PowerFlex 755

Click to enlarge - pf755


Designed for ease of integration, application flexibility and performance the PowerFlex 755 AC drive provides improved functionality across many manufacturing systems. The PowerFlex 755 AC drive is designed to maximize user’s investment and help improve productivity. Ideal for applications that require safety, high motor control performance, and application flexibility, the PowerFlex 755 is highly functional and cost effective solution.

The PowerFlex 755 AC drive can be configured with drive instructions embedded in Allen-Bradley Logix Programmable Automation Controllers (PAC).


at a glance …
Ratings
    380…480V:
    600V:
    690V:

0.75…1400 kW / 1.0…2000 Hp / 2.1…2330 A
0.5…1500 Hp / 1.7…1530
5.5…1500 kW / 12…1485 A
Motor Control
  • V/Hz Control

  • Sensorless Vector Control

  • Vector Control with FORCE Technology
         (with and without encoder)

  • Permanent Magnet Motor Control

  •      Surface Mount:
            Frames 2…7 (with and without encoder)
            Frames 8…10 (with encoder)
         Internal Mount:
            Frames 8…10 (with encoder)
    Communications Embedded EtherNet/IP port standard (see Communication Option Kits)
    User Interface HIM (see Human Interface Modules for options)
    Enclosures
  • IP00/IP20, NEMA/UL Type Open

  • Flange Mount

  • IP54/NEMA/UL Type 12

  • IP20, NEMA/UL Type 1 (MCC Style Cabinet)

  • IP54, NEMA Type 12 (MCC Style Cabinet)
  • Safety
  • Safe Torque-Off PLe/SIL3 Cat. 3

  • Safe Speed Monitor PLe/SIL3 Cat. 4
  • Additional Features
  • DeviceLogix

  • Configure and control with embedded instruction sets in RSLogix 5000 (v19 or higher)

  • Predictive Diagnostics

  • Five option slots for I/O, feedback, safety, auxiliary control power, communications

  • Accurate positioning with PCAM, Indexer, Electronic Gearing, and speed/position profiling

  • Incremental and Absolute feedback supported

  • TorqProve for lifting applications

  • Pump Jack and Pump Off for oil well applications

  • Pjump and Traverse for Fibers application

  • Conformal Coating

  • DC Link Choke

  • AC line fuses included with Frame 8…10 drives

  • Roll-out design for Frame 8…10 drives
  • Certifications
  • ABS (Frames 2…8, 400/480V AC)

  • C-Tick

  • c-UL-us

  • CE

  • EPRI/SEMI F47

  • GOST-R (Frames 2…8, 400/480V AC)

  • Lloyd's Register (Frames 2…8, 400/480V AC)

  • RINA (Frames 2…8, 400/480V AC)

  • RoHS compliant materials

  • TÜV FS ISO/EN13849-1 (EN954-1) with Safe Torque-Off option
  • Additional Information PowerFlex 750-Series Product Profile, publication 750-PP001
    PowerFlex 750-Series Technical Data, publication 750-TD001
     

    To interpret the meaning of a catalog number, match the values of the catalog number code in positions a, b, c, etc. with the tables labeled a, b, c, etc. below.

    20G   1   A   N   D   248   A   A   0   N   N   N   N   N   -  LD  -  P3  -  P11…
    a   b   c   d   e   f1…f4   g   h                           Cabinet Options (21G)

    a
    Drive
    Code Type
    20G PowerFlex 755
    21G PowerFlex 755 Drive with Options

    b
    Future Use

    c
    Input Type ⋆ 
    Code Description Frames
    1 AC & DC Input w/Precharge 1…5, 8…10
    4 DC Input w/Precharge 5…10
    A AC Input w/Precharge, no DC Terminals 6…8
    ⋆ Frames 1…4, Code 1 provides the functionality of DC input with precharge. Frames 5 & larger, Code 4 is required for DC input with precharge. The DC Bus Bar kit (20-750-DCBB1-Fx) is available for Frames 6…7 AC input drives requiring DC bus terminals.

    d
    Enclosure
    Code Description Frames
    R IP20, NEMA/UL Type Open, Frame 1 1
    F §  Flange (NEMA/UL Type 4X/12 back) 2…5
    G IP54, NEMA/UL Type 12 2…7
    N ‡  IP20/IP00, NEMA/UL Type Open 2…7
    B IP20, NEMA/UL Type 1,
    600 mm (23.6 in.) Deep,
    Standard Cabinet Color (RAL 7032)
    8…10
    J IP54, NEMA Type 12,
    800 mm (31.5 in.) Deep,
    Standard Cabinet Color (RAL 7032)
    8…10
    K ∆  IP54, NEMA Type 12,
    2500 MCC Style Cabinet & Options
    w/MCC Power Bus, 800 mm (31.5 in.) Deep,
    Standard Cabinet Color (RAL 7032)
    8…10
    L IP20, NEMA/UL Type 1,
    800 mm (31.5 in.) Deep,
    Standard Cabinet Color (RAL 7032)
    8…10
    P ∆  IP20, NEMA/UL Type 1,
    2500 MCC Style Cabinet & Options
    w/MCC Power Bus, 800 mm (31.5 in.) Deep,
    Standard Cabinet Color (RAL 7032)
    8…10
    W ∆  IP20, NEMA/UL Type 1,
    2500 MCC Style Cabinet & Options
    w/MCC Power Bus, 800 mm (31.5 in.) Deep,
    CenterLine 2100 Gray (ASA49)
    8…10
    Y ∆  IP54, NEMA Type 12,
    2500 MCC Style Cabinet & Options
    w/MCC Power Bus, 800 mm (31.5 in.) Deep,
    CenterLine 2100 Gray (ASA49)
    8…10
    T IP00, UL Open Type without Control POD 8…10
    § For Frames 6…7 a User Installed Flange Kit is available to convert a Code N drive that provides a NEMA/UL Type 4X/12 back.
    ‡ Frames 2…5 are IP20, Frames 6…7 are IP00.
    ∆ Available as a drive with options (21G).

    e
    Voltage Rating
    Code Voltage
    C 400V AC/540V DC
    D 480V AC/650V DC
    E 600V AC/725V DC
    F 690V AC/932V DC (not UL listed)

    f1
    ND Rating
    400V, 50 Hz Input
    Code Amps kW Frame
    Enclosure Code
    B, J, L, T F G N K, P, W, Y R
    2P1 2.1 0.75 2 2 2 1
    3P5 3.5 1.5
    5P0 5.0 2.2
    8P7 8.7 4
    011 11.5 5.5
    015 15.4 7.5
    022 22 11
    030 30 15 3 3 3
    037 37 18.5
    043 43 22
    060 60 30 4 4 4
    072 72 37 5
    085 85 45 5 5
    104 104 55 6
    140 140 75 §  6
    170 170 90
    205 205 110
    260 260 132 7
    302 302 160 7
    367 367 200
    456 456 250
    460 460 250 8 8 ∆ 
    540 540 315
    567 567 315
    650 650 355
    750 750 400
    770 770 400
    910 910 500 9 9 ∆ 
    1K0 1040 560
    1K1 1090 630
    1K2 1175 710
    1K4 1465 800
    1K5 1480 850
    1K6 1590 900 10 10 ∆ 
    2K1 2150 1250
    § For Frames 6…7 a User Installed Flange Kit is available to convert a Code N drive that provides a NEMA/UL Type 4X/12 back.
    ∆ Available as a drive with options (21G).

    f2
    ND Rating
    480V, 60 Hz Input
    Code Amps Hp Frame
    Enclosure Code
    B, J, L, T F G N K, P, W, Y R
    2P1 2.1 1 2 2 2 1
    3P4 3.4 2
    5P0 5.0 3
    8P0 8.0 5
    011 11 7.5
    014 14 10
    022 22 15
    027 27 20 3 3 3
    034 34 25
    040 40 30
    052 52 40 4 4 4
    065 65 50 5
    077 77 60 5 5
    096 96 75 6
    125 125 100 §  6
    156 156 125
    186 186 150
    248 248 200 7
    302 302 250 7
    361 361 300
    415 415 350
    430 430 350 8 8 ∆ 
    485 485 400
    545 545 450
    617 617 500
    710 710 600
    740 740 650
    800 800 700 9 9 ∆ 
    960 960 800
    1K0 1045 900
    1K2 1135 1000
    1K3 1365 1100
    1K4 1420 1250
    1K5 1525 1350 10 10 ∆ 
    2K0 2070 1750
    § For Frames 6…7 a User Installed Flange Kit is available to convert a Code N drive that provides a NEMA/UL Type 4X/12 back.
    ∆ Available as a drive with options (21G).

    f3
    ND Rating
    600V, 60 Hz Input
    Code Amps Hp Frame
    Enclosure Code
    B, J, L, T F G N K, P, W, Y R
    1P7 1.7 1 3 3 3
    2P7 2.7 2
    3P9 3.9 3
    6P1 6.1 5
    9 9 7.5
    11 11 10
    17 17 15
    22 22 20
    27 27 25 4 4 4
    32 32 30
    41 41 40 5 5 5
    52 52 50
    63 63 60 6 6
    77 77 75
    99 99 100
    125 125 125
    144 144 150
    192 192 200 7 7
    242 242 250
    289 289 300
    295 295 300 8 8 ∆ 
    355 355 350
    395 395 400
    435 435 450
    460 460 500
    510 510 500
    595 595 600 9 9 ∆ 
    630 630 700
    760 760 800
    825 825 900
    900 900 950
    980 980 1000
    1K1 1110 1100 10 10 ∆ 
    1K4 1430 1400
    ∆ Available as a drive with options (21G).

    f4
    ND Rating
    690V, 60 Hz Input (not UL listed)
    Code Amps kW Frame
    Enclosure Code
    B, J, L, T F G N K, P, W, Y R
    12 12 7.5 6 6
    15 15 11
    20 20 15
    23 23 18.5
    30 30 22
    34 34 30
    46 46 37
    50 50 45
    61 61 55
    82 82 75
    98 98 90
    119 119 110
    142 142 132
    171 171 160 7 7
    212 212 200
    263 263 250
    265 265 250 8 8 ∆ 
    330 330 315
    370 370 355
    415 415 400
    460 460 450
    500 500 500
    590 590 560 9 9 ∆ 
    650 650 630
    710 710 710
    765 765 750
    795 795 800
    960 960 900
    1K0 1040 1000 10 10 ∆ 
    1K4 1400 1400
    ∆ Available as a drive with options (21G).

    g
    Filtering and CM Cap Configuration ♦ 
    Code Filtering Default CM Cap Connection
    A Yes Jumper Removed
    J Yes Jumper Installed
    ♦ 480V drives must select code "A." Jumpers are included for field reconfiguration as desired.

    h
    Dynamic Braking & 
    Code Internal Resistor ♠  Internal Transistor ▶ 
    A No Yes
    N No No
    ♠ Frames 1…2 only.
    ▶ Standard on Frames 1…5, optional on 6…7.
    & Not available on Frames 8…10, specify Code "N."

    PowerFlex 755 w/Options (21G) - Required Selections
    Code Option Type Frames
    LD Light Duty System Overload Duty Cycle ⋆  8…10
    ND Normal Duty
    HD Heavy Duty
    P3 Input Thermal Magnetic Circuit Breaker Power Disconnect or Wiring Only Bay ⋆  8…10
    P5 Input Non-Fused Molded Case Disconnect Switch
    P14 Wiring Only Bay
    ⋆ Only one option of this type may be selected.

    PowerFlex 755 w/Options (21G) - Additional Selections
    Code Option Type Frames
    P11 Input Contactor Contactors ⋆  §  8
    P12 Output Contactor
    L1 3% Input Reactor Reactors ⋆  8…10
    L2 3% Output Reactor
    L3 5% Input Reactor 8
    L4 5% Output Reactor
    P20 1200 Amp Bus MCC Power Bus Capacity ⋆  8…10
    P22 2000 Amp Bus
    P24 3000 Amp Bus
    P30 UPS Control Bus, DC Input w/Precharge only UPS Control Bus 8…10
    ⋆ Only one option of this type may be selected.
    § Contactor options are not available for systems with MCC power bus.

    The catalog numbers listed below are for base drives in their respective power ratings. Click "Build a Catalog Number" to configure a drive for ordering. For detailed drive information, refer to the PowerFlex 750-Series Technical Data, publication 750-TD001.

    IP00/IP20, NEMA/UL Type Open ♣ 

    380…480V AC, Three-Phase Drives
    480V AC Input 400V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    2.1 2.3 3.2 1 0.5 20G11RD2P1AA0NNNNN 2.1 2.3 3.2 0.75 0.37 20G11RC2P1JA0NNNNN 1
    3.4 3.7 5.1 2 1.5 20G11RD3P4AA0NNNNN 3.5 3.9 5.3 1.5 0.75 20G11RC3P5JA0NNNNN 1
    5 5.5 7.5 3 2 20G11RD5P0AA0NNNNN 5 5.5 7.5 2.2 1.5 20G11RC5P0JA0NNNNN 1
    8 8.8 12 5 3 20G11RD8P0AA0NNNNN 8.7 9.6 13.1 4 2.2 20G11RC8P7JA0NNNNN 1
    11 12.1 16.5 7.5 5 20G11RD011AA0NNNNN 11.5 12.7 17.3 5.5 4 20G11RC011JA0NNNNN 1
    14 15.4 21 10 7.5 20G11RD014AA0NNNNN 15.4 16.9 23.1 7.5 5.5 20G11RC015JA0NNNNN 1
    2.1 3.1 3.7 1 1 20G11ND2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20G11NC2P1JA0NNNNN 2
    3.4 5.1 6.1 2 2 20G11ND3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20G11NC3P5JA0NNNNN 2
    5 7.5 9 3 3 20G11ND5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20G11NC5P0JA0NNNNN 2
    8 12 14.4 5 5 20G11ND8P0AA0NNNNN 8.7 13 15.6 4 4 20G11NC8P7JA0NNNNN 2
    11 16.5 19.8 7.5 7.5 20G11ND011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20G11NC011JA0NNNNN 2
    14 (11) 15.4 (16.5) 21 (21) 10 7.5 20G11ND014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20G11NC015JA0NNNNN 2
    22 (14) 24.2 (21) 33 (33) 15 10 20G11ND022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20G11NC022JA0NNNNN 2
    27 (22) 29.7 (33) 40.5 (40.5) 20 15 20G11ND027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20G11NC030JA0NNNNN 3
    34 (27) 37.4 (40.5) 51 (51) 25 20 20G11ND034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20G11NC037JA0NNNNN 3
    40 (34) 44 (51) 60 (61.2) 30 25 20G11ND040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20G11NC043JA0NNNNN 3
    52 (40) 57.2 (60) 78 (78) 40 30 20G11ND052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20G11NC060JA0NNNNN 4
    65 (52) 71.5 (78) 97.5 (97.5) 50 40 20G11ND065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20G11NC072JA0NNNNN 4
    77 (65) 84.7 (97.5) 116 (117) 60 50 20G11ND077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20G11NC085JA0NNNNN 5
    96 (77) 106 (116) 144 (144) 75 60 20G11ND096AA0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20G11NC104JA0NNNNN 5
    125 (96) 138 (144) 188 (188) 100 75 20G1AND125AN0NNNNN 140 (104) 154 (156) 210 (210) 75 55 20G1ANC140JN0NNNNN 6 ♠ 
    156 (125) 172 (188) 234 (234) 125 100 20G1AND156AN0NNNNN 170 (140) 187 (210) 255 (255) 90 75 20G1ANC170JN0NNNNN 6 ♠ 
    186 (156) 205 (234) 279 (281) 150 125 20G1AND186AN0NNNNN 205 (170) 226 (255) 308 (308) 110 90 20G1ANC205JN0NNNNN 6 ♠ 
    248 (186) 273 (279) 372 (372) 200 150 20G1AND248AN0NNNNN 260 (205) 286 (308) 390 (390) 132 110 20G1ANC260JN0NNNNN 6 ♠ 
    302 (248) 332 (372) 453 (453) 250 200 20G1AND302AN0NNNNN 302 (260) 332 (390) 453 (468) 160 132 20G1ANC302JN0NNNNN 7 ♠ 
    361 (302) 397 (453) 542 (544) 300 250 20G1AND361AN0NNNNN 367 (302) 404 (453) 551 (551) 200 160 20G1ANC367JN0NNNNN 7 ♠ 
    415 (361) 457 (542) 623 (650) 350 300 20G1AND415AN0NNNNN 456 (367) 502 (551) 684 (684) 250 200 20G1ANC456JN0NNNNN 7 ♠ 
    ♣ Frames 2…5 are IP20, Frames 6…7 are IP00.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ♠ Also available with internal Brake IGBT (20G1xxxxxxx A xxxxxx).
    § Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    Frames 3, 4 and 5 are 600V only drives. Frames 6 and 7 are dual voltage drives and can be operated at 600V or 690V AC.
    Important: Frames 3, 4, and 5 must NOT be used in common DC input sharing applications with Frame 6 or larger drives. For details, contact your local Rockwell Automation sales office or Allen Bradley Distributor.


