Catalogs > Drives Catalog > PowerFlex 4
PowerFlex 4
| Introduction | Conformity to Standards | Drive Description | Catalog Number Explanation | Product Selection | User Installed Options |
| IP30/NEMA 1/UL Type 1 Conversion Kit | ||
| Description | Drive Frame | Cat. No. |
| Converts IP20 drive to IP30, NEMA/UL Type 1 enclosure. Includes conduit box, mounting screws and plastic top panel. | A | 22-JBAA |
| B | 22-JBAB | |
| Human Interface Module Option Kits and Accessories | |
| Description | Cat. No. |
| Remote (Panel Mount) LCD Display, Digital Speed Control, CopyCat Capable. IP66 (NEMA/UL Type 4X/12) Indoor Use Only. Includes 2.0 meter cable. | 22-HIM-C2S § |
| Remote Handheld, LCD Display, Full Numeric Keypad, Digital Speed Control, CopyCat Capable. IP30 (NEMA/UL Type 1). Includes 1.0 meter cable. Panel mount with optional Bezel Kit. | 22-HIM-A3 |
| Remote Handheld, Wireless Interface Module with Bluetooth® Technology. IP30 (NEMA/UL Type 1). Panel Mount with optional Bezel Kit. | 22-WIM-N1 |
| Remote (Panel Mount), Wireless Interface Module with Bluetooth Technology. IP66 (NEMA/UL Type 4X/12) Indoor Use Only. | 22-WIM-N4S |
| Bezel Kit. Panel Mount for LCD Display, Remote Handheld Unit. IP30 (NEMA/UL Type 1). Includes a 22-RJ45CBL-C20 cable. | 22-HIM-B1 |
| DSI HIM Cable (DSI HIM to RJ45 cable) | |
| 22-HIM-H10 | |
| 22-HIM-H30 | |
| § The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement. | |
| Spare Parts | |
| Description | Cat. No. |
| Fan Replacement Kit - Frame A | SK-U1-FAN1-A1 |
| Fan Replacement Kit - Frame B, 1 Fan | SK-U1-FAN1-B1 |
| Fan Replacement Kit - Frame B, 2 Fans | SK-U1-FAN2-B1 |
| Frame A Cover with Power Terminal Guard | SK-U1-ACVR1-A1 |
| Frame B Cover with Power Terminal Guard | SK-U1-ACVR1-B1 |
| Communication Option Kits | |
| Description | Cat. No. |
| Serial Converter Module (RS485 to RS232) Provides serial communication via DF1 protocol for use with DriveExplorer and DriveExecutive™ software. Includes DSI to RS232 serial converter, 1203-SFC serial cable, 22-RJ45CBL-C20 cable, and DriveExplorer Lite CD. |
22-SCM-232 |
| Serial Cable 2.0 meter with a locking low profile connector. Connects the serial converter to a 9-pin sub-miniature D female computer connector. |
1203-SFC |
| Serial Null Modem Adapter Use when connecting the serial converter to DriveExplorer on a handheld PC. |
1203-SNM |
| Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables | 1203-USB |
| DSI Cable 2.0 meter RJ45 to RJ45 cable, male to male connectors. |
22-RJ45CBL-C20 |
| Splitter Cable RJ45 one to two port splitter cable. |
AK-U0-RJ45-SC1 |
| Terminating Resistors 120 Ohm resistor embedded in an RJ45 connector (2 pieces). |
AK-U0-RJ45-TR1 |
