.5 7.5 55 AK-R2-120P1K2
7.5 10 39 AK-R2-120P1K2
11 15 24 AK-R2-120P1K2 T 
600V 50/60 Hz
3-Phase
0.75 1.0 120 AK-R2-360P500
1.5 2.0 120 AK-R2-360P500
2.2 3.0 82 AK-R2-120P1K2
4.0 5.0 82 AK-R2-120P1K2
5.5 7.5 51 AK-R2-120P1K2
7.5 10 51 AK-R2-120P1K2
11 15 51 AK-R2-120P1K2 T 
  
¬ Resistors listed in this table are rated 5% duty cycle.
T Requires two resistors wired in parallel.

Input Line Reactors - 240V, 50/60 Hz, Three-Phase, 3% Impedance
kW Hp Fundamental Amps Maximum Continuous Amps Inductance Watts Loss Cat. No.¬ 
A A mh W
0.4 0.5 4.0 6.0 6.5 20 1321-3R4-B
0.75 1.0 8.0 12 3.0 29 1321-3R4-B
1.5 2.0 8.0 12 1.5 19.5 1321-3R8-A
2.2 3.0 12 18 1.25 26 1321-3R12-A
3.7 5.0 18 27 0.8 36 1321-3R18-A
5.5 7.5 25 37.5 0.5 48 1321-3R25-A
7.5 10 35 52.5 0.4 49 1321-3R35-A
  
¬ Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-TD001….

Input Line Reactors - 480V, 50/60 Hz, Three-Phase, 3% Impedance
kW Hp Fundamental Amps Maximum Continuous Amps Inductance Watts Loss Cat. No.¬ 
A A mh W
0.4 0.5 2.0 3.0 20 11.3 1321-3R2-B
0.75 1.0 4.0 6.0 9.0 20 1321-3R4-C
1.5 2.0 4.0 6.0 6.5 20 1321-3R4-B
2.2 3.0 8.0 12 5.0 25.3 1321-3R8-C
4.0 5.0 12 18 2.5 31 1321-3R8-B
5.5 7.5 12 18 2.5 31 1321-3R12-B
7.5 10 18 27 1.5 43 1321-3R18-B
11 15 25 37.5 1.2 52 1321-3R25-B
  
¬ Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-TD001….

Input Line Reactors - 600V, 50/60 Hz, Three-Phase, 3% Impedance
kW Hp Fundamental Amps Maximum Continuous Amps Inductance Watts Loss Cat. No.¬ 
A A mh W
0.75 1.0 2.0 3.0 20 11.3 1321-3R2-B
1.5 2.0 4.0 6.0 6.5 20 1321-3R4-C
2.2 3.0 4.0 6.0 6.5 20 1321-3R4-B
4.0 5.0 8.0 12 5.0 25.3 1321-3R8-C
5.5 7.5 12 18 2.5 31 1321-3R12-B
7.5 10 12 18 2.5 31 1321-3R12-B
11 15 18 27 1.5 43 1321-3R18-B
  
¬ Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-TD001….

EMC Filters
Drive Ratings S Type Filter L Type Filter
Input Voltage kW Hp Cat. No. ¬  Cat. No. § 
240V 50/60 Hz
3-Phase
0.4 0.5 22-RF021-BS ‡  22-RF021-BL
0.75 1.0 22-RF021-BS ‡  22-RF021-BL
1.5 2.0 22-RF021-BS ‡  22-RF021-BL
2.2 3.0 22-RF021-BS ‡  22-RF021-BL
3.7 5.0 22-RF021-BS ‡  22-RF021-BL
5.5 7.5 22-RF034-CS 22-RF034-CL
7.5 10 22-RF034-CS 22-RF034-CL
480V 50/60 Hz
3-Phase
0.4 0.5 22-RF012-BS 22-RF012-BL
0.75 1.0 22-RF012-BS 22-RF012-BL
1.5 2.0 22-RF012-BS 22-RF012-BL
2.2 3.0 22-RF012-BS 22-RF012-BL
4.0 5.0 22-RF012-BS 22-RF012-BL
5.5 7.5 22-RF018-CS 22-RF018-CL
7.5 10 22-RF018-CS 22-RF018-CL
11 15 22-RF026-CS 22-RF026-CL
600V 50/60 Hz
3-Phase
0.75 1.0 22-RF8P0-BL
1.5 2.0 22-RF8P0-BL
2.2 3.0 22-RF8P0-BL
4.0 5.0 22-RF8P0-BL
5.5 7.5 22-RF015-CL
7.5 10 22-RF015-CL
11 15 22-RF024-CL
  
¬ This filter is suitable for use with a cable length of up to 10 meters for Class A and 1 meter for Class B environments.
‡ Filter must be Series B or later.
§ This filter is suitable for use with a cable length of up to 100 meters for Class A and 5 meters for Class B environments.