    600V AC, Three-Phase Drives ♣ 
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
    Cont. 1 Min. 3 Sec.
    1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20G11NE1P7AA0NNNNN 3
    2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20G11NE2P7AA0NNNNN 3
    3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20G11NE3P9AA0NNNNN 3
    6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20G11NE6P1AA0NNNNN 3
    9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20G11NE009AA0NNNNN 3
    11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20G11NE011AA0NNNNN 3
    17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20G11NE017AA0NNNNN 3
    22 (17) 24 (26) 33 (46) 20 15 20G11NE022AA0NNNNN 3
    27 (22) 30 (33) 41 (59) 25 20 20G11NE027AA0NNNNN 4
    32 (27) 35 (41) 48 (73) 30 25 20G11NE032AA0NNNNN 4
    41 (32) 45 (48) 62 (86) 40 30 20G11NE041AA0NNNNN 5
    52 (41) 57 (62) 78 (111) 50 40 20G11NE052AA0NNNNN 5
    63 (52) 69 (78) 95 (140) 60 50 20G11NE063AN0NNNNN 6
    77 (63) 85 (95) 116 (170) 75 60 20G11NE077AN0NNNNN 6
    99 (77) 109 (116) 149 (208) 100 75 20G11NE099AN0NNNNN 6
    125 (99) 138 (149) 188 (267) 125 100 20G11NE125AN0NNNNN 6
    144 (125) 158 (188) 216 (338) 150 125 20G11NE144AN0NNNNN 6
    192 (144) 211 (216) 288 (389) 200 150 20G11NE192AN0NNNNN 7
    242 (192) 266 (288) 363 (518) 250 200 20G11NE242AN0NNNNN 7
    289 (242) 318 (363) 434 (653) 300 250 20G11NE289AN0NNNNN 7
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase Drives ♣ 
    Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆  Frame Size
    Cont. 1 Min. 3 Sec.
    12 (8.5) 12.7 (12.8) 17.3 (23) 7.5 5.5 20G11NF012JN0NNNNN 6
    15 (11.5) 16.5 (17.3) 22.5 (31.1) 11 7.5 20G11NF015JN0NNNNN 6
    20 (15) 22 (23) 30 (41) 15 11 20G11NF020JN0NNNNN 6
    23 (20) 25 (30) 35 (54) 18.5 15 20G11NF023JA0NNNNN 6
    30 (23) 33 (35) 45 (62) 22 18.5 20G11NF030JN0NNNNN 6
    34 (30) 37 (45) 51 (81) 30 22 20G11NF034JN0NNNNN 6
    46 (34) 51 (51) 69 (92) 37 30 20G11NF046JN0NNNNN 6
    50 (46) 55 (69) 75 (124) 45 37 20G11NF050JN0NNNNN 6
    61 (50) 67 (75) 92 (135) 55 45 20G11NF061JN0NNNNN 6
    82 (61) 90 (92) 123 (165) 75 55 20G11NF082JN0NNNNN 6
    98 (82) 108 (123) 147 (221) 90 75 20G11NF098JN0NNNNN 6
    119 (98) 131 (147) 179 (265) 110 90 20G11NF119JN0NNNNN 6
    142 (119) 156 (179) 213 (321) 132 110 20G11NF142JN0NNNNN 6
    171 (142) 188 (213) 257 (383) 160 132 20G11NF171JN0NNNNN 7
    212 (171) 233 (257) 318 (462) 200 160 20G11NF212JN0NNNNN 7
    263 (212) 289 (318) 395 (572) 250 200 20G11NF263JN0NNNNN 7
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    Flange Mount
    Front = IP20, NEMA/UL Type Open, Back/Heatsink = IP66, NEMA/UL Type 4X


    380…480V AC, Three-Phase Drives
    480V AC Input 400V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    2.1 3.1 3.7 1 1 20G11FD2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20G11FC2P1JA0NNNNN 2
    3.4 5.1 6.1 2 2 20G11FD3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20G11FC3P5JA0NNNNN 2
    5 7.5 9 3 3 20G11FD5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20G11FC5P0JA0NNNNN 2
    8 12 14.4 5 5 20G11FD8P0AA0NNNNN 8.7 13 15.6 4 4 20G11FC8P7JA0NNNNN 2
    11 16.5 19.8 7.5 7.5 20G11FD011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20G11FC011JA0NNNNN 2
    14 (11) 15.4 (16.5) 21 (21) 10 7.5 20G11FD014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20G11FC015JA0NNNNN 2
    22 (14) 24.2 (21) 33 (33) 15 10 20G11FD022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20G11FC022JA0NNNNN 2
    27 (22) 29.7 (33) 40.5 (40.5) 20 15 20G11FD027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20G11FC030JA0NNNNN 3
    34 (27) 37.4 (40.5) 51 (51) 25 20 20G11FD034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20G11FC037JA0NNNNN 3
    40 (34) 44 (51) 60 (61.2) 30 25 20G11FD040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20G11FC043JA0NNNNN 3
    52 (40) 57.2 (60) 78 (78) 40 30 20G11FD052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20G11FC060JA0NNNNN 4
    65 (52) 71.5 (78) 97.5 (97.5) 50 40 20G11FD065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20G11FC072JA0NNNNN 4
    77 (65) 84.7 (97.5) 116 (117) 60 50 20G11FD077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20G11FC085JA0NNNNN 5
    96 (77) 106 (116) 144 (144) 75 60 20G11FD096AA0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20G11FC104JA0NNNNN 5
    Note: Frames 6…7 require an optional user installed flange kit with an IP00, NEMA/UL Type Open drive.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    § Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    600V AC, Three-Phase Drives ♣ 
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
    Cont. 1 Min. 3 Sec.
    1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20G11FE1P7AA0NNNNN 3
    2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20G11FE2P7AA0NNNNN 3
    3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20G11FE3P9AA0NNNNN 3
    6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20G11FE6P1AA0NNNNN 3
    9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20G11FE009AA0NNNNN 3
    11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20G11FE011AA0NNNNN 3
    17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20G11FE017AA0NNNNN 3
    22 (17) 24 (26) 33 (46) 20 15 20G11FE022AA0NNNNN 3
    27 (22) 30 (33) 41 (59) 25 20 20G11FE027AA0NNNNN 4
    32 (27) 35 (41) 48 (73) 30 25 20G11FE032AA0NNNNN 4
    41 (32) 45 (48) 62 (86) 40 30 20G11FE041AA0NNNNN 5
    52 (41) 57 (62) 78 (111) 50 40 20G11FE052AA0NNNNN 5
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    IP54, NEMA/UL Type 12

    380…480V AC, Three-Phase Drives
    480V AC Input 400V AC Input Frame Size
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆ 
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    2.1 3.1 3.7 1 1 20G11GD2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20G11GC2P1JA0NNNNN 2
    3.4 5.1 6.1 2 2 20G11GD3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20G11GC3P5JA0NNNNN 2
    5 7.5 9 3 3 20G11GD5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20G11GC5P0JA0NNNNN 2
    8 12 14.4 5 5 20G11GD8P0AA0NNNNN 8.7 13 15.6 4 4 20G11GC8P7JA0NNNNN 2
    11 16.5 19.8 7.5 7.5 20G11GD011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20G11GC011JA0NNNNN 2
    14 (11) 15.4 (16.5) 21 (21) 10 7.5 20G11GD014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20G11GC015JA0NNNNN 2
    22 (14) 24.2 (21) 33 (33) 15 10 20G11GD022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20G11GC022JA0NNNNN 2
    27 (22) 29.7 (33) 40.5 (40.5) 20 15 20G11GD027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20G11GC030JA0NNNNN 3
    34 (27) 37.4 (40.5) 51 (51) 25 20 20G11GD034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20G11GC037JA0NNNNN 3
    40 (34) 44 (51) 60 (61.2) 30 25 20G11GD040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20G11GC043JA0NNNNN 3
    52 (40) 57.2 (60) 78 (78) 40 30 20G11GD052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20G11GC060JA0NNNNN 4
    65 (52) 71.5 (78) 97.5 (97.5) 50 40 20G11GD065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20G11GC072JA0NNNNN 5
    77 (65) 84.7 (97.5) 116 (117) 60 50 20G11GD077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20G11GC085JA0NNNNN 5
    96 (77) 106 (116) 144 (144) 75 60 20G1AGD096AN0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20G1AGC104JN0NNNNN 6 ♠ 
    125 (96) 138 (144) 188 (188) 100 75 20G1AGD125AN0NNNNN 140 (104) 154 (156) 210 (210) 75 55 20G1AGC140JN0NNNNN 6 ♠ 
    156 (125) 172 (188) 234 (234) 125 100 20G1AGD156AN0NNNNN 170 (140) 187 (210) 255 (255) 90 75 20G1AGC170JN0NNNNN 6 ♠ 
    186 (156) 205 (234) 279 (281) 150 125 20G1AGD186AN0NNNNN 205 (170) 226 (255) 308 (308) 110 90 20G1AGC205JN0NNNNN 6 ♠ 
    248 (186) 273 (279) 372 (372) 200 150 20G1AGD248AN0NNNNN 260 (205) 286 (308) 390 (390) 132 110 20G1AGC260JN0NNNNN 7 ♠ 
    302 (248) 332 (372) 453 (453) 250 200 20G1AGD302AN0NNNNN 302 (260) 332 (390) 453 (468) 160 132 20G1AGC302JN0NNNNN 7 ♠ 
    361 (302) 397 (453) 542 (544) 300 250 20G1AGD361AN0NNNNN 367 (302) 404 (453) 551 (551) 200 160 20G1AGC367JN0NNNNN 7 ♠ 
    415 (361) 457 (542) 623 (650) 350 300 20G1AGD415AN0NNNNN 456 (367) 502 (551) 684 (684) 250 200 20G1AGC456JN0NNNNN 7 ♠ 
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ♠ Also available with internal Brake IGBT (20G1xxxxxxx A xxxxxx).
    § Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

    Frames 3, 4 and 5 are 600V only drives. Frames 6 and 7 are dual voltage drives and can be operated at 600V or 690V AC.
    Important: Frames 3, 4, and 5 must NOT be used in common DC input sharing applications with Frame 6 or larger drives. For details, contact your local Rockwell Automation sales office or Allen Bradley Distributor.


    600V AC, Three-Phase Drives ♣ 
    Output Amps §  Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
    Cont. 1 Min. 3 Sec.
    1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20G11GE1P7AA0NNNNN 3
    2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20G11GE2P7AA0NNNNN 3
    3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20G11GE3P9AA0NNNNN 3
    6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20G11GE6P1AA0NNNNN 3
    9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20G11GE009AA0NNNNN 3
    11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20G11GE011AA0NNNNN 3
    17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20G11GE017AA0NNNNN 3
    22 (17) 24 (26) 33 (46) 20 15 20G11GE022AA0NNNNN 3
    27 (22) 30 (33) 41 (59) 25 20 20G11GE027AA0NNNNN 4
    32 (27) 35 (41) 48 (73) 30 25 20G11GE032AA0NNNNN 4
    41 (32) 45 (48) 62 (86) 40 30 20G11GE041AA0NNNNN 5
    52 (41) 57 (62) 78 (111) 50 40 20G11GE052AA0NNNNN 5
    63 (52) 69 (78) 95 (140) 60 50 20G11GE063AN0NNNNN 6
    77 (63) 85 (95) 116 (170) 75 60 20G11GE077AN0NNNNN 6
    99 (77) 109 (116) 149 (208) 100 75 20G11GE099AN0NNNNN 6
    125 (99) 138 (149) 188 (267) 125 100 20G11GE125AN0NNNNN 6
    144 (125) 158 (188) 216 (338) 150 125 20G11GE144AN0NNNNN 6
    192 (144) 211 (216) 288 (389) 200 150 20G11GE192AN0NNNNN 7
    242 (192) 266 (288) 363 (518) 250 200 20G11GE242AN0NNNNN 7
    289 (242) 318 (363) 434 (653) 300 250 20G11GE289AN0NNNNN 7
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase Drives ♣ 
    Output Amps §  Normal Duty kW Heavy Duty kW Cat. No. ⋆  Frame Size
    Cont. 1 Min. 3 Sec.
    12 (8.5) 12.7 (12.8) 17.3 (23) 7.5 5.5 20G11GF012JN0NNNNN 6
    15 (11.5) 16.5 (17.3) 22.5 (31.1) 11 7.5 20G11GF015JN0NNNNN 6
    20 (15) 22 (23) 30 (41) 15 11 20G11GF020JN0NNNNN 6
    23 (20) 25 (30) 35 (54) 18.5 15 20G11GF023JN0NNNNN 6
    30 (23) 33 (35) 45 (62) 22 18.5 20G11GF030JN0NNNNN 6
    34 (30) 37 (45) 51 (81) 30 22 20G11GF034JN0NNNNN 6
    46 (34) 51 (51) 69 (92) 37 30 20G11GF046JN0NNNNN 6
    50 (46) 55 (69) 75 (124) 45 37 20G11GF050JN0NNNNN 6
    61 (50) 67 (75) 92 (135) 55 45 20G11GF061JN0NNNNN 6
    82 (61) 90 (92) 123 (165) 75 55 20G11GF082JN0NNNNN 6
    98 (82) 108 (123) 147 (221) 90 75 20G11GF098JN0NNNNN 6
    119 (98) 131 (147) 179 (265) 110 90 20G11GF119JN0NNNNN 6
    142 (119) 156 (179) 213 (321) 132 110 20G11GF142JN0NNNNN 6
    171 (142) 188 (213) 257 (383) 160 132 20G11GF171JN0NNNNN 7
    212 (171) 233 (257) 318 (462) 200 160 20G11GF212JN0NNNNN 7
    263 (212) 289 (318) 395 (572) 250 200 20G11GF263JN0NNNNN 7
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    § These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    DC Bus terminals are not supplied with AC input Frame 6 and 7 drives, however user installed kits are available (see PowerFlex 750-Series Option Kits). For Frame 8 and 9 Common DC Input drives, see IP20, NEMA/UL Type 1 (2500 MCC Style Cabinet).

    200 kW / 250 Hp to 1400 kW / 2000 Hp — Frames 8…10

    Click to enlarge - pf755_1bay_open   Click to enlarge - pf755_2bay_open
         
    IP20, NEMA/UL Type 1 Drive (2500 MCC Style Cabinet)   IP20, NEMA/UL Type 1 Drive and Options (2500 MCC Style Cabinet)
         
    includes:
  • DC link choke

  • AC line fuses

  • Roll-out design
  •   includes:
  • DC link choke

  • AC line fuses

  • Roll-out design

  • Option bay for control/protection devices
  •      
    Important: A Roll-out Cart is required for installation.   Important: A Roll-out Cart is required for installation.

      Click to enlarge - rollout_whandle  
         
      Roll-out Cart  
         
     
  • Required for Frame 8…9 drives

  • Adjustable Curb Height: 0…182 mm (0…7.2 in.)

  • Adjustment for Curb Offset/Reach: 0…114 mm (0…4.5 in.)

  • For ordering information, see
  • PowerFlex 750-Series Option Kits
     

    2500 MCC Style Cabinets

    Drives listed on the following pages utilize a CENTERLINE® 2500 MCC style cabinet. This term refers to the type of cabinet and does not imply that the MCC bus is included. To add an MCC bus, refer to pages 98…99 and choose option P20, P22 or P24.

    Power Wiring Options (Frame 8 Only)
    Cable Option Wire Entry/Exit Location IP20, NEMA/UL Type 1 Drive
    (2500 MCC Style Cabinet)
    IP20, NEMA/UL Type 1 Drive and Options
    (2500 MCC Style Cabinet)
    600 mm (23.6 in.) Deep Drive Bay 800 mm (31.5 in.) Deep Drive Bay 600 mm Deep Drive Bay w/600 mm Wide Wiring Only Bay 600 or 800 mm Deep Drive Bay w/600 mm Options Bay
    Armored Cable with Conduit Hubs Top Entry, Bottom Exit   ü ü ü
    Bottom Entry, Bottom Exit   ü ü  
    Top Entry, Top Exit   ü ü  
    Shielded Cable with Conduit Hubs Top Entry, Bottom Exit ü ü ü ü
    Bottom Entry, Bottom Exit   ü ü  
    Top Entry, Top Exit   ü ü ü ∆ 
    Shielded Cable without Conduit Hubs ♦  Bottom Entry, Bottom Exit ü ü ü  
    ∆ This wiring configuration is possible when there are no ouput options in the option bay and the motor connections are wired from the drive bay.
    ♦ Other configurations with shielded cable are possible, however the use of conduit hubs is recommended.

    IP20, NEMA/UL Type 1 (2500 MCC Style Cabinet)

    380…400V AC, Three-Phase and 540V DC Input Drives ▶ 
    Light Duty Normal Duty Heavy Duty Cat. No. ⋆  §  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    540 594 NA 315 460 506 693 250 385 578 693 200 20G1A‡ C460JN0NNNNN 8
    585 644 315 540 594 821 315 456 684 821 250 20G1A‡ C540JN0NNNNN 8
    612 673 355 567 624 851 315 472 708 851 250 20G1A‡ C567JN0NNNNN 8
    750 825 400 650 715 975 355 540 810 975 315 20G1A‡ C650JN0NNNNN 8
    796 876 450 750 825 1125 400 585 878 1125 315 20G1A‡ C750JN0NNNNN 8
    832 915 450 770 847 1155 400 642 963 1155 355 20G1A‡ C770JN0NNNNN 8
    1040 1144 560 910 1001 1365 500 750 1125 1365 400 20G11‡ C910JN0NNNNN 9
    1090 1199 630 1040 1144 1584 560 880 1320 1584 500 20G11‡ C1K0JN0NNNNN 9
    1175 1293 710 1090 1199 1638 630 910 1365 1638 500 20G11‡ C1K1JN0NNNNN 9
    1465 1612 800 1175 1293 1872 710 1040 1560 1872 560 20G11‡ C1K2JN0NNNNN 9
    1480 1628 850 1465 1612 2198 800 1090 1635 2198 630 20G11‡ C1K4JN0NNNNN 9
    1600 1760 900 1480 1628 2220 850 1175 1763 2220 710 20G11‡ C1K5JN0NNNNN 9
    1715 1887 1000 1590 1749 2385 900 1325 1988 2385 710 20G11‡ C1K6JN0NNNNN 10
    2330 2563 1400 2150 2365 3225 1250 1800 2700 3225 1000 20G11‡ C2K1JN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. Refer to the Power Wiring Options table.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .

    480V AC, Three-Phase and 650V DC Input Drives ▶ 
    Light Duty Normal Duty Heavy Duty Cat. No. §  Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    485 534 NA 400 430 473 666 350 370 555 666 300 20G1A‡ D430AN0NNNNN 8
    545 600 450 485 534 745 400 414 621 745 350 20G1A‡ D485AN0NNNNN 8
    590 649 500 545 600 818 450 454 681 818 350 20G1A‡ D545AN0NNNNN 8
    710 781 600 617 679 926 500 485 728 926 400 20G1A‡ D617AN0NNNNN 8
    765 842 650 710 781 1065 600 545 818 1065 450 20G1A‡ D710AN0NNNNN 8
    800 880 700 740 817 1110 650 617 926 1110 500 20G1A‡ D740AN0NNNNN 8
    960 1056 800 800 880 1278 700 710 1065 1278 600 20G11‡ D800AN0NNNNN 9
    1045 1150 900 960 1056 1440 800 795 1193 1440 700 20G11‡ D960AN0NNNNN 9
    1135 1249 1000 1045 1150 1568 900 800 1200 1568 750 20G11‡ D1K0AN0NNNNN 9
    1365 1502 1100 1135 1249 1728 1000 960 1440 1728 800 20G11‡ D1K2AN0NNNNN 9
    1420 1562 1250 1365 1502 2048 1100 1045 1568 2048 900 20G11‡ D1K3AN0NNNNN 9
    1540 1694 1350 1420 1562 2130 1250 1135 1703 2130 1000 20G11‡ D1K4AN0NNNNN 9
    1655 1821 1500 1525 1678 2288 1350 1270 1905 2288 1100 20G11‡ D1K5JN0NNNNN 10
    2240 2464 2000 2070 2277 3105 1750 1730 2595 3105 1650 20G11‡ D2K0JN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. Refer to the Power Wiring Options table.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .

    600V AC, Three-Phase and 810V DC Input Drives ▶ 
    Light Duty Normal Duty Heavy Duty Cat. No. §  Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    355 391 NA 350 295 325 490 300 272 408 490 250 20G1A‡ E295AN0NNNNN 8
    395 435 400 355 391 533 350 295 443 533 300 20G1A‡ E355AN0NNNNN 8
    435 479 450 395 435 593 400 329 494 593 350 20G1A‡ E395AN0NNNNN 8
    460 506 500 435 479 639 450 355 533 639 350 20G1A‡ E435AN0NNNNN 8
    510 561 500 460 506 711 500 395 593 711 400 20G1A‡ E460AN0NNNNN 8
    545 600 550 510 561 765 500 425 638 765 450 20G1A‡ E510AN0NNNNN 8
    690 759 700 595 655 918 600 510 765 918 500 20G11‡ E595AN0NNNNN 9
    760 836 800 630 693 1071 700 595 893 1071 600 20G11‡ E630AN0NNNNN 9
    835 919 900 760 836 1140 800 630 945 1140 700 20G11‡ E760AN0NNNNN 9
    900 990 950 825 908 1260 900 700 1050 1260 750 20G11‡ E825AN0NNNNN 9
    980 1078 1000 900 990 1368 950 760 1140 1368 800 20G11‡ E900AN0NNNNN 9
    1045 1150 1100 980 1078 1470 1000 815 1223 1470 900 20G11‡ E980AN0NNNNN 9
    1220 1342 1200 1110 1221 1665 1100 920 1380 1665 1000 20G11‡ E1K1AN0NNNNN 10 ♣ 
    1530 1683 1500 1430 1573 2145 1400 1190 1785 2145 1250 20G11‡ E1K4AN0NNNNN 10 ♣ 
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. Refer to the Power Wiring Options table.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase and 932V DC Input Drives ▶ 
    Light Duty Normal Duty Heavy Duty Cat. No. §  ⋆  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    330 363 NA 315 265 292 375 250 215 323 375 200 20G1A‡ F265AN0NNNNN 8
    370 407 355 330 363 473 315 265 398 473 250 20G1A‡ F330AN0NNNNN 8
    410 451 400 370 407 555 355 308 462 555 300 20G1A‡ F370AN0NNNNN 8
    460 506 450 415 457 639 400 370 555 639 355 20G1A‡ F415AN0NNNNN 8
    500 550 500 460 506 675 450 375 563 675 375 20G1A‡ F460AN0NNNNN 8
    530 583 530 500 550 750 500 413 620 750 400 20G1A‡ F500AN0NNNNN 8
    650 715 630 590 649 885 560 460 690 885 450 20G11‡ F590AN0NNNNN 9
    710 781 710 650 715 975 630 500 750 975 500 20G11‡ F650AN0NNNNN 9
    790 869 800 710 781 1065 710 590 885 1065 560 20G11‡ F710AN0NNNNN 9
    860 946 850 765 842 1170 750 650 975 1170 630 20G11‡ F765AN0NNNNN 9
    960 1056 900 795 875 1350 800 750 1125 1350 710 20G11‡ F795AN0NNNNN 9
    1020 1122 1000 960 1056 1440 900 795 1193 1440 800 20G11‡ F960AN0NNNNN 9
    1150 1265 1100 1040 1144 1560 1000 865 1298 1560 900 20G11‡ F1K0AN0NNNNN 10 ♣ 
    1485 1634 1500 1400 1540 2100 1400 1160 1740 2100 1120 20G11‡ F1K4AN0NNNNN 10 ♣ 
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. Refer to the Power Wiring Options table.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    IP54, NEMA Type 12 (2500 MCC Style Cabinet)

    380…400V AC, Three-Phase and 540V DC Input Drives ▶  ♣ 
    Light Duty Normal Duty Heavy Duty Cat. No. ⋆  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    540 594 NA 315 460 506 693 250 385 578 693 200 20G1AJC460AN0NNNNN 8
    585 644 315 540 594 821 315 456 684 821 250 20G1AJC540AN0NNNNN 8
    612 673 355 567 624 851 315 472 708 851 250 20G1AJC567AN0NNNNN 8
    750 825 400 650 715 975 355 540 810 975 315 20G1AJC650AN0NNNNN 8
    796 876 450 750 825 1125 400 585 878 1125 315 20G1AJC750AN0NNNNN 8
    832 915 450 770 847 1155 400 642 963 1155 355 20G1AJC770AN0NNNNN 8
    1040 1144 560 910 1001 1365 500 750 1125 1365 400 20G11JC910AN0NNNNN 9
    1090 1199 630 1040 1144 1584 560 880 1320 1584 500 20G11JC1K0AN0NNNNN 9
    1175 1293 710 1090 1199 1638 630 910 1365 1638 500 20G11JC1K1AN0NNNNN 9
    1465 1612 800 1175 1293 1872 710 1040 1560 1872 560 20G11JC1K2AN0NNNNN 9
    1480 1628 850 1465 1612 2198 800 1090 1635 2198 630 20G11JC1K4AN0NNNNN 9
    1600 1760 900 1480 1628 2220 850 1175 1763 2220 710 20G11JC1K5AN0NNNNN 9
    1715 1887 1000 1590 1749 2385 900 1325 1988 2385 710 20G11JC1K6AN0NNNNN 10
    2330 2563 1400 2150 2365 3225 1250 1800 2700 3225 1000 20G11JC2K1AN0NNNNN 10
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    480V AC, Three-Phase and 650V DC Input Drives ▶  ♣ 
    Light Duty Normal Duty Heavy Duty Cat. No. Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    485 534 NA 400 430 473 666 350 370 555 666 300 20G1AJD430AN0NNNNN 8
    545 600 450 485 534 745 400 414 621 745 350 20G1AJD485AN0NNNNN 8
    590 649 500 545 600 818 450 454 681 818 350 20G1AJD545AN0NNNNN 8
    710 781 600 617 679 926 500 485 728 926 400 20G1AJD617AN0NNNNN 8
    765 842 650 710 781 1065 600 545 818 1065 450 20G1AJD710AN0NNNNN 8
    800 880 700 740 817 1110 650 617 926 1110 500 20G1AJD740AN0NNNNN 8
    960 1056 800 800 880 1278 700 710 1065 1278 600 20G11JD800AN0NNNNN 9
    1045 1150 900 960 1056 1440 800 795 1193 1440 700 20G11JD960AN0NNNNN 9
    1135 1249 1000 1045 1150 1568 900 800 1200 1568 750 20G11JD1K0AN0NNNNN 9
    1365 1502 1100 1135 1249 1728 1000 960 1440 1728 800 20G11JD1K2AN0NNNNN 9
    1420 1562 1250 1365 1502 2048 1100 1045 1568 2048 900 20G11JD1K3AN0NNNNN 9
    1540 1694 1350 1420 1562 2130 1250 1135 1703 2130 1000 20G11JD1K4AN0NNNNN 9
    1655 1821 1500 1525 1678 2288 1350 1270 1905 2288 1100 20G11JD1K5AN0NNNNN 10
    2240 2464 2000 2070 2277 3105 1750 1730 2595 3105 1650 20G11JD2K0AN0NNNNN 10
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    600V AC, Three-Phase and 810V DC Input Drives ▶  ♣ 
    Light Duty Normal Duty Heavy Duty Cat. No. Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    355 391 NA 350 295 325 490 300 272 408 490 250 20G1AJE295AN0NNNNN 8
    395 435 400 355 391 533 350 295 443 533 300 20G1AJE355AN0NNNNN 8
    435 479 450 395 435 593 400 329 494 593 350 20G1AJE395AN0NNNNN 8
    460 506 500 435 479 639 450 355 533 639 350 20G1AJE435AN0NNNNN 8
    510 561 500 460 506 711 500 395 593 711 400 20G1AJE460AN0NNNNN 8
    545 600 550 510 561 765 500 425 638 765 450 20G1AJE510AN0NNNNN 8
    690 759 700 595 655 918 600 510 765 918 500 20G11JE595AN0NNNNN 9
    760 836 800 630 693 1071 700 595 893 1071 600 20G11JE630AN0NNNNN 9
    835 919 900 760 836 1140 800 630 945 1140 700 20G11JE760AN0NNNNN 9
    900 990 950 825 908 1260 900 700 1050 1260 750 20G11JE825AN0NNNNN 9
    980 1078 1000 900 990 1368 950 760 1140 1368 800 20G11JE900AN0NNNNN 9
    1045 1150 1100 980 1078 1470 1000 815 1223 1470 900 20G11JE980AN0NNNNN 9
    1220 1342 1200 1110 1221 1665 1100 920 1380 1665 1000 20G11JE1K1AN0NNNNN 10
    1530 1683 1500 1430 1573 2145 1400 1190 1785 2145 1250 20G11JE1K4AN0NNNNN 10
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase and 932V DC Input Drives ▶  ♣ 
    Light Duty Normal Duty Heavy Duty Cat. No. ⋆  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    330 363 NA 315 265 292 375 250 215 323 375 200 20G1AJF265AN0NNNNN 8
    370 407 355 330 363 473 315 265 398 473 250 20G1AJF330AN0NNNNN 8
    410 451 400 370 407 555 355 308 462 555 300 20G1AJF370AN0NNNNN 8
    460 506 450 415 457 639 400 370 555 639 355 20G1AJF415AN0NNNNN 8
    500 550 500 460 506 675 450 375 563 675 375 20G1AJF460AN0NNNNN 8
    530 583 530 500 550 750 500 413 620 750 400 20G1AJF500AN0NNNNN 8
    650 715 630 590 649 885 560 460 690 885 450 20G11JF590AN0NNNNN 9
    710 781 710 650 715 975 630 500 750 975 500 20G11JF650AN0NNNNN 9
    790 869 800 710 781 1065 710 590 885 1065 560 20G11JF710AN0NNNNN 9
    860 946 850 765 842 1170 750 650 975 1170 630 20G11JF765AN0NNNNN 9
    960 1056 900 795 875 1350 800 750 1125 1350 710 20G11JF795AN0NNNNN 9
    1020 1122 1000 960 1056 1440 900 795 1193 1440 800 20G11JF960AN0NNNNN 9
    1150 1265 1100 1040 1144 1560 1000 865 1298 1560 900 20G11JF1K0AN0NNNNN 10
    1485 1634 1500 1400 1540 2100 1400 1160 1740 2100 1120 20G11JF1K4AN0NNNNN 10
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    IP00, NEMA Type Open Drive

    To order an IP00 drive:

    1. Using the tables that follow, locate your desired drive output values.
    3. Note the Quantity Required.
    4. Order the specified quantity (1, 2, or 3) of the Base Drive Catalog Number.

    380…400V AC, Three-Phase and 540V DC Input Drives ♣  ▶ 
    Light Duty Normal Duty Heavy Duty Base Drive Cat. No. ⋆  Quantity Required Equivalent Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. Cont. Cont.
    540 315 460 250 385 200 20G11TC460AN0NNNNN 1 8
    585 315 540 315 456 250 20G11TC540AN0NNNNN 1 8
    612 355 567 315 472 250 20G11TC567AN0NNNNN 1 8
    750 400 650 355 540 315 20G11TC650AN0NNNNN 1 8
    796 450 750 400 585 315 20G11TC750AN0NNNNN 1 8
    832 450 770 400 642 355 20G11TC770AN0NNNNN 1 8
    1040 560 910 500 750 400 20G11TC460AN0NNNNN 2 9
    1090 630 1040 560 880 500 20G11TC540AN0NNNNN 2 9
    1175 710 1090 630 910 500 20G11TC567AN0NNNNN 2 9
    1465 800 1175 710 1040 560 20G11TC650AN0NNNNN 2 9
    1480 850 1465 800 1090 630 20G11TC750AN0NNNNN 2 9
    1600 900 1480 850 1175 710 20G11TC770AN0NNNNN 2 9
    1715 1000 1590 900 1325 710 20G11TC567AN0NNNNN 3 10
    2330 1400 2150 1250 1800 1000 20G11TC770AN0NNNNN 3 10
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    480V AC, Three-Phase and 650V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. Quantity Required Equivalent Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. Cont. Cont.
    485 400 430 350 370 300 20G11TD430AN0NNNNN 1 8
    545 450 485 400 414 350 20G11TD485AN0NNNNN 1 8
    590 500 545 450 454 350 20G11TD545AN0NNNNN 1 8
    710 600 617 500 485 400 20G11TD617AN0NNNNN 1 8
    765 650 710 600 545 450 20G11TD710AN0NNNNN 1 8
    800 700 740 650 617 500 20G11TD740AN0NNNNN 1 8
    960 800 800 700 710 600 20G11TD430AN0NNNNN 2 9
    1045 900 960 800 795 700 20G11TD485AN0NNNNN 2 9
    1135 1000 1045 900 800 750 20G11TD545AN0NNNNN 2 9
    1365 1100 1135 1000 960 800 20G11TD617AN0NNNNN 2 9
    1420 1250 1365 1100 1045 900 20G11TD710AN0NNNNN 2 9
    1540 1350 1420 1250 1135 1000 20G11TD740AN0NNNNN 2 9
    1655 1500 1525 1350 1270 1100 20G11TD545AN0NNNNN 3 10
    2240 2000 2070 1750 1730 1650 20G11TD740AN0NNNNN 3 10
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    600V AC, Three-Phase and 725V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. Quantity Required Equivalent Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. Cont. Cont.
    355 350 295 300 272 250 20G11TE295AN0NNNNN 1 8
    395 400 355 350 295 300 20G11TE355AN0NNNNN 1 8
    435 450 395 400 329 350 20G11TE395AN0NNNNN 1 8
    460 500 435 450 355 350 20G11TE435AN0NNNNN 1 8
    510 500 460 500 395 400 20G11TE460AN0NNNNN 1 8
    545 550 510 500 425 450 20G11TE510AN0NNNNN 1 8
    690 700 595 600 510 500 20G11TE295AN0NNNNN 2 9
    760 800 630 700 595 600 20G11TE355AN0NNNNN 2 9
    835 900 760 800 630 700 20G11TE395AN0NNNNN 2 9
    900 950 825 900 700 750 20G11TE435AN0NNNNN 2 9
    980 1000 900 950 760 800 20G11TE460AN0NNNNN 2 9
    1045 1100 980 1000 815 900 20G11TE510AN0NNNNN 2 9
    1220 1200 1110 1100 920 1000 20G11TE395AN0NNNNN 3 10
    1530 1500 1430 1400 1190 1250 20G11TE510AN0NNNNN 3 10
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase and 932V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. ⋆  Quantity Required Equivalent Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. Cont. Cont.
    330 315 265 250 215 200 20G11TF265AN0NNNNN 1 8
    370 355 330 315 265 250 20G11TF330AN0NNNNN 1 8
    410 400 370 355 308 300 20G11TF370AN0NNNNN 1 8
    460 450 415 400 370 355 20G11TF415AN0NNNNN 1 8
    500 500 460 450 375 375 20G11TF460AN0NNNNN 1 8
    530 530 500 500 413 400 20G11TF500AN0NNNNN 1 8
    650 630 590 560 460 450 20G11TF265AN0NNNNN 2 9
    710 710 650 630 500 500 20G11TF330AN0NNNNN 2 9
    790 800 710 710 590 560 20G11TF370AN0NNNNN 2 9
    860 850 765 750 650 630 20G11TF415AN0NNNNN 2 9
    960 900 795 800 750 710 20G11TF460AN0NNNNN 2 9
    1020 1000 960 900 795 800 20G11TF500AN0NNNNN 2 9
    1150 1100 1040 1000 865 900 20G11TF370AN0NNNNN 3 10
    1485 1500 1400 1400 1160 1120 20G11TF500AN0NNNNN 3 10
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    PowerFlex 755 IP00 Option Kits
    Description Required? Frame 8 Frame 9 Frame 10
    Cat. No. Qty. Cat. No. Qty. Cat. No. Qty.
    Field Termination, Converter, AC Input Recommended 20-750-BUS2-F8 1 20-750-BUS2-F9 1 20-750-BUS2-F10 1
    Field Termination, Inverter, AC Output Recommended 20-750-BUS3-F8 1 20-750-BUS3-F9 1 20-750-BUS3-F10 1
    Field Termination, Inverter, DC Bus Recommended 20-750-BUS4-F8 1 20-750-BUS4-F9 1 20-750-BUS4-F10 1
    Field Termination, DC Input, Common Bus Precharge §  ♠  Recommended 20-750-BUS5-F8 1 20-750-BUS5-F9 1 20-750-BUS5-F10 1
    POD, Bucket Assembly Required 20-750-POD1-F8 1 20-750-POD1-F8 1 20-750-POD1-F8 1
    POD, Cable, 24 Volt Supply ♦  Required 20-750-PH1-F8 ∆  20-750-PH2-F9 1 20-750-PH3-F10 1
    Cable, Fiber Optic, 560 mm (22 in.) ♦  Required 20-750-FCBL1-F8 1 - - - -
    Cable, Fiber Optic, 2.8 m (110 in.) ♦  Required - - 20-750-FCBL1-F10 2 20-750-FCBL1-F10 3
    POD, Remote Mounting Kit Optional 20-750-RPD1-F8 1 20-750-RPD1-F9 1 20-750-RPD1-F10 1
    Mounting Kit, Back Panel Recommended 20-750-MNT2-F8 1 20-750-MNT2-F9 1 20-750-MNT2-F10 1
    Mounting Kit, Floor Recommended 20-750-MNT3-F8 1 20-750-MNT3-F9 1 20-750-MNT3-F10 1
    Duct, Top Outlet Recommended 20-750-DUCT2-F8 1 20-750-DUCT2-F8 2 20-750-DUCT2-F8 3
    Duct, Bottom Inlet Recommended 20-750-DUCT4-F8 1 20-750-DUCT4-F8 2 20-750-DUCT4-F8 3
    Roll-Out Cart Recommended 20-750-CART1-F8 1 20-750-CART1-F8 1 20-750-CART1-F8 1
    Control Power Circuit Breaker §  Recommended 1489-A2D130 1 1489-A2D130 2 1489-A2D130 3
    Control Power Circuit Breaker Lock §  Recommended 1489-AAL0A 1 1489-AAL0A 2 1489-AAL0A 3
    EMC Core, Converter Input, AC Input Optional 20-750-EMCBUS1-F8 1 20-750-EMCBUS1-F9 1 20-750-EMCBUS1-F10 1
    EMC Core, Inverter Output Optional 20-750-EMCCM1-F8 1 20-750-EMCCM1-F8 2 20-750-EMCCM1-F8 3
    § Common DC input drives only.
    ♠ EMC cores are included with the 20-750-BUS5-Fx kits.
    ∆ 24 volt supply cable is included with each Frame 8 drive unit.
    ♦ 20-750-PH1-Fx and 20-750-FBCL1-Fx kits are used if the Control Pod is mounted in the drive. If the Control Pod is to be remote mounted (up to 23 m or 75 ft away), order a 20-750-RPD1-Fx kit instead.