| Terminal Block RJ45 two position terminal block (6 pieces) with two 120 Ohm terminating resistors (loose). |
AK-U0-RJ45-TB2P |
| DSI External Communications Kit External mounting kit for 22-COMM Communication Adapters. |
22-XCOMM-DC-BASE |
| External Communications Kit Power Supply Optional 100…240V AC Power Supply for External DSI Communications Kit. |
20-XCOMM-AC-PS1 |
| BACnet® MS/TP RS485 Communication Adapter | 22-COMM-B |
| ControlNet™ Communication Adapter | 22-COMM-C |
| DeviceNet™ Communication Adapter | 22-COMM-D |
| EtherNet/IP™ Communication Adapter | 22-COMM-E |
| LonWorks® Communication Adapter | 22-COMM-L |
| PROFIBUS™ DP Communication Adapter | 22-COMM-P |
| Compact I/O Module (3 Channel) | 1769-SM2 |
| PowerFlex 4 drives require External DSI Communication Kits. Communication Adapters cannot be drive mounted. | |
| Terminators | |
| Description ª | Cat. No. |
| for use with 3.7 kW (5 Hp) & below drives | 1204-TFA1 |
| for use with 1.5 kW (2 Hp) & up drives | 1204-TFB2 |
| ª Refer to Appendix A of publication DRIVES-IN001 for selection information. | |
| PC Programming Software |
| Description |
| DriveTools™ SP Software ª |
| DriveExplorer™ Software (Lite/Full) ª v |
| ª Set-up wizards are available for use with DriveTools SP and DriveExplorer (Lite/Full) only. |
| v DriveExplorer Lite is available for free download at: http://www.ab.com/drives/driveexplorer/free_download.html. |
| Dynamic Brake Resistors | ||||
| Drive Ratings | Minimum Resistance | Cat. No. z | ||
| Input Voltage | kW | Hp | W | |
| 120V 50/60 Hz 1-Phase |
0.2 | 0.25 | 48 | AK-R2-091P500 |
| 0.4 | 0.5 | 48 | AK-R2-091P500 | |
| 0.75 | 1.0 | 48 | AK-R2-091P500 | |
| 240V 50/60 Hz 1-Phase |
0.2 | 0.25 | 48 | AK-R2-091P500 |
| 0.4 | 0.5 | 48 | AK-R2-091P500 | |
| 0.75 | 1.0 | 48 | AK-R2-091P500 | |
| 1.5 | 2.0 | 48 | AK-R2-091P500 | |
| 240V 50/60 Hz 3-Phase |
0.2 | 0.25 | 48 | AK-R2-091P500 |
| 0.4 | 0.5 | 48 | AK-R2-091P500 | |
| 0.75 | 1.0 | 48 | AK-R2-091P500 | |
| 1.5 | 2.0 | 48 | AK-R2-091P500 | |
| 2.2 | 3.0 | 32 | AK-R2-047P500 | |
| 3.7 | 5.0 | 19 | AK-R2-047P500 | |
| 480V 50/60 Hz 3-Phase |
0.4 | 0.5 | 97 | AK-R2-360P500 |
| 0.75 | 1.0 | 97 | AK-R2-360P500 | |
| 1.5 | 2.0 | 97 | AK-R2-360P500 | |
| 2.2 | 3.0 | 97 | AK-R2-120P1K2 | |
| 3.7 | 5.0 | 77 | AK-R2-120P1K2 | |
| z Resistors listed in this table are rated 5% duty cycle. | ||||
| Input Line Reactors - 240V, 50/60 Hz, Three-Phase, 3% Impedance | ||||||
| kW | Hp | Fundamental Amps | Maximum Continuous Amps | Inductance | Watts Loss | Cat. No.¬ |
| A | A | mh | W | |||
| 0.2 | 0.25 | 2.0 | 3.0 | 12.0 | 7.5 | 1321-3R2-A |
| 0.4 | 0.5 | 4.0 | 6.0 | 12.0 | 21 | 1321-3R4-B |
| 0.75 | 1.0 | 8.0 | 12 | 3.0 | 29 | 1321-3R8-B |