    Cabinet Options

    PowerFlex 755 2100 Transition Section ♣  ▶ 
    Description Cat. No. Frame
    Transition Section Cabinet, Gray 20-750-XSEC-LH-20G 8…10
    Transition Section Cabinet, Gray 20-750-XSEC-RH-20G 8…10
    Left Mount, Bus Bar, Bump Back, 1200 A ⋆  20-750-XBUS-LHBB-1200 8…10
    Left Mount, Bus Bar, Bump Back, 2000 A ⋆  20-750-XBUS-LHBB-2000 8…10
    Left Mount, Bus Bar, Bump Back, 3000 A ⋆  20-750-XBUS-LHBB-3000 8…10
    Left Mount, Bus Bar, Non-Bump Back, 1200 A ⋆  20-750-XBUS-LHNB-1200 8…10
    Left Mount, Bus Bar, Non-Bump Back, 2000 A ⋆  20-750-XBUS-LHNB-2000 8…10
    Left Mount, Bus Bar, Non-Bump Back, 3000 A ⋆  20-750-XBUS-LHNB-3000 8…10
    Right Mount, Bus Bar, Bump Back, 1200 A ‡  20-750-XBUS-RHBB-1200 8…10
    Right Mount, Bus Bar, Bump Back, 2000 A ‡  20-750-XBUS-RHBB-2000 8…10
    Right Mount, Bus Bar, Bump Back, 3000 A ‡  20-750-XBUS-RHBB-3000 8…10
    Right Mount, Bus Bar, Non-Bump Back, 1200 A ‡  20-750-XBUS-RHNB-1200 8…10
    Right Mount, Bus Bar, Non-Bump Back, 2000 A ‡  20-750-XBUS-RHNB-2000 8…10
    Right Mount, Bus Bar, Non-Bump Back, 3000 A ‡  20-750-XBUS-RHNB-3000 8…10
    ⋆ Left side of drive to right side of 2100 MCC.
    ‡ Right side of drive to left side of 2100 MCC.
    ▶ Requires the appropriate drive option P20, P22 or P24, which is dependent on the back bus ampacity.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    PowerFlex 755 Empty Option Bay ♣  § 
    Description Cat. No. Frame
    Option bay, 600 mm wide by 600 mm deep 20-750-PBAY-66 8…10
    Option bay, 800 mm wide by 600 mm deep 20-750-PBAY-86 8…10
    Option bay, 1000 mm wide by 600 mm deep 20-750-PBAY-106 8…10
    Option bay, 600 mm wide by 800 mm deep 20-750-PBAY-68 8…10
    Option bay, 800 mm wide by 800 mm deep 20-750-PBAY-88 8…10
    Option bay, 1000 mm wide by 800 mm deep 20-750-PBAY-108 8…10
    Side Bus Bar Connection-AC Line (left side of drive) 20-750-PBAY-LH-LINE 8…10
    Side Bus Bar Connection-DC Bus (left side of drive) 20-750-PBAY-LH-DCBUS 8…10
    Side Bus Bar Connection-AC Motor (left side of drive) 20-750-PBAY-LH-MOTOR 8…10
    Side Bus Bar Connection-AC Line (right side of drive) 20-750-PBAY-RH-LINE 8…10
    Side Bus Bar Connection-DC Bus (right side of drive) 20-750-PBAY-RH-DCBUS 8…10
    Side Bus Bar Connection-AC Motor (right side of drive) 20-750-PBAY-RH-MOTOR 8…10
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.
    § Not available with drive option P20, P22 or P24.

    Drive Options - AC Input (2500 MCC Style Cabinet)

    To configure a catalog number for a drive with options:

    1. Select the base drive catalog number from the tables that follow.
    2. Select the System Overload Duty Cycle and Power Disconnect options from the Required Options table. Add the desired option codes to the end of the base catalog number, separating each option code with a dash. For example: 21G1A‡ C460JN0NNNNN-LD-P3.
    3. Select other options from the Additional Options table. Add the option code(s) to the end of the catalog number separating each code with a dash. For example: 21G1A‡ C460JN0NNNNN-LD-P3-P11.

    Required Options
    Type Option Description
    System Overload Duty Cycle ∆ ♦  LD Light Duty 100% continuous current, 110% current for 1 minute.
    ND Normal Duty 100% continuous current, 110% current for 1 minute, 150% for 3 seconds.
    HD Heavy Duty 100% continuous current, 150% current for 1 minute, 200% for 3 seconds.
    Power Disconnect ∆  P3 Input Thermal Magnetic Circuit Breaker This option is for disconnecting drive power. An Allen-Bradley 140U Molded Case Circuit Breaker is provided. All switches include flange style handle operators that are door interlocking and padlockable.
    P5 Input Non-Fused Molded Case Disconnect Switch This option is for disconnecting drive power. An Allen-Bradley 140U Molded Case Switch is provided. All switches include flange style handle operators that are door interlocking and padlockable. Please note that PowerFlex 755 Frame 8 converter modules have input fuses installed as standard equipment.
    Wiring Only Bay P14 Wiring Only Bay This option identifies that an extra bay will be provided for the purpose of wiring the drive. This option will extend the drive power bus from the drive bay into the option bay, making field connection options more flexible. No drive input protection is supplied with this option. Documentation to reflect input disconnection and protection is customer supplied. See Power Wiring Options (Frame 8 Only) for more information on power cable entry/exit locations.
    ∆ Only one option of this type may be selected.
    ♦ See previous selection tables for specific rating information.

    Additional Options
    Type Option Description
    Contactors ∆  ♠  P11 ♣  Input Contactor A contactor is provided between the AC line and the drive. The contactor is controlled by customer supplied 120V AC (480V input) or 230V AC (400V input) remote contact closure logic. A terminal block for control is provided for customer use, and is wired to 1 N.O. and 1 N.C. auxiliary contact on the contactor.
    Important: The P11 option “Alternate Contact Circuit” is not intended to be used as a Start/Stop circuit.
    P12 ♣  Output Contactor A contactor is provided between the drive output and the motor. The contactor is controlled by customer supplied 120V AC (480V input) or 230V AC (400V input) remote contact closure logic. A terminal block for control is provided for customer use and is wired to 1 N.O. and 1 N.C. auxiliary contact on the contactor.
    Note: As an alternative to an output contactor, certain safety applications can be satisfied using the PowerFlex 750-Series Safe Torque-Off Option Card (Cat. No. 20-750-S). Safe Torque-Off is ideal for safety related applications requiring removal of rotational power to the motor without removing power from the drive. Safe Torque-Off functionality offers the benefit of quick start-up after a demand on the safety system and helps reduce wear from repetitive start-up. It also provides safety ratings up to and including SIL CL3, PLe, and CAT 3.
    Reactors ∆  L1 3% Input Reactor Provides an open core drive input line reactor that mounts inside the drive enclosure. Typical impedance is 3%.
    L2 3% Output Reactor Provides an open core drive output load reactor, which mounts inside the drive enclosure. Typical impedance is 3%.
    L3 ♣  5% Input Reactor Provides an open core drive input line reactor that mounts inside the drive enclosure. Typical impedance is 5%.
    L4 ♣  5% Output Reactor Provides an open core drive output load reactor, which mounts inside the drive enclosure. Typical impedance is 5%.
    MCC Power Bus Capacity ∆  P20 1250 Amp Bus Provides a 1250 Amp Bus.
    P22 2000 Amp Bus Provides a 2000 Amp Bus.
    P24 3000 Amp Bus Provides a 3000 Amp Bus.
    UPS Control Bus P30 UPS Control Bus, DC Input w/Precharge Provides a UPS Control Bus, DC Input w/Precharge only.
    ∆ Only one option of this type may be selected.
    ♠ Contactor options are not available for systems with MCC power bus.
    ♣ Frame 8 drives only.

    Drive Options - DC Input with Precharge (2500 MCC Style Cabinet)

    To configure a catalog number for a drive with options:

    1. Select the base drive catalog number from the tables that follow.
    2. Select the System Overload Duty Cycle and MCC Power Bus Capacity from the Required Options table below. Add the UPC Control Bus option (if needed) to the end of the base catalog number, separating it with a dash. For example: 21G14TF500AN0NNNNN-ND-P22-P30.

    Required Options
    Type Option Description
    System Overload Duty Cycle ∆ ♦  LD Light Duty 100% continuous current, 110% current for 1 minute.
    ND Normal Duty 100% continuous current, 110% current for 1 minute, 150% for 3 seconds.
    HD Heavy Duty 100% continuous current, 150% current for 1 minute, 200% for 3 seconds.
    MCC Power Bus Capacity ∆  P20 1250 Amp Bus Provides a 1250 Amp Bus.
    P22 2000 Amp Bus Provides a 2000 Amp Bus.
    P24 3000 Amp Bus Provides a 3000 Amp Bus.
    ∆ Only one option of this type may be selected.
    ♦ See previous selection tables for specific rating information.

    Additional Options
    Type Option Description
    UPS Control Bus P30 UPS Control Bus, DC Input w/Precharge Provides a UPS Control Bus, DC Input w/Precharge only.

    IP20, NEMA/UL Type 1 and Options (2500 MCC Style Cabinet)

    380…400V AC, Three-Phase and 540V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. ⋆  §  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    540 594 NA 315 460 506 693 250 385 578 693 200 21G1A‡ C460JN0NNNNN 8
    585 644 315 540 594 821 315 456 684 821 250 21G1A‡ C540JN0NNNNN 8
    612 673 355 567 624 851 315 472 708 851 250 21G1A‡ C567JN0NNNNN 8
    750 825 400 650 715 975 355 540 810 975 315 21G1A‡ C650JN0NNNNN 8
    796 876 450 750 825 1125 400 585 878 1125 315 21G1A‡ C750JN0NNNNN 8
    832 915 450 770 847 1155 400 642 963 1155 355 21G1A‡ C770JN0NNNNN 8
    1040 1144 560 910 1001 1365 500 750 1125 1365 400 21G11‡ C910JN0NNNNN 9
    1090 1199 630 1040 1144 1584 560 880 1320 1584 500 21G11‡ C1K0JN0NNNNN 9
    1175 1293 710 1090 1199 1638 630 910 1365 1638 500 21G11‡ C1K1JN0NNNNN 9
    1465 1612 800 1175 1293 1872 710 1040 1560 1962 560 21G11‡ C1K2JN0NNNNN 9
    1480 1628 850 1465 1612 2198 800 1090 1635 2198 630 21G11‡ C1K4JN0NNNNN 9
    1600 1760 900 1480 1628 2220 850 1175 1763 2220 710 21G11‡ C1K5JN0NNNNN 9
    1715 1887 1000 1590 1749 2385 900 1325 1988 2385 710 21G11‡ C1K6JN0NNNNN 10
    2330 2563 1400 2150 2365 3225 1250 1800 2700 3225 1000 21G11‡ C2K1JN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. "P" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep. "W" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    480V AC, Three-Phase and 650V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. §  Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    485 534 NA 400 430 473 666 350 370 555 666 300 21G1A‡ D430AN0NNNNN 8
    545 600 450 485 534 745 400 414 621 745 350 21G1A‡ D485AN0NNNNN 8
    590 649 500 545 600 818 450 454 681 818 350 21G1A‡ D545AN0NNNNN 8
    710 781 600 617 679 926 500 485 728 926 400 21G1A‡ D617AN0NNNNN 8
    765 842 650 710 781 1065 600 545 818 1065 450 21G1A‡ D710AN0NNNNN 8
    800 880 700 740 817 1110 650 617 926 1110 500 21G1A‡ D740AN0NNNNN 8
    960 1056 800 800 880 1278 700 710 1065 1278 600 21G11‡ D800AN0NNNNN 9
    1045 1150 900 960 1056 1440 800 795 1193 1440 700 21G11‡ D960AN0NNNNN 9
    1135 1249 1000 1045 1150 1568 900 800 1200 1568 750 21G11‡ D1K0AN0NNNNN 9
    1365 1502 1100 1135 1249 1728 1000 960 1440 1728 800 21G11‡ D1K2AN0NNNNN 9
    1420 1562 1250 1365 1502 2048 1100 1045 1568 2048 900 21G11‡ D1K3AN0NNNNN 9
    1540 1694 1350 1420 1562 2130 1250 1135 1703 2130 1000 21G11‡ D1K4AN0NNNNN 9
    1655 1821 1500 1525 1678 2288 1350 1270 1905 2288 1100 21G11‡ D1K5JN0NNNNN 10
    2240 2464 2000 2070 2277 3105 1750 1730 2595 3105 1650 21G11‡ D2K0JN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. "P" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep. "W" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    600V AC, Three-Phase and 810V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. §  Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    355 391 NA 350 295 325 490 300 272 408 490 250 21G1A‡ E295AN0NNNNN 8
    395 435 400 355 391 533 350 295 443 533 300 21G1A‡ E355AN0NNNNN 8
    435 479 450 395 435 593 400 329 494 593 350 21G1A‡ E395AN0NNNNN 8
    460 506 500 435 479 639 450 355 533 639 350 21G1A‡ E435AN0NNNNN 8
    510 561 500 460 506 711 500 395 593 711 400 21G1A‡ E460AN0NNNNN 8
    545 600 550 510 561 765 500 425 638 765 450 21G1A‡ E510AN0NNNNN 8
    690 759 700 595 655 918 600 510 765 918 500 21G11‡ E595AN0NNNNN 9
    760 836 800 630 693 1071 700 595 893 1071 600 21G11‡ E630AN0NNNNN 9
    835 919 900 760 836 1140 800 630 945 1140 700 21G11‡ E760AN0NNNNN 9
    900 990 950 825 908 1260 900 700 1050 1260 750 21G11‡ E825AN0NNNNN 9
    980 1078 1000 900 990 1368 950 760 1140 1368 800 21G11‡ E900AN0NNNNN 9
    1045 1150 1100 980 1078 1470 1000 815 1223 1470 900 21G11‡ E980AN0NNNNN 9
    1220 1342 1200 1110 1221 1665 1100 920 1380 1665 1000 21G11‡ E1K1AN0NNNNN 10
    1530 1683 1500 1430 1573 2145 1400 1190 1785 2145 1250 21G11‡ E1K4AN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. "P" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep. "W" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase and 932V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. ⋆  §  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    330 363 NA 315 265 292 375 250 215 323 375 200 21G1A‡ F265AN0NNNNN 8
    370 407 355 330 363 473 315 265 398 473 250 21G1A‡ F330AN0NNNNN 8
    410 451 400 370 407 555 355 308 462 555 300 21G1A‡ F370AN0NNNNN 8
    460 506 450 415 457 639 400 370 555 639 355 21G1A‡ F415AN0NNNNN 8
    500 550 500 460 506 675 450 375 563 675 375 21G1A‡ F460AN0NNNNN 8
    530 583 530 500 550 750 500 413 620 750 400 21G1A‡ F500AN0NNNNN 8
    650 715 630 590 649 885 560 460 690 885 450 21G11‡ F590AN0NNNNN 9
    710 781 710 650 715 975 630 500 750 975 500 21G11‡ F650AN0NNNNN 9
    790 869 800 710 781 1065 710 590 885 1065 560 21G11‡ F710AN0NNNNN 9
    860 946 850 765 842 1170 750 650 975 1170 630 21G11‡ F765AN0NNNNN 9
    960 1056 900 795 875 1350 800 750 1125 1350 710 21G11‡ F795AN0NNNNN 9
    1020 1122 1000 960 1056 1440 900 795 1193 1440 800 21G11‡ F960AN0NNNNN 9
    1150 1265 1100 1040 1144 1560 1000 865 1298 1560 900 21G11‡ F1K0AN0NNNNN 10
    1485 1634 1500 1400 1540 2100 1400 1160 1740 2100 1120 21G11‡ F1K4AN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "B" = IP20, NEMA/UL Type 1, MCC style 600 mm (23.6 in.) deep. "L" = IP20, NEMA/UL Type 1, MCC style 800 mm (31.5 in.) deep. "P" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep. "W" = Packaged Drive - IP20, NEMA/UL Type 1, MCC style w/MCC bus, 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    IP54, NEMA Type 12 and Options (2500 MCC Style Cabinet)

    380…400V AC, Three-Phase and 540V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. ⋆  §  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    540 594 NA 315 460 506 693 250 385 578 693 200 21G1A‡ C460JN0NNNNN 8
    585 644 315 540 594 821 315 456 684 821 250 21G1A‡ C540JN0NNNNN 8
    612 673 355 567 624 851 315 472 708 851 250 21G1A‡ C567JN0NNNNN 8
    750 825 400 650 715 975 355 540 810 975 315 21G1A‡ C650JN0NNNNN 8
    796 876 450 750 825 1125 400 585 878 1125 315 21G1A‡ C750JN0NNNNN 8
    832 915 450 770 847 1155 400 642 963 1155 355 21G1A‡ C770JN0NNNNN 8
    1040 1144 560 910 1001 1365 500 750 1125 1365 400 21G11‡ C910JN0NNNNN 9
    1090 1199 630 1040 1144 1584 560 880 1320 1584 500 21G11‡ C1K0JN0NNNNN 9
    1175 1293 710 1090 1199 1638 630 910 1365 1638 500 21G11‡ C1K1JN0NNNNN 9
    1465 1612 800 1175 1293 1872 710 1040 1560 1962 560 21G11‡ C1K2JN0NNNNN 9
    1480 1628 850 1465 1612 2198 800 1090 1635 2198 630 21G11‡ C1K4JN0NNNNN 9
    1600 1760 900 1480 1628 2220 850 1175 1763 2220 710 21G11‡ C1K5JN0NNNNN 9
    1715 1887 1000 1590 1749 2385 900 1325 1988 2385 710 21G11‡ C1K6JN0NNNNN 10
    2330 2563 1400 2150 2365 3225 1250 1800 2700 3225 1000 21G11‡ C2K1JN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "K" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, standard color. "Y" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    480V AC, Three-Phase and 650V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. §  Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    485 534 NA 400 430 473 666 350 370 555 666 300 21G1A‡ D430AN0NNNNN 8
    545 600 450 485 534 745 400 414 621 745 350 21G1A‡ D485AN0NNNNN 8
    590 649 500 545 600 818 450 454 681 818 350 21G1A‡ D545AN0NNNNN 8
    710 781 600 617 679 926 500 485 728 926 400 21G1A‡ D617AN0NNNNN 8
    765 842 650 710 781 1065 600 545 818 1065 450 21G1A‡ D710AN0NNNNN 8
    800 880 700 740 817 1110 650 617 926 1110 500 21G1A‡ D740AN0NNNNN 8
    960 1056 800 800 880 1278 700 710 1065 1278 600 21G11‡ D800AN0NNNNN 9
    1045 1150 900 960 1056 1440 800 795 1193 1440 700 21G11‡ D960AN0NNNNN 9
    1135 1249 1000 1045 1150 1568 900 800 1200 1568 750 21G11‡ D1K0AN0NNNNN 9
    1365 1502 1100 1135 1249 1728 1000 960 1440 1728 800 21G11‡ D1K2AN0NNNNN 9
    1420 1562 1250 1365 1502 2048 1100 1045 1568 2048 900 21G11‡ D1K3AN0NNNNN 9
    1540 1694 1350 1420 1562 2130 1250 1135 1703 2130 1000 21G11‡ D1K4AN0NNNNN 9
    1655 1821 1500 1525 1678 2288 1350 1270 1905 2288 1100 21G11‡ D1K5JN0NNNNN 10 ♣ 
    2240 2464 2000 2070 2277 3105 1750 1730 2595 3105 1650 21G11‡ D2K0JN0NNNNN 10 ♣ 
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "K" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, standard color. "Y" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    600V AC, Three-Phase and 810V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. §  Frame Size
    Output Amps Hp Output Amps Hp Output Amps Hp
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    355 391 NA 350 295 325 490 300 272 408 490 250 21G1A‡ E295AN0NNNNN 8
    395 435 400 355 391 533 350 295 443 533 300 21G1A‡ E355AN0NNNNN 8
    435 479 450 395 435 593 400 329 494 593 350 21G1A‡ E395AN0NNNNN 8
    460 506 500 435 479 639 450 355 533 639 350 21G1A‡ E435AN0NNNNN 8
    510 561 500 460 506 711 500 395 593 711 400 21G1A‡ E460AN0NNNNN 8
    545 600 550 510 561 765 500 425 638 765 450 21G1A‡ E510AN0NNNNN 8
    690 759 700 595 655 918 600 510 765 918 500 21G11‡ E595AN0NNNNN 9
    760 836 800 630 693 1071 700 595 893 1071 600 21G11‡ E630AN0NNNNN 9
    835 919 900 760 836 1140 800 630 945 1140 700 21G11‡ E760AN0NNNNN 9
    900 990 950 825 908 1260 900 700 1050 1260 750 21G11‡ E825AN0NNNNN 9
    980 1078 1000 900 990 1368 950 760 1140 1368 800 21G11‡ E900AN0NNNNN 9
    1045 1150 1100 980 1078 1470 1000 815 1223 1470 900 21G11‡ E980AN0NNNNN 9
    1220 1342 1200 1110 1221 1665 1100 920 1380 1665 1000 21G11‡ E1K1AN0NNNNN 10
    1530 1683 1500 1430 1573 2145 1400 1190 1785 2145 1250 21G11‡ E1K4AN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "K" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, standard color. "Y" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    690V AC, Three-Phase and 932V DC Input Drives ♣  ▶ 
    Light Duty (-LD) Normal Duty (-ND) Heavy Duty (-HD) Base Drive Cat. No. ⋆  §  Frame Size
    Output Amps kW Output Amps kW Output Amps kW
    Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
    330 363 NA 315 265 292 375 250 215 323 375 200 21G1A‡ F265AN0NNNNN 8
    370 407 355 330 363 473 315 265 398 473 250 21G1A‡ F330AN0NNNNN 8
    410 451 400 370 407 555 355 308 462 555 300 21G1A‡ F370AN0NNNNN 8
    460 506 450 415 457 639 400 370 555 639 355 21G1A‡ F415AN0NNNNN 8
    500 550 500 460 506 675 450 375 563 675 375 21G1A‡ F460AN0NNNNN 8
    530 583 530 500 550 750 500 413 620 750 400 21G1A‡ F500AN0NNNNN 8
    650 715 630 590 649 885 560 460 690 885 450 21G11‡ F590AN0NNNNN 9
    710 781 710 650 715 975 630 500 750 975 500 21G11‡ F650AN0NNNNN 9
    790 869 800 710 781 1065 710 590 885 1065 560 21G11‡ F710AN0NNNNN 9
    860 946 850 765 842 1170 750 650 975 1170 630 21G11‡ F765AN0NNNNN 9
    960 1056 900 795 875 1350 800 750 1125 1350 710 21G11‡ F795AN0NNNNN 9
    1020 1122 1000 960 1056 1440 900 795 1193 1440 800 21G11‡ F960AN0NNNNN 9
    1150 1265 1100 1040 1144 1560 1000 865 1298 1560 900 21G11‡ F1K0AN0NNNNN 10
    1485 1634 1500 1400 1540 2100 1400 1160 1740 2100 1120 21G11‡ F1K4AN0NNNNN 10
    § The 5th character determines Input Type. "1" = AC & DC input w/precharge. "4" = DC input w/precharge. "A" = AC input w/precharge & no DC terminals.
    ‡ The 6th character determines Enclosure Type & Depth. "K" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, standard color. "Y" = IP54, NEMA Type 12, MCC style 800 mm (31.5 in.) deep, gray. Refer to the Power Wiring Options table.
    ⋆ The 11th character determines default Filtering and Common Mode Cap jumper configuration. "J" = Installed, "A" = Removed.
    ▶ A Roll-out Cart is required with Frame 8…10 drives to assist with power wiring and cabinet mounting. Refer to .
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    Human Interface Modules
                 
    Click to enlarge - 20him_blank Click to enlarge - 20him_a3 Click to enlarge - 20him_a5 Click to enlarge - 20him_a6 Click to enlarge - 20him_c3s Click to enlarge - 20him_c5s Click to enlarge - 20him_c6s
    Blank Plate 20-HIM-A3 20-HIM-A5 20-HIM-A6 20-HIM-C3S 20-HIM-C5S 20-HIM-C6S

    Human Interface Modules
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    No HIM (Blank Plate), Handheld/Local (Drive Mount) 20-HIM-A0 ü ü ü ü ü ü
    LCD Display, Full Numeric Keypad, Handheld/Local (Drive Mount) 20-HIM-A3 ü ü ü ü ü  
    LCD Display, Programmer Only, Handheld/Local (Drive Mount) 20-HIM-A5 ü ü ü ü ü  
    Enhanced, LCD, Full Numeric Keypad, Handheld/Local (Drive Mount) 20-HIM-A6 ü ü ü ü ü ü § 
    Remote (Panel Mount) LCD Display, Full Numeric Keypad ⋆ ‡  20-HIM-C3S ü ü ü ü ü  
    Remote (Panel Mount) LCD Display, Programmer Only ⋆ ‡  20-HIM-C5S ü ü ü ü ü  
    Enhanced, LCD, Full Numeric Keypad ⋆ ‡  20-HIM-C6S ü ü ü ü ü ü ♦ 
    ⋆ IP66, NEMA Type 4X/12 - For indoor use only.
    ‡ Includes a 1202-C30 interface cable (3 meters) for connection to drive.
    § Select for Frames 2…5 IP54, NEMA/UL Type 12 drives.
    ♦ Select for Frames 6…7 IP54, NEMA/UL Type 12 drives.

    Human Interface Module Accessories
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Bezel Kit for LCD HIMs, NEMA Type 1 ‡  20-HIM-B1 ü ü ü ü ü ü
    PowerFlex HIM Interface Cable, 1 m (39 in) ♣  20-HIM-H10 ü ü ü ü ü ü
    Comm Option Cable Kit (Male-Male)              
    0.33 Meters (1.1 Feet) 1202-C03 ü ü ü ü ü ü
    1 Meter (3.3 Feet) 1202-C10 ü ü ü ü ü ü
    3 Meter (9.8 Feet) 1202-C30 ü ü ü ü ü ü
    9 Meter (29.5 Feet) 1202-C90 ü ü ü ü ü ü
    Cable Kit (Male-Female) ∆               
    0.33 Meters (1.1 Feet) 1202-H03 ü ü ü ü ü ü
    1 Meter (3.3 Feet) 1202-H10 ü ü ü ü ü ü
    3 Meter (9.8 Feet) 1202-H30 ü ü ü ü ü ü
    9 Meter (29.5 Feet) 1202-H90 ü ü ü ü ü ü
    DPI™ Cable Kit with Connectors, Tools and 100 m (328 ft) Cable 1202-CBL-KIT-100M ü ü ü ü ü ü
    DPI Cable Connector Kit 1202-TB-KIT-SET ü ü ü ü ü ü
    DPI/SCANport™ One to Two Port Splitter Cable 1203-S03 ü ü ü ü ü ü
    ‡ Includes a 1202-C30 interface cable (3 meters) for connection to drive.
    ♣ Required only when HIM is used as handheld or remote.
    ∆ Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 Meters (32.8 Feet).

    Communication Option Kits
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    BACnet/IP Option Module 20-750-BNETIP           ü
    BACnet® MS/TP RS485 Communication Adapter 20-COMM-B ü ü ü      
    Coaxial ControlNet™ Option Module 20-750-CNETC           ü
    ControlNet™ Communication Adapter (Coax) 20-COMM-C ü ü ü ü ü ü § 
    ControlNet™ Communication Adapter (Coax) Conformal Coat 20-COMM-C-MX3 ü ü ü ü ü ü § 
    DeviceNet™ Option Module 20-750-DNET           ü
    DeviceNet™ Communication Adapter 20-COMM-D ü ü ü ü ü ü § 
    DeviceNet™ Communication Adapter Conformal Coat 20-COMM-D-MX3 ü ü ü ü ü ü § 
    Dual-port EtherNet/IP Option Module 20-750-ENETR           ü
    EtherNet/IP™ Communication Adapter 20-COMM-E ü ü ü ü ü ü § 
    EtherNet/IP™ Communication Adapter Conformal Coat 20-COMM-E-MX3 ü ü ü ü ü ü § 
    HVAC Communication Adapter 20-COMM-H ü ü ü ü ♠  ü ü § 
    CANopen® Communication Adapter 20-COMM-K ü ü ü ü ü ü § 
    LonWorks® Communication Adapter 20-COMM-L ü ü ü     ü § 
    Modbus/TCP Communication Adapter 20-COMM-M ü ü ü ü ü ü § 
    Profibus DPV1 Option Module 20-750-PBUS           ü
    Single-port Profinet IO Option Module 20-750-PNET           ü ♣ 
    Dual-port Profinet IO Option Module 20-750-PNET2P           ü ♣ 
    PROFIBUS™ DP Communication Adapter 20-COMM-P ü ü ü ü ü ü § 
    ControlNet™ Communication Adapter (Fiber) 20-COMM-Q ü ü ü ü ü ü § & 
    Remote I/O Communication Adapter ∆  20-COMM-R ü ü ü ü ü ü § 
    Remote I/O Communication Adapter Conformal Coat ∆  20-COMM-R-MX3 ü ü ü ü ü ü § 
    RS485 DF1 Communication Adapter 20-COMM-S ü ü ü ü ü ü § 
    RS485 DF1 Communication Adapter Conformal Coat 20-COMM-S-MX3 ü ü ü ü ü ü § 
    External Communications Kit Power Supply 20-XCOMM-AC-PS1 ü ü ü ü ü ü
    DPI External Communications Kit 20-XCOMM-DC-BASE ü ü ü ü ü ü
    External DPI I/O Option Board ♦  20-XCOMM-IO-OPT1 ü ü ü ü ü ü
    PowerFlex Compact I/O to DPI/SCANport Module 1769-SM1 ü ü ü ü ü ü
    DriveLogix ControlNet Communication Adapter (Coax) ‡  1788-CNC       ü ü ▶   
    DriveLogix Comm Option, ControlNet Redundant (Coax) ‡  1788-CNCR       ü ü ▶   
    DriveLogix Comm Option, ControlNet (Fiber) ‡  1788-CNF       ü ü ▶   
    DriveLogix Comm Option, ControlNet Redundant (Fiber) ‡  1788-CNFR       ü ü ▶   
    DriveLogix Comm Option, DeviceNet (Open Conn.) ‡  1788-DNBO       ü ü ▶   
    DriveLogix Comm Option, EtherNet/IP (Twisted Pair) ‡  1788-ENBT       ü ü ▶   
    DriveLogix5730 Comm Option, Embedded EtherNet/IP 20D-DL2-ENET0       ü ü ▶   
    ♦ For use only with DPI External Communications Kits 20-XCOMM-DC-BASE.
    ♠ Only Modbus RTU can be used.
    ‡ For use with DriveLogix option only. Requires Logix Expansion Board (20D-DL2-LEB0).
    § Requires a Communication Carrier Card (20-750-20COMM or 20-750-20COMM-F1). Refer to PowerFlex 750-Series Legacy Communication Compatibility for compatibility details.
    ▶ When using a PowerFlex 700S control.
    ∆ This item has Silver Series status. For information, refer to http://www.ab.com/silver.
    & Not supported in Frame 1.
    ♣ Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

    Communication Accessories
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Serial Null Modem Adapter 1203-SNM ü ü ü ü ü ü
    Smart Self-powered Serial Converter (RS232) includes 1203-SFC and 1202-C10 Cables 1203-SSS ü ü ü ü ü ü
    Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables 1203-USB ü ü ü ü ü ü
    ControlNet T-tap right angle 1786-TPR       ü ü ü
    Communication Carrier Card for PowerFlex 750-Series Frame 1 drives 20-750-20COMM-F1           ü
    Communication Carrier Card for PowerFlex 750-Series Frame 2 or higher drives 20-750-20COMM           ü
      

    PowerFlex 750-Series Legacy Communication Compatibility

    Most legacy communication adapters (20-COMM) can be used with the PowerFlex 753/755. However, the restrictions stated below do apply.

    Frame 1 - It is recommended that the 20-750-20COMM-F1 Communication Carrier Card only be installed in Port 4. Port 5 will not be accessible when this module is installed.

    Frames 2 and larger - It is recommended that the 20-750-20COMM Communication Carrier Card be installed in Port 6. Using Port 4 or 5 will make the adjacent left port inaccessible to other option modules and may interfere with network cable connections.


    Adapter Accesses Ports 2, 3 and 6
    for I/O Connections
    (Implicit & Explicit Messaging)
    Accesses Port 7…14 Devices Supports Drive Add On Profiles Supports Asian-Languages ♦ 
    20-COMM-B Not Compatible
    20-COMM-C ü‡  ü v3.001 ♣  ü ∆  ü v3.001 ♣ 
    20-COMM-D Not Compatible
    20-COMM-E ü v4.001 ♣  ü ∆  ü v4.001 ♣ 
    20-COMM-H ü v2.009 §  Not Compatible
    20-COMM-K ü v1.001 ♣ 
    20-COMM-L ü v1.007 ♣ 
    20-COMM-M ü‡  ü v2.001 ♣  Not Compatible ü v2.001 ♣ 
    20-COMM-Q ü‡  ü v3.001 ♣  ü ∆  ü v3.001 ♣ 
    20-COMM-R Not Compatible
    20-COMM-S
    ‡ Controller must be capable of reading/writing 32-bit floating point (REAL) values.
    § Supports all three modes of operation (RTU, P1, N2).
    ♣ Requires this adapter firmware version or higher.
    ∆ Requires firmware version v1.05 or higher of the drive Add On Profiles for RSLogix 5000 version v16 or higher.
    ♦ Chinese, Japanese, and Korean languages are supported at the time of publication.

    Feedback Options
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    5V/12V Encoder &  20A-ENC-1 ü          
    12V/5V Encoder 20B-ENC-1   ü     ü  
    12V/5V Encoder with Conformal Coat 20B-ENC-1-MX3   ü        
    Multi-Device Interface ♦  20D-MDI-C2       ü ü ▶   
    2nd Encoder, 5V/12V ♦  20D-P2-ENC0       ü ü ▶   
    Resolver ♦  20D-RES-A1       ü ü ▶   
    Stegmann High Resolution Hyperface Encoder ♦  20D-STEG-B1       ü ü ▶   
    Heidenhain High Resolution EnDat Encoder 20D-HEID-D0       ü ü ▶   
    Incremental Encoder 20-750-ENC-1           ü ♠ 
    Dual Incremental Encoder 20-750-DENC-1           ü ♠ 
    Universal Feedback (includes Stegmann, Heidenhain, SSI, Biss, 5V Incremental) 20-750-UFB-1           ü ⋆ 
    & Works only with PowerFlex 70 Enhanced Control.
    ♦ Requires Expanded Cassette
    # When using a PowerFlex 700 with Vector Control.
    ⋆ PowerFlex 755 only.
    ▶ When using a PowerFlex 700S control.
    ♠ Homing and registration functions are not supported when using this device with RSLogix 5000 embedded motion instructions. To use these functions, the Universal Feedback Board (20-750-UFB-1) must be used.

    I/O Option Kits
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    24V DC Digital Inputs (6) w/Analog I/O (4), Slot A ♠  20C-DA1-A     ü      
    115V AC Digital Inputs (6) w/Analog I/O (4), Slot A ♠  20C-DA1-B     ü      
    115V AC Digital Outputs (3), Slot B ♠  20C-DO1     ü      
    24V DC I/O with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs 20-750-2262C-2R           ü § 
    115V AC I/O with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs 20-750-2262D-2R           ü § 
    24V DC I/O with 2 Analog In, 2 Analog Out, 6 Digital In, 3 Digital Out, 1 Relay & 2 Transistor Outputs 20-750-2263C-1R2T           ü § 
    ♠ Only one card allowed per slot.
    § I/O option kits are not allowed in CIP motion mode.

    Safety Options
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    DriveGuard Safe Torque-Off 20A-DG01 ü          
    DriveGuard Safe Torque-Off w/2nd Encoder 20D-P2-DG01       ü ü ▶   
    Safe Torque-Off (ATEX capable) ♠  20C-DG1     ü      
    Safe Torque-Off 20-750-S           ü ⋆ 
    Safe Speed Monitor 20-750-S1           ü ⋆ ‡ 
    ♠ Only one card allowed per slot.
    ▶ When using PowerFlex 700S control. This option kit cannot be used on Frame 2 drives, however it is available as a factory installed option.
    ‡ Requires the Dual Incremental Encoder or Universal Feedback Option. Also requires the 20-750-EMCSSM1-F8 EMC Option Kit with Frame 8…9 drives.
    ⋆ Drive can accomodate only one option.

    PowerFlex 700 Control Option Kits
    Control with I/O Factory Installed
    Cat. Code # 
    Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Vector Control - 24V DC with: ▶ 
    60 Hz Maximum NNAD 20B-VECT-C0AD   ü        
    82 Hz Maximum NNAX 20B-VECTB-C0AX   ü        
    Cascading Fan/Pump Control NNAE 20B-VECT-C0AE   ü        
    Pump Off (for Pump Jack) NNBA 20B-VECTB-C0BA   ü        
    Vector Control - 24V DC, Conformal Coat ▶  20B-VECTB-C0-MX3   ü        
    Vector Control - 115V AC ▶  D &  20B-VECTB-D0   ü        
    Vector Control - 115V AC with: ▶ 
    60 Hz Maximum NNAD 20B-VECT-D0AD   ü        
    82 Hz Maximum NNAX 20B-VECTB-D0AX   ü        
    Cascading Fan/Pump Control NNAE 20B-VECT-D0AE   ü        
    Pump Off (for Pump Jack) NNBA 20B-VECT-D0BA   ü        
    Vector Control - 115V AC, Conformal Coat ▶  20B-VECTB-D0-MX3   ü        
    ▶ Vector Control option utilizes DPI Only.
    # This code is entered at the end of the drive catalog number (positions 17…20).
    & This code is entered at position 15 of the drive catalog number.