| 1.5 | 2.0 | 8.0 | 12 | 1.5 | 19.5 | 1321-3R8-A |
| 2.2 | 3.0 | 12 | 18 | 1.25 | 26 | 1321-3R12-A |
| 3.7 | 5.0 | 18 | 27 | 0.8 | 36 | 1321-3R18-A |
| ¬ Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-TD001…. | ||||||
| Input Line Reactors - 480V, 50/60 Hz, Three-Phase, 3% Impedance | ||||||
| kW | Hp | Fundamental Amps | Maximum Continuous Amps | Inductance | Watts Loss | Cat. No.¬ |
| A | A | mh | W | |||
| 0.4 | 0.5 | 2.0 | 3.0 | 20.0 | 11.3 | 1321-3R2-B |
| 0.75 | 1.0 | 4.0 | 6.0 | 9.0 | 20 | 1321-3R4-C |
| 1.5 | 2.0 | 4.0 | 6.0 | 6.5 | 20 | 1321-3R4-B |
| 2.2 | 3.0 | 8.0 | 12 | 5.0 | 25.3 | 1321-3R8-C |
| 3.7 | 5.0 | 8.0 | 12 | 3.0 | 29 | 1321-3R8-B |
| ¬ Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-TD001…. | ||||||
| Reflected Wave Reduction Modules w/Common Mode Choke | |
| Description ª | Cat. No. |
| 17A with Common Mode Choke | 1204-RWC-17-A |
| ª Refer to Appendix A of publication DRIVES-IN001 for selection information. | |
| Reflected Wave Reduction Modules | |||
| Voltage | Drive Cat. No. | ND Hp | Cat. No. |
| 480V AC | 22A-D8P7 | 5.0 | 1321-RWR8-DP |
| EMC Filters | ||||
| Drive Ratings | S Type Filter | L Type Filter | ||
| Input Voltage | kW | Hp | Cat. No. ¬ | Cat. No. |
| 120V 50/60 Hz 1-Phase |
0.2 | 0.25 | | 22-RF010-AL |
| 0.4 | 0.5 | | 22-RF010-AL | |
| 0.75 | 1.0 | | 22-RF018-BL | |
| 1.1 | 1.5 | | 22-RF025-CL § | |
| 240V 50/60 Hz 1-Phase |
0.2 | 0.25 | T | 22-RF010-AL |
| 0.4 | 0.5 | T | 22-RF010-AL | |
| 0.75 | 1.0 | T | 22-RF010-AL | |
| 1.5 | 2.0 | T | 22-RF018-BL | |
| 240V 50/60 Hz 1-Phase NO BRAKE |
0.2 | 0.25 | T | 22-RF010-AL |
| 0.4 | 0.5 | T | 22-RF010-AL | |
| 0.75 | 1.0 | T | 22-RF010-AL | |
| 1.5 | 2.0 | T | 22-RF018-BL | |
| 2.2 | 3.0 | T | 22-RF025-CL § | |
| 240V 50/60 Hz 3-Phase |
0.2 | 0.25 | 22-RF9P5-AS | 22-RF9P5-AL |
| 0.4 | 0.5 | 22-RF9P5-AS | 22-RF9P5-AL | |
| 0.75 | 1.0 | 22-RF9P5-AS | 22-RF9P5-AL | |
| 1.5 | 2.0 | 22-RF9P5-AS | 22-RF9P5-AL | |
| 2.2 | 3.0 | 22-RF021-BS | 22-RF021-BL | |
| 3.7 | 5.0 | 22-RF021-BS | 22-RF021-BL | |
| 480V 50/60 Hz 3-Phase |
0.4 | 0.5 | 22-RF5P7-AS | 22-RF5P7-AL |
| 0.75 | 1.0 | 22-RF5P7-AS | 22-RF5P7-AL | |
| 1.5 | 2.0 | 22-RF5P7-AS | 22-RF5P7-AL | |
| 2.2 | 3.0 | 22-RF012-BS | 22-RF012-BL | |
| 3.7 | 5.0 | 22-RF012-BS | 22-RF012-BL | |
| ¬ This filter is suitable for use with a cable length of up to 10 meters for Class A and 1 meter for Class B environments. | ||||
| T Drives are available in these ratings with internal S Type filters. | ||||
| This filter is suitable for use with a cable length of up to 100 meters for Class A and 5 meters for Class B environments. | ||||
| § The piggyback mounting option cannot be used with Frame B PowerFlex 4 drives and Frame C EMC Line Filters. | ||||