    PowerFlex 750-Series Option Kits
    Description Frame Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Auxiliary Power Supply 24V Aux Power Supply 2…7 ∆  20-750-APS           ü
    DC Bus Bar Option Kit DC Bus Bars, 380…480V AC drives 6 20-750-DCBB1-F6           ü
    7 20-750-DCBB1-F7           ü
    DC Bus Connection Kit Allows connection of the drive DC bus terminals to the bus rails at the back of the cabinet. 8…10 20-750-BUS1-F8           ü
    EMC Option Kit EMC Plate with Core 1 20-750-EMC1-F1           ü
    2 20-750-EMC1-F2           ü
    3 20-750-EMC1-F3           ü
    EMC Plate with Cores 4 20-750-EMC1-F4           ü
    5 20-750-EMC1-F5           ü
    EMC Core 1 20-750-EMC2-F1           ü
    2 20-750-EMC2-F2           ü
    3 20-750-EMC2-F3           ü
    EMC Cores 4…5 20-750-EMC2-F45           ü
    EMC Core – Inverter-mounted output, for AC Input and DC Input drives. 8…10 20-750-EMCCM1-F8           ü
    EMC Core – Cabinet-mounted input, for Common DC Input drives only. 8…10 20-750-CBPEMCCM1-F8           ü
    EMC Core – Cabinet-mounted input, for AC Input drives only. 8…10 20-750-EMCCM1-F9           ü
    EMC Cores – Required when using the Safe Speed Monitor option 20-750-S1. 8…10 20-750-EMCSSM1-F8           ü
    Door Shielding Kit 8…10 20-750-EMCDK1-F10           ü
    Flange Adapter Kit Converts Open Type drive to external heatsink (flange) with NEMA/UL Type 1 integrity backside. §  2 20-750-FLNG1-F2           ü
    3 20-750-FLNG1-F3           ü
    4 20-750-FLNG1-F4           ü
    5 20-750-FLNG1-F5           ü
    Converts Open Type drive to external heatsink (flange) with NEMA/UL Type 4X/12 integrity backside. 6 20-750-FLNG4-F6           ü
    7 20-750-FLNG4-F7           ü
    L Bus Bar Kit Includes three L-brackets 8…10 20-750-LBRKT1           ü
    NEMA/UL Type 1 Option Kit NEMA/UL Type 1 Kit 1 20-750-NEMA1-F1           ü
    2 20-750-NEMA1-F2           ü
    3 20-750-NEMA1-F3           ü
    4 20-750-NEMA1-F4           ü
    5 20-750-NEMA1-F5           ü
    6 20-750-NEMA1-F6           ü
    7 20-750-NEMA1-F7           ü
    Power Terminal Extension Allows connection of two parallel leads to the AC power terminals. 6 20-750-ACTE1-F6           ü
    Power Terminal Guard Provides additional ingress protection on power terminals. 6 20-750-PTG1-F6           ü
    7 20-750-PTG1-F7           ü
    Remote Control POD Mounting Kit Mounting hardware with 25 m (75 ft) fiber optic and 24V control cables for mounting the control POD in a cabinet that is separate from the drive. 8…10 20-750-RPD1-F8           ü
    Roll-Out Cart ♣  Provides a means to move the power core and allow access to the power terminals. 8…10 20-750-CART1-F8           ü
    ∆ Frame 8 and up drives can be powered from an external 24V DC source, a 20-750-APS is not required.
    § This kit is for use with IP20, NEMA/UL Type 0 drives and will not provide an air-tight or water-tight seal. Where sealing is required (e.g. contaminated, dirty or wet environments), a drive with an “F” enclosure option must be used.
    ♣ Required for Frame 8 and up drives to assist with power wiring.

    Other Options
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    115V AC Interface AK-M9-115VAC-1 ü          
    Frame E Flange Gasket AK-M9-GASKET1-E4 ü          
    Service Connection Board ⋆  SK-M9-SCB1 ü          
    Removable I/O Terminal Block SK-G9-TB1-S1   ü        
    Removable Encoder Terminal Block SK-G9-TB1-ENC1   ü        
    Touch Cover - Converts IP00/Open Type drive to IP20/NEMA/UL Type 1. No wiring space provided. 20-OPT-TC     ü      
    Top Hat - Converts IP00/Open Type drive to IP20/NEMA/UL Type 1. Allows for wiring space. 20-OPT-TH     ü      
    Auxiliary Control Power Supply 20-24V-AUX1       ü    
    PowerFlex 700S Phase II Control with Expanded Cassette 20D-P2-CKE1       ü ü ▶   
    PowerFlex 700S Phase II Control with Slim Cassette 20D-P2-CKS1       ü    
    PowerFlex 700S DriveLogix5730 Phase II Control with Expanded Cassette 20D-DL2-CKE1       ü ü ▶   
    PowerFlex 700S DriveLogix5730 Phase II Control with Slim Cassette 20D-DL2-CKS1       ü    
    ⋆ Provides temporary DPI/HIM connection for NEMA/UL Type 1 and Flange drives with cover removed.
    ▶ When using PowerFlex 700S control and Expanded Cassette.

    SynchLink Accessories
    Description ⋆  Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    SynchLink Board 20D-P2-SLB0       ü ü ▶   
    SynchLink Fiber Base Block 1751-SLBA       ü ü ▶   
    SynchLink 4-port Fiber Splitter Block 1751-SL4SP       ü ü ▶   
    SynchLink Fiber Bypass Switch Block 1751-SLBP       ü ü ▶   
    2x3 Meter Fiber Link for Power Monitor/SynchLink 1403-CF003       ü ü ▶   
    2x5 Meter Fiber Link for Power Monitor/SynchLink 1403-CF005       ü ü ▶   
    10 Meter Fiber Link for Power Monitor/SynchLink 1403-CF010       ü ü ▶   
    ⋆ Refer to publication number 1769-SG001 for details on SynchLink.
    ▶ When using PowerFlex 700S control.

    DriveLogix Option Kits
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Logix Expansion board for DriveLogix5730 ♦  20D-DL2-LEB0       ü ü ▶   
    Industrial Compact Flash 64 MB Memory Card for DriveLogix5730 1784-CF64       ü ü ▶   
    ♦ Requires Expanded Cassette.
    ▶ When using PowerFlex 700S control.

    DriveLogix I/O Cables
    Description Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    DriveLogix5730 - Compact I/O cable, 3.28 ft. (1 meter), Left Bus Cap♦ ♣  20D-DL2-CL3       ü ü ▶   
    DriveLogix5730 - Compact I/O cable, 3.28 ft. (1 meter), Right Bus Cap ♦ ♣  20D-DL2-CR3       ü ü ▶   
    Logix5000 RS-232 Programming Cable 1756-CP3       ü ü ▶   
    ♦ Requires Expanded Cassette.
    ♣ Refer to Publication 1769-SG001 for details and selection of Compact I/O.
    ▶ When using PowerFlex 700S control.

    PowerFlex 70 Small Duty Internal Dynamic Brake Resistors

    Limited duty resistors mount directly to the back surface of the drive and require no extra panel space. Internal resistors are non-destructive and do not require a resistor overheat external safety circuit.

    PowerFlex 70 AC Drive Small Duty Internal DB Resistor
    Normal Duty⋆ 
    kW (Hp)
    Heavy Duty⋆ 
    kW (Hp)
    Min DB Res
    Ohms ±10%
    Cat. No. Resistance‡ 
    Ohms ±5%
    Continuous Power
    kW
    Max Energy
    kJ
    Max Braking Torque
    % of ND Motor
    Application Type 1 Application Type 2
    Braking Torque
    % of ND Motor
    Duty Cycle Braking Torque
    % of ND Motor
    Duty Cycle
    200…240 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 33 20AB-DB1-A 62 0.048 8.3 307% 100% 25.9% 150% 17.3%
    0.75 (1.0) 0.55 (0.75) 33 20AB-DB1-A 62 0.048 7.3 300% 100% 12.8% 150% 8.5%
    1.5 (2.0) 1.1 (1.5) 33 20AB-DB1-B 62 0.028 0.8 160% 100% 3.7% 150% 2.5%
    2.2 (3.0) 1.5 (2.0) 33 20AB-DB1-B 62 0.028 0.8 109% 100% 2.5% 109% 2.3%
    4.0 (5.0) 3.0 (3.0) 30 20AB-DB1-C 62 0.040 0.8 60% 60% 3.3% N/A N/A
    5.5 (7.5) 4.0 (5.0) 21 20AB-DB1-D 22 0.036 0.9 117% 100% 1.3% 117% 1.1%
    7.5 (10) 5.5 (7.5) 21 20AB-DB1-D 22 0.036 0.9 86% 86% 1.1% N/A N/A
    400…480 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 68 20AD-DB1-A 115 0.048 8.3 320% 100% 25.9% 150% 17.3%
    0.75 (1.0) 0.55 (0.75) 68 20AD-DB1-A 115 0.048 9.0 259% 100% 12.8% 150% 8.5%
    1.5 (2.0) 1.1 (1.5) 68 20AD-DB1-A 115 0.048 2.4 243% 100% 6.4% 150% 4.3%
    2.2 (3.0) 1.5 (2.0) 68 20AD-DB1-B 115 0.028 0.9 206% 100% 2.5% 150% 1.7%
    4.0 (5.0) 3.0 (3.0) 68 20AD-DB1-B 115 0.028 0.9 129% 100% 1.4% 129% 1.1%
    5.5 (7.5) 4.0 (5.0) 74 20AD-DB1-C 115 0.04 0.9 94% 94% 1.5% N/A N/A
    7.5 (10) 5.5 (7.5) 74 20AD-DB1-C 115 0.04 0.9 69% 69% 1.5% N/A N/A
    11 (15) 7.5 (10) 44 20AD-DB1-D 62 0.036 0.8 87% 87% 0.8% N/A N/A
    15 (20) 11 (15) 31 20AD-DB1-D 62 0.036 0.8 64% 64% 0.8% N/A N/A
    500…600 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 117 20AD-DB1-A 115 0.048 8.3 287% 100% 25.9% 150% 17.3%
    0.75 (1.0) 0.55 (0.75) 117 20AD-DB1-A 115 0.048 9.0 263% 100% 12.8% 150% 8.5%
    1.5 (2.0) 1.1 (1.5) 117 20AD-DB1-A 115 0.048 2.4 243% 100% 6.4% 150% 4.3%
    2.2 (3.0) 1.5 (2.0) 117 20AD-DB1-B 115 0.028 0.9 202% 100% 2.5% 150% 1.7%
    4.0 (5.0) 3.0 (3.0) 80 20AD-DB1-B 115 0.028 0.9 193% 100% 1.4% 150% 0.9%
    5.5 (7.5) 4.0 (5.0) 80 20AD-DB1-C 115 0.04 0.9 147% 100% 1.5% 147% 1.0%
    7.5 (10) 5.5 (7.5) 80 20AD-DB1-C 115 0.04 0.9 108% 100% 1.1% 108% 1.0%
    11 (15) 7.5 (10) 48 N/A N/A N/A N/A N/A N/A N/A N/A N/A
    15 (20) 11 (15) 48 N/A N/A N/A N/A N/A N/A N/A N/A N/A
    ⋆ Duty cycle listed is based on full speed to zero speed deceleration. For constant regen at full speed, duty cycle capability is half of what is listed. Application Type 1 represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
    ‡ Always check resistor Ohms against minimum resistance for drive being used.

    PowerFlex 70 Medium Duty External Dynamic Brake Resistors

    These resistors provide a larger duty cycle capability than the internal type. Includes an internal thermal switch for use in external safety circuit.

    PowerFlex 70 AC Drive Medium Duty External DB Resistor
    Normal Duty⋆ 
    kW (Hp)
    Heavy Duty⋆ 
    kW (Hp)
    Min DB Res
    Ohms ±10%
    Cat. No. Resistance‡ 
    Ohms ±5%
    Continuous Power
    kW
    Max Energy
    kJ
    Max Braking Torque
    % of ND Motor
    Application Type 1 Application Type 2
    Braking Torque
    % of ND Motor
    Duty Cycle Braking Torque
    % of ND Motor
    Duty Cycle
    200…240 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 33 AK-R2-091P500 91 0.086 17 293% 100% 46% 150% 31%
    0.75 (1.0) 0.55 (0.75) 33 AK-R2-091P500 91 0.086 17 218% 100% 23% 150% 15%
    1.5 (2.0) 1.1 (1.5) 33 AK-R2-091P500 91 0.086 17 109% 100% 11% 109% 11%
    2.2 (3.0) 1.5 (2.0) 33 AK-R2-047P500 47 0.166 33 144% 100% 15% 144% 11%
    4.0 (5.0) 3.0 (3.0) 30 AK-R2-047P500 47 0.166 33 79% 79% 11% N/A N/A
    5.5 (7.5) 4.0 (5.0) 23 AK-R2-030P1K2 30 0.26 52 90% 90% 10% N/A N/A
    7.5 (10) 5.5 (7.5) 23 AK-R2-030P1K2 30 0.26 52 66% 66% 10% N/A N/A
    400…480 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 68 AK-R2-360P500 360 0.086 17 305% 100% 47% 150% 31%
    0.75 (1.0) 0.55 (0.75) 68 AK-R2-360P500 360 0.086 17 220% 100% 23% 150% 15%
    1.5 (2.0) 1.1 (1.5) 68 AK-R2-360P500 360 0.086 17 110% 100% 12% 110% 11%
    2.2 (3.0) 1.5 (2.0) 68 AK-R2-120P1K2 120 0.26 52 197% 100% 24% 150% 16%
    4.0 (5.0) 3.0 (3.0) 68 AK-R2-120P1K2 120 0.26 52 124% 100% 13% 124% 10%
    5.5 (7.5) 4.0 (5.0) 74 AK-R2-120P1K2 120 0.26 52 90% 90% 10% N/A N/A
    7.5 (10) 5.5 (7.5) 74 AK-R2-120P1K2 120 0.26 52 66% 66% 10% N/A N/A
    11 (15) §  7.5 (10) §  44 §  60 0.52 104 90% 90% 10% N/A N/A
    15 (20) §  11 (15) §  31 §  60 0.52 104 66% 66% 10% N/A N/A
    500…600 Volt AC Input Drives
    0.37 (0.5) 0.25 (0.33) 117 AK-R2-360P500 360 0.086 17 274% 100% 46% 150% 31%
    0.75 (1.0) 0.55 (0.75) 117 AK-R2-360P500 360 0.086 17 251% 100% 23% 150% 15%
    1.5 (2.0) 1.1 (1.5) 117 AK-R2-360P500 360 0.086 17 172% 100% 11% 150% 8%
    2.2 (3.0) 1.5 (2.0) 117 AK-R2-120P1K2 120 0.26 52 193% 100% 24% 150% 16%
    4.0 (5.0) 3.0 (3.0) 80 AK-R2-120P1K2 120 0.26 52 185% 100% 13% 150% 9%
    5.5 (7.5) 4.0 (5.0) 80 AK-R2-120P1K2 120 0.26 52 141% 100% 9% 141% 7%
    7.5 (10) 5.5 (7.5) 80 AK-R2-120P1K2 120 0.26 52 103% 100% 7% 103% 7%
    11 (15) §  7.5 (10) §  48 §  60 0.52 104 141% 100% 9% 141% 7%
    15 (20) §  11 (15) §  48 §  60 0.52 104 103% 100% 7% 103% 7%
    ⋆ Duty cycle listed is based on full speed to zero speed deceleration. For constant regen at full speed, duty cycle capability is half of what is listed. Application Type 1 represents maximum capability up to 100% braking torque where possible. Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
    ‡ Always check resistor Ohms against minimum resistance for drive being used.
    § For 11 and 15 kW (15 and 20 Hp) applications, use two 7.5 kW (10 Hp) size resistors wired in parallel.

    Internal Dynamic Brake Resistor Kits

    These resistors have a limited duty cycle. Refer to the PowerFlex Dynamic Braking Selection Guide to determine if an internal resistor will be sufficient for your application. An external resistor may be required.

    Drive Input Voltage Brake Resistance Frame Cat. No. Used with PowerFlex Drive
    W 70 700 700H 700S 700L 753/755
    208…240V AC 62 0 20BB-DB1-0   ü   ü    
    62 1 (except 7.5 Hp) 20BB-DB1-1   ü   ü    
    22 1 (7.5 Hp) 20BB-DB2-1   ü   ü    
    22 2 20BB-DB1-2   ü   ü    
    380…600V AC 115 0 20BD-DB1-0   ü   ü    
    115 1 20BD-DB1-1   ü   ü    
    68 2 20BD-DB1-2   ü   ü    
    62 2 20-750-DB1-D2           ü
      

    Terminators
    Description ‡  Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    for use with 3.7 kW (5 Hp) & below drives 1204-TFA1 ü ü   ü ü ü
    for use with 1.5 kW (2 Hp) & up drives 1204-TFB2 ü ü ü ü ü ü
    ‡ Refer to Appendix A of publication Drives-IN001 for selection information.

    Reflected Wave Reduction Modules w/Common Mode Choke
    Description ‡  Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    17A with Common Mode Choke 1204-RWC-17-A ü ü ü ü   ü
    ‡ Refer to Appendix A of publication Drives-IN001 for selection information.

    Reflected Wave Reduction Modules
    Voltage ND kW ND Hp Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    380…480V AC 4 5 1321-RWR8-DP ü ü   ü   ü
    5.5 7.5 1321-RWR12-DP ü ü   ü   ü
    7.5 10 1321-RWR18-DP ü ü   ü   ü
    11 15 1321-RWR25-DP ü ü   ü   ü
    15 20 1321-RWR35-DP ü ü   ü   ü
    18.5 25 1321-RWR35-DP ü ü   ü   ü
    22 30 1321-RWR45-DP ü ü   ü   ü
    30 40 1321-RWR55-DP ü ü   ü   ü
    37 50 1321-RWR80-DP ü ü   ü   ü
    45 60 1321-RWR80-DP   ü   ü   ü
    55 75 1321-RWR100-DP   ü   ü   ü
    75 100 1321-RWR130-DP   ü   ü   ü
    75 100 1321-RWR160-DP       ü    
    90 125 1321-RWR160-DP   ü   ü   ü
    110 150 1321-RWR200-DP   ü   ü   ü
    149 200 1321-RWR250-DP   ü ü ü   ü
    149 200 1321-RWR320-DP       ü    
    187 250 1321-RWR320-DP   ü ü ü   ü
    500…600V AC 4 5 1321-RWR8-EP ü ü   ü    
    5.5 7.5 1321-RWR8-EP       ü    
    5.5 7.5 1321-RWR12-EP ü ü        
    7.5 10 1321-RWR12-EP ü ü   ü    
    11 15 1321-RWR18-EP ü ü   ü    
    15 20 1321-RWR25-EP ü ü   ü    
    18.5 25 1321-RWR25-EP       ü    
    18.5 25 1321-RWR35-EP ü ü        
    22 30 1321-RWR35-EP ü ü   ü    
    30 40 1321-RWR45-EP ü ü   ü    
    37 50 1321-RWR55-EP ü ü   ü    
    45 60 1321-RWR80-EP   ü   ü    
    55 75 1321-RWR80-EP   ü   ü    
    75 100 1321-RWR100-EP   ü   ü    
    90 125 1321-RWR130-EP   ü   ü    
    110 150 1321-RWR160-EP   ü   ü    
    110 150 1321-RWR200-EP       ü    
    149 200 1321-RWR200-EP       ü    
      

    1492 Wiring System Modules and Cables

    Wiring System Modules and Cables provide an easy means to extend drive control wiring. A pre-wired cable (available in various lengths) plugs into the appropriate drive I/O terminal block. The remaining cable end plugs into the Wiring Module which provides a terminal block for direct I/O connection. See publication 1492-TD008 for detailed information.

    1492 Wiring Module and Cable Selection
    Drive I/O Wiring Module Description Wiring Module Cat. No. PowerFlex 700H Cable (see below) PowerFlex 700S Cable (see below) Used with PowerFlex Drive
    Fixed Terminal Block Removable Terminal Block 70 700 700H 700S 700L 753/755
    Analog I/O (TB1) 6 Channel Isolated - 3 Terminals/Ch. 1492-AIFM6S-3 1492-RAIFM6S-3 1492-ACABxxxZ7H 1492-ACABxxxZ7S     ü ü    
    DC Discrete Digital I/O (TB2) Standard,
    264V AC/DC
    1492-IFM20F 1492-RIFM20F 1492-CABxxxA7H 1492-CABxxxA7S     ü ü    
    Narrow Standard,
    132V AC/DC
    1492-IFM20FN 1492-RIFM20FN 1492-CABxxxA7H 1492-CABxxxA7S     ü ü    
    Extra Terminals
    (2 per I/O), 264V AC/DC
    1492-IFM20F-2 1492-RIFM20F-2 1492-CABxxxA7H 1492-CABxxxA7S     ü ü    
    AC Discrete Digital I/O (20C-DA1-B & 20C-DO1) Standard,
    264V AC/DC
    1492-IFM20F 1492-RIFM20F 1492-CABxxxB7H 1492-CABxxxB7H     ü      
    Narrow Standard,
    132V AC/DC
    1492-IFM20FN 1492-RIFM20FN 1492-CABxxxB7H 1492-CABxxxB7H     ü      
    Extra Terminals
    (2 per I/O), 264V AC/DC
    1492-IFM20F-2 1492-RIFM20F-2 1492-CABxxxB7H 1492-CABxxxB7H     ü      
    Encoder 2 Channel Encoder Input - 4 Outputs 1492-AIFMCE4 1492-ACABxxxX7S 1492-ACABxxxX7S       ü    
    2 Channel Fused Encoder Input - 4 Fused Outputs 1492-AIFMCE4-F 1492-ACABxxxX7S 1492-ACABxxxX7S       ü    
      

    1492 Pre-Wired Cable Assemblies
    Description PowerFlex 700H Cat. No. PowerFlex 700S Cat. No. Used with PowerFlex Drive
    70 700 700H 700S 700L 753/755
    Pre-Wired Cable for Analog I/O
    0.5 Meter (1.6 Feet) 1492-ACAB005Z7H 1492-ACAB005Z7S     ü ü    
    1.0 Meter (3.3 Feet) 1492-ACAB010Z7H 1492-ACAB010Z7S     ü ü    
    2.5 Meters (8.2 Feet) 1492-ACAB025Z7H 1492-ACAB025Z7S     ü ü    
    5.0 Meters (16.4 Feet) 1492-ACAB050Z7H 1492-ACAB050Z7S     ü ü    
    Pre-Wired Cable for Discrete DC I/O
    0.5 Meter (1.6 Feet) 1492-CAB005A7H 1492-CAB005A7S     ü ü    
    1.0 Meter (3.3 Feet) 1492-CAB010A7H 1492-CAB005A7S     ü ü    
    2.5 Meters (8.2 Feet) 1492-CAB025A7H 1492-CAB025A7S     ü ü    
    5.0 Meters (16.4 Feet) 1492-CAB050A7H 1492-CAB050A7S     ü ü    
    Pre-Wired Cable for Discrete AC I/O
    0.5 Meter (1.6 Feet) 1492-CAB005B7H     ü      
    1.0 Meter (3.3 Feet) 1492-CAB010B7H     ü      
    2.5 Meters (8.2 Feet) 1492-CAB025B7H     ü      
    5.0 Meters (16.4 Feet) 1492-CAB050B7H     ü      
    Pre-Wired Cable for Encoder
    0.5 Meter (1.6 Feet) 1492-ACAB005X7S       ü    
    1.0 Meter (3.3 Feet) 1492-ACAB010X7S       ü    
    2.5 Meters (8.2 Feet) 1492-ACAB025X7S       ü    
    5.0 Meters (16.4 Feet) 1492-ACAB050X7S       ü    
     

    Isolation Transformers - IP32, NEMA/UL Type 3R Standalone, 4…6% Nominal Impedance
           
      Click to enlarge - xfmr_sch1 Click to enlarge - xfmr_sch2  
      Diagram 1 Diagram 2  

    Motor Rating Wiring Diagram 240V, 60 Hz, Three-Phase, 240V Primary & 240V Secondary ⋆  460V, 60 Hz, Three-Phase, 460V Primary & 460V Secondary 575V, 60 Hz, Three-Phase 575V Primary & 575V Secondary ⋆  Used with PowerFlex Drive
    kW Hp Cat. No. Cat. No. Cat. No. 70 700 700H 700S 700L 753/755
    0.25 0.33 1 1321-3TW005-AA 1321-3TW005-BB ü ü   ü    
    0.37 0.5 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü    
    0.55 0.75 1 1321-3TW005-AA 1321-3TW005-BB ü ü   ü    
    0.75 1 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü   ü
    1.1 1.5 1 1321-3TW005-AA 1321-3TW005-BB ü ü   ü    
    1.5 2 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü   ü
    2.2 3 1 1321-3TW005-AA 1321-3TW005-BB 1321-3TW005-CC ü ü   ü   ü
    22 30 2 1321-3TW040-AA 1321-3TW040-BB 1321-3TW040-CC ü ü   ü   ü
    30 40 2 1321-3TW051-AA 1321-3TW051-BB 1321-3TW051-CC ü ü   ü   ü
    37 50 2 1321-3TH063-AA 1321-3TH063-BB 1321-3TH063-CC ü ü   ü   ü
    45 60 2 1321-3TH075-AA 1321-3TH075-BB 1321-3TH075-CC   ü   ü   ü
    55 75 2 1321-3TH093-AA 1321-3TH093-BB 1321-3TH093-CC   ü   ü   ü
    75 100 2 1321-3TH118-BB 1321-3TH118-CC   ü   ü   ü
    90 125 2 1321-3TH145-BB 1321-3TH145-CC   ü   ü   ü
    110 150 2 1321-3TH175-BB 1321-3TH175-CC   ü ü ü   ü
    149 200 2 1321-3TH220-BB 1321-3TH220-CC   ü ü ü   ü
    187 250 2 1321-3TH275-BB 1321-3TH275-CC   ü ü     ü
    224 300 2 1321-3TH330-BB 1321-3TH330-CC   ü ü     ü
    224 300 1 1321-3TH330-CC           ü
    261 350 1 1321-3TH440-BB 1321-3TH440-CC   ü ü     ü
    298 400 1 1321-3TH440-BB 1321-3TH440-CC   ü ü      
    298 400 1 1321-3TH440-BB 1321-3TH550-CC           ü
    336 450 1 1321-3TH550-BB 1321-3TH550-CC   ü ü     ü
    373 500 1 1321-3TH550-BB 1321-3TH550-CC   ü ü      
    373 500 1 1321-3TH550-BB 1321-3TH660-CC           ü
    410 550 1 1321-3TH660-CC           ü
    448 600 1 1321-3TH660-BB 1321-3TH660-CC   ü ü      
    448 600 1 1321-3TH660-BB 1321-3TH770-CC           ü
    485 650 1 1321-3TH770-CC   ü ü      
    522 700 1 1321-3TH770-BB 1321-3TH770-CC   ü ü     ü
    597 800 1 1321-3TH880-BB 1321-3TH880-CC           ü
    671 900 900 kVA ‡  950 kVA ‡            ü
    709 950 1000 kVA ‡            ü
    746 1000 1000 kVA ‡  1100 kVA ‡            ü
    821 1100 1200 kVA ‡            ü
    895 1200 1200 kVA ‡            ü
    933 1250 1200 kVA ‡            ü
    1007 1350 1300 kVA ‡            ü
    1119 1500 1500 kVA ‡  1500 kVA ‡            ü
    1492 2000 2000 kVA ‡            ü
      
    ⋆ Not applicable for the PowerFlex 755.
    ‡  1321 Isolation Transformer solution is not available. Approximate drive kVA is listed.

    Input and Output Reactors - 200…240V, 50/60 Hz, Three-Phase, 3% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R2-D 1321-3RA2-D 1321-3R2-D 1321-3RA2-D ü ü   ü    
    0.37 0.5 Normal 1321-3R2-D 1321-3RA2-D 1321-3R2-D 1321-3RA2-D ü ü   ü    
    0.55 0.75 Heavy 1321-3R4-A 1321-3RA4-A 1321-3R4-A 1321-3RA4-A ü ü   ü    
    0.75 1 Normal 1321-3R4-A 1321-3RA4-A 1321-3R4-A 1321-3RA4-A ü ü   ü    
    1.1 1.5 Heavy 1321-3R8-B 1321-3RA8-B 1321-3R8-A 1321-3RA8-A ü ü   ü    
    1.5 2 Normal 1321-3R8-A 1321-3RA8-A 1321-3R8-A 1321-3RA8-A ü ü   ü    
    Heavy 1321-3R8-A 1321-3RA8-A 1321-3R12-A 1321-3RA12-A ü ü   ü    
    2.2 3 Normal 1321-3R12-A 1321-3RA12-A 1321-3R12-A 1321-3RA12-A ü ü   ü    
    Heavy 1321-3R12-A 1321-3RA12-A 1321-3R18-A 1321-3RA18-A ü ü   ü    
    4 5 Normal 1321-3R18-A 1321-3RA18-A 1321-3R18-A 1321-3RA18-A ü ü   ü    
    Heavy 1321-3R18-A 1321-3RA18-A 1321-3R25-A 1321-3RA25-A ü ü   ü    
    5.5 7.5 Normal 1321-3R25-A 1321-3RA25-A 1321-3R25-A 1321-3RA25-A ü ü   ü    
    Heavy 1321-3R25-A 1321-3RA25-A 1321-3R35-A 1321-3RA35-A ü ü   ü    
    7.5 10 Normal 1321-3R35-A 1321-3RA35-A 1321-3R35-A 1321-3RA35-A ü ü   ü    
    Heavy 1321-3R35-A 1321-3RA35-A 1321-3R45-A 1321-3RA45-A ü ü   ü    
    11 15 Normal 1321-3R45-A 1321-3RA45-A 1321-3R45-A 1321-3RA45-A ü ü   ü    
    Heavy 1321-3R45-A 1321-3RA45-A 1321-3R55-A 1321-3RA55-A ü ü   ü    
    15 20 Normal 1321-3R55-A 1321-3RA55-A 1321-3R55-A 1321-3RA55-A ü ü   ü    
    Heavy 1321-3R55-A 1321-3RA55-A 1321-3R80-A 1321-3RA80-A ü ü   ü    
    18.5 25 Normal 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A ü ü   ü    
    Heavy 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A   ü   ü    
    22 30 Normal 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A   ü   ü    
    Heavy 1321-3R80-A 1321-3RA80-A 1321-3R80-A 1321-3RA80-A   ü   ü    
    30 40 Normal 1321-3R100-A 1321-3RA100-A 1321-3R100-A 1321-3RA100-A   ü   ü    
    Heavy 1321-3R100-A 1321-3RA100-A 1321-3R100-A 1321-3RA100-A   ü   ü    
    37 50 Normal 1321-3R130-A 1321-3RA130-A 1321-3R130-A 1321-3RA130-A   ü   ü    
    Heavy 1321-3R130-A 1321-3RA130-A 1321-3R130-A 1321-3RA130-A   ü   ü    
    45 60 Normal 1321-3R160-A 1321-3RA160-A 1321-3R160-A 1321-3RA160-A   ü   ü    
    Heavy 1321-3R160-A 1321-3RA160-A 1321-3R160-A 1321-3RA160-A   ü   ü    
    55 75 Normal 1321-3R200-A 1321-3RA200-A 1321-3R200-A 1321-3RA200-A   ü   ü    
    Heavy 1321-3R200-A 1321-3RA200-A 1321-3R200-A 1321-3RA200-A   ü   ü    
    75 100 Normal 1321-3RB250-A 1321-3RAB250-A 1321-3RB250-A 1321-3RAB250-A   ü   ü    
    ‡ Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD rated output currents.

    Input and Output Reactors - 200…240V, 50/60 Hz, Three-Phase, 5% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü    
    0.37 0.5 Normal 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü    
    0.55 0.75 Heavy 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B ü ü   ü    
    0.75 1 Normal 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B ü ü   ü    
    1.1 1.5 Heavy 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B ü ü   ü    
    1.5 2 Normal 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B ü ü   ü    
    Heavy 1321-3R8-B 1321-3RA8-B 1321-3R12-B 1321-3RA12-B ü ü   ü    
    2.2 3 Normal 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B ü ü   ü    
    Heavy 1321-3R12-B 1321-3RA12-B 1321-3R18-B 1321-3RA18-B ü ü   ü    
    4 5 Normal 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B ü ü   ü    
    Heavy 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B ü ü   ü    
    5.5 7.5 Normal 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü    
    Heavy 1321-3R25-B 1321-3RA25-B 1321-3R35-B 1321-3RA35-B ü ü   ü    
    7.5 10 Normal 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü    
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B ü ü   ü    
    11 15 Normal 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B ü ü   ü    
    Heavy 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B ü ü   ü    
    15 20 Normal 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B ü ü   ü    
    Heavy 1321-3R55-B 1321-3RA55-B 1321-3R80-B 1321-3RA80-B ü ü   ü    
    18.5 25 Normal 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    22 30 Normal 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü    
    30 40 Normal 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü    
    Heavy 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü    
    37 50 Normal 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü    
    Heavy 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü    
    45 60 Normal 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü    
    Heavy 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü    
    55 75 Normal 1321-3R200-B 1321-3RA200-B 1321-3R200-B 1321-3RA200-B   ü   ü    
    Heavy 1321-3R200-B 1321-3RA200-B 1321-3R200-B 1321-3RA200-B   ü   ü    
    75 100 Normal 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B   ü   ü    
    ‡ Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD rated output currents.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 3% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-C 1321-3RA1-C 1321-3R2-B 1321-3RA2-B ü ü   ü    
    0.37 0.5 Normal 1321-3R1-C 1321-3RA1-C 1321-3R2-B 1321-3RA2-B ü ü   ü    
    0.55 0.75 Heavy 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü    
    0.75 1 Normal 1321-3R2-A 1321-3RA2-A 1321-3R2-A 1321-3RA2-A ü ü   ü   ü
    1.1 1.5 Heavy 1321-3R4-C 1321-3RA4-C 1321-3R4-B 1321-3RA4-B ü ü   ü   ü
    1.5 2 Normal 1321-3R4-B 1321-3RA4-B 1321-3R4-B 1321-3RA4-B ü ü   ü   ü
    Heavy 1321-3R4-B 1321-3RA4-B 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    2.2 3 Normal 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    Heavy 1321-3R8-C 1321-3RA8-C 1321-3R8-B 1321-3RA8-B ü ü   ü   ü
    4 5 Normal 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B ü ü   ü   ü
    Heavy 1321-3R8-B 1321-3RA8-B 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    5.5 7.5 Normal 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    Heavy 1321-3R12-B 1321-3RA12-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    7.5 10 Normal 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    Heavy 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    11 15 Normal 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    Heavy 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    15 20 Normal 1321-3R35-B 1321-3RA35-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    18.5 25 Normal 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    22 30 Normal 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    Heavy 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    30 40 Normal 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    Heavy 1321-3R55-B 1321-3RA55-B 1321-3R80-B 1321-3RA80-B ü ü   ü   ü
    37 50 Normal 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B ü ü   ü   ü
    Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    55 75 Normal/Heavy 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü   ü
    75 100 Normal/Heavy 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü   ü
    90 125 Normal/Heavy 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü   ü
    110 150 Normal 1321-3R200-B 1321-3RA200-B 1321-3R200-C 1321-3RA200-C   ü ü ü   ü
    Heavy 1321-3R200-B 1321-3RA200-B 1321-3R200-C 1321-3RA200-C   ü   ü   ü
    Heavy 1321-3R200-B 1321-3RA200-B     ü      
    200 Normal/Heavy 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B           ü
    132 Normal/Heavy 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B           ü
    149 200 Normal 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B   ü ü ü    
    Heavy 1321-3RB250-B 1321-3RAB250-B 1321-3RB250-B 1321-3RAB250-B   ü ü ü    
    160 250 Normal/Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B           ü
    187 250 Normal/Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B   ü ü      
    200 300 Normal 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü ü     ü
    Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü ü     ü
    350 Normal/Heavy 1321-3R500-B 1321-3R500-B 1321-3R500-B 1321-3R500-B           ü
    250 Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    261 350 Normal 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü        
    Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B   ü ü      
    Normal 1321-3R500-B 1321-3RA500-B     ü      
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two output reactors wired in parallel.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 3% Impedance (continued)
    kW Hp Duty ♦  Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    400 Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    280 400 Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B   ü        
    315 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    450 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    336 450 Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B   ü ü      
    355 Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    500 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    373 500 Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B   ü ü      
    400 Light/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    Normal 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    600 Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    448 600 Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B   ü ü      
    Heavy 1321-3R750-B 1321-3RA750-B     ü      
    Heavy 1321-3R750-B 1321-3RA750-B 1321-3R600-B 1321-3RA600-B   ü        
    450 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    650 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    700 Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    522 700 Normal 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B   ü        
    Normal/Heavy 1321-3RB400-B 1321-3RB400-B     ü §       
    750 Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    500 Normal/Heavy 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    500 800 Normal/Heavy 1321-3R500-B 1321-3RA500-B     ü §       
    800 Light/Normal/Heavy 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    560 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    630 900 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    Normal 1321-3R500-B 1321-3RA500-B     ü §       
    Heavy 1321-3R600-B 1321-3RA600-B     ü §       
    710 1000 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    746 1000 Normal 1321-3R600-B 1321-3RA600-B     ü §       
    Heavy 1321-3R750-B 1321-3RA750-B     ü §       
    800 1100 Light/Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü § 
    850 Light/Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü § 
    895 1200 Normal 1321-3R750-B 1321-3RA750-B     ü §       
    900 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü § 
    1250 Light/Normal 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü § 
    933 1250 Normal 1321-3R750-B 1321-3RA750-B     ü §       
    1350 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü § 
    1500 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    1000 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    2000 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    1400 Light 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.
    ♦ Light Duty refers to PowerFlex 755 drives only.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 5% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-B 1321-3RA1-B 1321-3R2-C 1321-3RA2-C ü ü   ü    
    0.37 0.5 Normal 1321-3R1-B 1321-3RA1-B 1321-3R2-C 1321-3RA2-C ü ü   ü    
    0.55 0.75 Heavy 1321-3R2-C 1321-3RA2-C 1321-3R2-B 1321-3RA2-B ü ü   ü    
    0.75 1 Normal 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B ü ü   ü   ü
    1.1 1.5 Heavy 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    1.5 2 Normal 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    Heavy 1321-3R4-D 1321-3RA4-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    2.2 3 Normal 1321-3R8-D 1321-3RA8-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    Heavy 1321-3R8-D 1321-3RA8-D 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    4 5 Normal 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    Heavy 1321-3R8-C 1321-3RA8-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    5.5 7.5 Normal 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    Heavy 1321-3R12-C 1321-3RA12-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    7.5 10 Normal 1321-3R18-C 1321-3RA18-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    Heavy 1321-3R18-C 1321-3RA18-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    11 15 Normal/Heavy 1321-3R25-C 1321-3RA25-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    15 20 Normal 1321-3R35-C 1321-3RA35-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    18.5 25 Normal 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    22 30 Normal 1321-3R45-C 1321-3RA45-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    Heavy 1321-3R45-C 1321-3RA45-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    30 40 Normal 1321-3R55-C 1321-3RA55-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    Heavy 1321-3R55-C 1321-3RA55-C 1321-3R80-C 1321-3RA80-C ü ü   ü   ü
    37 50 Normal 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C ü ü   ü   ü
    Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    55 75 Normal/Heavy 1321-3R100-C 1321-3RA100-C 1321-3R100-C 1321-3RA100-C   ü   ü   ü
    75 100 Normal/Heavy 1321-3R130-C 1321-3RA130-C 1321-3R130-C 1321-3RA130-C   ü   ü   ü
    90 125 Normal/Heavy 1321-3R160-C 1321-3RA160-C 1321-3R160-C 1321-3RA160-C   ü   ü   ü
    110 150 Normal 1321-3R200-C 1321-3RA200-C 1321-3R200-C 1321-3RA200-C   ü   ü   ü
    Heavy 1321-3R200-C 1321-3RA200-C 1321-3R200-C 1321-3RA200-C   ü ü ü   ü
    Heavy 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C     ü ü ♣     
    200 Normal/Heavy 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C           ü
    132 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    149 200 Normal 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C   ü   ü ∆     
    Heavy 1321-3RB250-C 1321-3RAB250-C 1321-3RB250-C 1321-3RAB250-C   ü ü ü    
    160 250 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    187 250 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C   ü ü      
    300 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    200 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    224 300 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C   ü ü      
    350 Normal/Heavy 1321-3R500-C 1321-3R500-C 1321-3R500-C 1321-3R500-C           ü
    250 Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    261 350 Normal 1321-3R500-C 1321-3RA500-C 1321-3RB400-C 1321-3RAB400-C   ü        
    Normal 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C     ü      
    Heavy 1321-3R500-C 1321-3RA500-C 1321-3RB400-C 1321-3RAB400-C   ü ü      
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ♣ For use with 300A PowerFlex 700S.
    ∆ For use with 248A and 261A PowerFlex 700S.

    Input and Output Reactors - 380…480V, 50/60 Hz, Three-Phase, 5% Impedance (continued)
    kW Hp Duty ♦  Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    400 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    298 400 Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C   ü        
    315 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    336 450 Normal/Heavy 1321-3RA600-C 1321-3RA600-C 1321-3R500-C 1321-3RA500-C   ü ü      
    450 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    355 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    373 500 Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C   ü ü      
    500 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    400 Light/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    Normal 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    448 600 Normal/Heavy 1321-3R750-E 1321-3RA750-E 1321-3R750-E 1321-3RA750-E   ü        
    600 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    450 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    500 Normal/Heavy 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    522 600 Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C     ü ⋆       
    650 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    700 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    522 700 Normal 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C   ü        
    Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    671 700 Heavy 1321-3RB400-C 1321-3RAB400-C     ü §       
    750 Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    800 Light/Normal/Heavy 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    560 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    597 800 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    630 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    746 800 Heavy 1321-3R500-C 1321-3RA500-C     ü §       
    900 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    671 900 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    Heavy 1321-3RA600-C 1321-3RA600-C     ü §       
    710 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    1000 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    746 1000 Normal 1321-3RA600-C 1321-3RA600-C     ü §       
    Heavy 1321-3R750-C 1321-3RA750-C     ü § ⋆       
    1100 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    800 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    850 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    895 1200 Normal 1321-3R750-C 1321-3RA750-C     ü § ⋆       
    1250 Light/Normal 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü § 
    900 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü § 
    933 1250 Normal 1321-3R750-C 1321-3RA750-C     ü §       
    1350 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü § 
    1500 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    1000 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    2000 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    1400 Light 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ⋆ 4% impedance.
    § Requires two output reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.
    ♦ Light Duty refers to PowerFlex 755 drives only.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 3% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-C 1321-3RA1-C 1321-3R1-B 1321-3RA1-B ü          
    0.37 0.5 Normal 1321-3R1-C 1321-3RA1-C 1321-3R1-B 1321-3RA1-B ü          
    Heavy 1321-3R1-C 1321-3RA1-C 1321-3R2-B 1321-3RA2-B   ü   ü    
    0.55 0.75 Heavy 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B ü          
    0.75 1 Normal 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B ü ü   ü   ü
    Heavy 1321-3R2-B 1321-3RA2-B 1321-3R4-D 1321-3RA4-D   ü   ü   ü
    1.1 1.5 Heavy 1321-3R2-A 1321-3RA2-A 1321-3R4-D 1321-3RA4-D ü          
    1.5 2 Normal 1321-3R4-C 1321-3RA4-C 1321-3R4-D 1321-3RA4-D ü          
    Heavy 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C ü         ü
    Normal 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D   ü   ü   ü
    Heavy 1321-3R4-D 1321-3RA4-D 1321-3R4-C 1321-3RA4-C   ü   ü   ü
    2.2 3 Normal 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C ü ü   ü   ü
    Heavy 1321-3R4-C 1321-3RA4-C 1321-3R8-C 1321-3RA8-C ü ü   ü    
    4 5 Normal 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C ü ü   ü   ü
    Heavy 1321-3R8-C 1321-3RA8-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    5.5 7.5 Normal 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    Heavy 1321-3R12-C 1321-3RA12-C 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    7.5 10 Normal 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B ü ü   ü   ü
    Heavy 1321-3R12-B 1321-3RA12-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    11 15 Normal 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B ü ü   ü   ü
    Heavy 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    15 20 Normal 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B ü ü   ü   ü
    Heavy 1321-3R25-B 1321-3RA25-B 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    18.5 25 Normal 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    22 30 Normal 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B ü ü   ü   ü
    Heavy 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    30 40 Normal 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B ü ü   ü   ü
    Heavy 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    37 50 Normal 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B ü ü   ü   ü
    Heavy 1321-3R55-B 1321-3RA55-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    55 75 Normal/Heavy 1321-3R80-B 1321-3RA80-B 1321-3R80-B 1321-3RA80-B   ü   ü   ü
    75 100 Normal/Heavy 1321-3R100-B 1321-3RA100-B 1321-3R100-B 1321-3RA100-B   ü   ü   ü
    90 125 Normal/Heavy 1321-3R130-B 1321-3RA130-B 1321-3R130-B 1321-3RA130-B   ü   ü   ü
    110 150 Normal 1321-3R160-B 1321-3RA160-B 1321-3R160-B 1321-3RA160-B   ü   ü   ü
    Normal/Heavy 1321-3R200-C 1321-3RA200-C     ü      
    132 Heavy 1321-3RB250-C 1321-3RAB250-C     ü      
    149 200 Normal/Heavy 1321-3R200-B 1321-3RA200-B     ü      
    160 Normal/Heavy 1321-3RB250-C 1321-3RAB250-C     ü      
    187 250 Normal/Heavy 1321-3RB250-B 1321-3RAB250-B     ü      
    300 Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B           ü
    200 Normal 1321-3RB250-C 1321-3RAB250-C     ü      
    Heavy 1321-3RB320-C 1321-3RAB320-C     ü      
    Heavy 1321-3R250-B 1321-3RA250-B 1321-3R250-B 1321-3RA250-B           ü
    350 Light/Normal/Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    250 Normal 1321-3RB320-C 1321-3RAB320-C     ü      
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü      
    Normal/Heavy 1321-3RB320-B 1321-3RAB320-B 1321-3RB320-B 1321-3RAB320-B           ü
    261 350 Normal/Heavy 1321-3RB320-B 1321-3RAB320-B     ü      
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 3% Impedance (continued)
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    298 400 Normal/Heavy 1321-3RB400-B 1321-3RAB400-B     ü      
    400 Light/Normal/Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    300 Heavy 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    450 Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    315 Normal 1321-3RB400-C 1321-3RAB400-C     ü      
    Heavy 1321-3R500-C 1321-3RA500-C     ü      
    Light/Normal 1321-3RB400-B 1321-3RAB400-B 1321-3RB400-B 1321-3RAB400-B           ü
    336 450 Normal 1321-3RB400-B 1321-3RAB400-B     ü      
    Normal 1321-3R500-B 1321-3RA500-B     ü      
    Heavy 1321-3RB400-B 1321-3RAB400-B     ü      
    500 Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    355 Normal 1321-3R500-C 1321-3RA500-C     ü      
    Heavy 1321-3R600-C 1321-3RA600-C     ü      
    Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    373 500 Normal/Heavy 1321-3R500-B 1321-3RA500-B     ü      
    550 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    375 Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    400 Normal 1321-3R500-C 1321-3RA500-C     ü      
    Light/Normal/Heavy 1321-3R500-B 1321-3RA500-B 1321-3R500-B 1321-3RA500-B           ü
    448 600 Normal 1321-3R600-B 1321-3RA600-B     ü      
    600 Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    450 Normal/Heavy 1321-3R600-C 1321-3RA600-C     ü      
    Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    485 650 Heavy 1321-3RB320-B 1321-3RAB320-B     ü §       
    500 Normal 1321-3R600-C 1321-3RA600-C     ü      
    Heavy 1321-3R750-C 1321-3RA750-C     ü      
    Light/Normal/Heavy 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    522 700 Normal 1321-3RB320-B 1321-3RAB320-B     ü §       
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü §       
    700 Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    530 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü
    560 Normal 1321-3R750-C 1321-3RA750-C     ü      
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü §       
    Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    750 Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    597 800 Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    800 Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    630 Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    Heavy 1321-3R500-C 1321-3RA500-C     ü §       
    Light/Normal/Heavy 1321-3R750-B 1321-3RA750-B 1321-3R750-B 1321-3RA750-B           ü
    671 900 Normal 1321-3RB400-B 1321-3RAB400-B     ü §       
    Heavy 1321-3R1000-C 1321-3RA1000-C     ü      
    900 Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    710 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    Light/Normal/Heavy 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    950 Light/Normal 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    746 1000 Normal 1321-3R1000-C 1321-3RA1000-C     ü      
    Heavy 1321-3R1000-B 1321-3RA1000-B     ü      
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two reactors wired in parallel.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 3% Impedance (continued)
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    750 Normal 1321-3R850-B 1321-3RA850-B 1321-3R850-B 1321-3RA850-B           ü
    800 Normal 1321-3R500-C 1321-3RA500-C     ü §       
    Heavy 1321-3R600-C 1321-3RA600-C     ü §       
    Light/Normal/Heavy 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    1000 Light/Normal 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    821 1100 Normal 1321-3R1000-B 1321-3RA1000-B     ü      
    Heavy 1321-3R600-B 1321-3RA600-B     ü §       
    1100 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    850 Light 1321-3R1000-B 1321-3RA1000-B 1321-3R1000-B 1321-3RA1000-B           ü
    900 Normal/Heavy 1321-3R600-C 1321-3RA600-C     ü §       
    Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    970 1300 Normal 1321-3R600-B 1321-3RA600-B     ü §       
    1000 Normal 1321-3R600-C 1321-3RA600-C     ü §       
    Heavy 1321-3R750-C 1321-3RA750-C     ü §       
    Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü § 
    1100 Normal 1321-3R750-C 1321-3RA750-C     ü §       
    Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    1200 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    1500 Light/Normal 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    1500 Light 1321-3R600-B 1321-3RA600-B 1321-3R600-B 1321-3RA600-B           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    § Requires two reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 5% Impedance
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    0.25 0.33 Heavy 1321-3R1-A 1321-3RA1-A 1321-3R1-B 1321-3RA1-B ü          
    0.37 0.5 Normal 1321-3R1-B 1321-3RA1-B 1321-3R1-B 1321-3RA1-B ü          
    0.37 0.5 Heavy 1321-3R1-B 1321-3RA1-B 1321-3R2-C 1321-3RA2-C   ü   ü    
    0.55 0.75 Heavy 1321-3R2-C 1321-3RA2-C 1321-3R2-C 1321-3RA2-C ü          
    0.75 1 Normal 1321-3R2-C 1321-3RA2-C 1321-3R2-C 1321-3RA2-C ü ü   ü   ü
    Heavy 1321-3R2-C 1321-3RA2-C 1321-3R4-D 1321-3RA4-D   ü   ü   ü
    1.1 1.5 Heavy 1321-3R2-B 1321-3RA2-B 1321-3R4-D 1321-3RA4-D ü ü   ü    
    1.5 2 Normal/Heavy 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    2.2 3 Normal 1321-3R4-D 1321-3RA4-D 1321-3R4-D 1321-3RA4-D ü ü   ü   ü
    Heavy 1321-3R4-D 1321-3RA4-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    4 5 Normal 1321-3R8-D 1321-3RA8-D 1321-3R8-D 1321-3RA8-D ü ü   ü   ü
    Heavy 1321-3R8-D 1321-3RA8-D 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    5.5 7.5 Normal/Heavy 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    7.5 10 Normal 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C ü ü   ü   ü
    Heavy 1321-3R12-C 1321-3RA12-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    11 15 Normal 1321-3R18-C 1321-3RA18-C 1321-3R18-C 1321-3RA18-C ü ü   ü   ü
    Heavy 1321-3R18-C 1321-3RA18-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    15 20 Normal 1321-3R25-C 1321-3RA25-C 1321-3R25-C 1321-3RA25-C ü ü   ü   ü
    Heavy 1321-3R25-C 1321-3RA25-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    18.5 25 Normal/Heavy 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    22 30 Normal 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C ü ü   ü   ü
    Heavy 1321-3R35-C 1321-3RA35-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    30 40 Normal 1321-3R45-C 1321-3RA45-C 1321-3R45-C 1321-3RA45-C ü ü   ü   ü
    Heavy 1321-3R45-C 1321-3RA45-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    37 50 Normal 1321-3R55-C 1321-3RA55-C 1321-3R55-C 1321-3RA55-C ü ü   ü   ü
    Heavy 1321-3R55-C 1321-3RA55-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    45 60 Normal/Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    55 75 Normal/Heavy 1321-3R80-C 1321-3RA80-C 1321-3R80-C 1321-3RA80-C   ü   ü   ü
    75 100 Normal/Heavy 1321-3R100-C 1321-3RA100-C 1321-3R100-C 1321-3RA100-C   ü   ü   ü
    90 125 Normal/Heavy 1321-3R130-C 1321-3RA130-C 1321-3R130-C 1321-3RA130-C   ü   ü   ü
    110 150 Normal 1321-3R160-C 1321-3RA160-C 1321-3R160-C 1321-3RA160-C   ü   ü   ü
    Heavy 1321-3R160-C 1321-3RA160-C     ü ⋆       
    Normal 1321-3R200-C 1321-3RA200-C     ü ∆       
    149 200 Normal 1321-3R200-B 1321-3RA200-B     ü ⋆       
    Heavy 1321-3R200-C 1321-3RA200-C     ü ⋆       
    187 250 Normal/Heavy 1321-3RB250-C 1321-3RAB250-C     ü ⋆       
    300 Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    200 Heavy 1321-3R250-C 1321-3RA250-C 1321-3R250-C 1321-3RA250-C           ü
    350 Light/Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    250 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C 1321-3RB320-C 1321-3RAB320-C           ü
    261 350 Normal/Heavy 1321-3RB320-C 1321-3RAB320-C     ü ⋆       
    400 Light/Normal/Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    298 400 Normal/Heavy 1321-3RB400-C 1321-3RAB400-C     ü ⋆       
    continued
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ⋆ 4% impedance.
    ∆ 3% impedance.

    Input and Output Reactors - 500…690V, 50/60 Hz, Three-Phase, 5% Impedance (continued)
    kW Hp Duty Input Line Reactor ‡  Output Reactor ‡  Used with PowerFlex Drive
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    IP00
    (Open Style)
    IP11
    (NEMA/UL Type 1)
    70 700 700H 700S 700L 753/755
    300 Heavy 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    315 Light/Normal 1321-3RB400-C 1321-3RAB400-C 1321-3RB400-C 1321-3RAB400-C           ü
    450 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    336 450 Normal 1321-3R500-C 1321-3RA500-C     ü ⋆       
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü      
    500 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    355 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    373 500 Normal/Heavy 1321-3R500-C 1321-3RA500-C     ü      
    550 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    375 Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    400 Light/Normal/Heavy 1321-3R500-C 1321-3RA500-C 1321-3R500-C 1321-3RA500-C           ü
    448 600 Normal 1321-3R600-C 1321-3RA600-C     ü ⋆       
    600 Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    450 Light/Normal/Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    485 650 Heavy 1321-3RB320-C 1321-3RAB320-C     ü ⋆ §       
    500 Heavy 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    522 700 Normal 1321-3RB320-C 1321-3RAB320-C     ü ⋆ §       
    Heavy 1321-3RB400-C 1321-3RAB400-C     ü ⋆ §       
    700 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    530 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü
    750 Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    560 Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    597 800 Normal 1321-3RB400-C 1321-3RAB400-C     ü ⋆ §       
    800 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    630 Light/Normal/Heavy 1321-3R750-C 1321-3RA750-C 1321-3R750-C 1321-3RA750-C           ü
    671 900 Normal 1321-3RB400-C 1321-3RAB400-C     ü §       
    Heavy 1321-3R500-C 1321-3RA500-C     ü ⋆ §       
    900 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    950 Light/Normal 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    710 Light/Normal/Heavy 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    746 1000 Normal 1321-3R500-C 1321-3RA500-C     ü ⋆ §       
    Heavy 1321-3R1000-C 1321-3RA1000-C     ü ⋆       
    750 Normal 1321-3R850-C 1321-3RA850-C 1321-3R850-C 1321-3RA850-C           ü
    1000 Light/Normal 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    800 Light/Normal/Heavy 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    821 1100 Normal 1321-3R1000-C 1321-3RA1000-C     ü ⋆       
    Heavy 1321-3R600-C 1321-3RA600-C     ü ⋆ §       
    1100 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    850 Light 1321-3R1000-C 1321-3RA1000-C 1321-3R1000-C 1321-3RA1000-C           ü
    900 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    970 1300 Normal 1321-3R600-C 1321-3RA600-C     ü ⋆ §       
    1000 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü § 
    1100 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    1200 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    1500 Light/Normal 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    1500 Light 1321-3R600-C 1321-3RA600-C 1321-3R600-C 1321-3RA600-C           ü ♠ 
    ‡ Input line reactors were sized based on the NEC fundamental motor amps (PowerFlex 700H has an integral input reactor). Output line reactors were sized based on the VFD rated output currents.
    ⋆ 4% impedance.
    § Requires two output reactors wired in parallel.
    ♠ Requires three reactors wired in parallel.

    For details, refer to the PowerFlex 750-Series Technical Data.

    Certifications
    ABS (Frames 2…8, 400/480V AC) American Bureau of Shipping Certificate 11-HS743429-PDA
    C-Tick Australian Communications and Media Authority
    In conformity with the following:
        Radiocommunications Act: 1992
        Radiocommunications Standard: 2008
        Radiocommunications Labelling Notice: 2008
    Standards applied:
        EN 61800-3:2004
    c-UL-us Listed to UL508C and CAN/CSA-C22.2 No. 14-05.
    CE In conformity with the following European Directives:
        EMC Directive (2004/108/EC)
        Low Voltage Directive (2006/95/EC)
    Standards applied:
        EN 61800-3:2004
        EN 61800-5-1:2007
    EPRI/SEMI F47 Electric Power Research Institute
    Certified compliant with the following standards:
        SEMI F47
        IEC 61000-4-34
    GOST-R (Frames 2…8, 400/480V AC) Russian GOST-R Certificate no.
        POCC US.ME92.H00040
    Lloyds Register (Frames 2…8, 400/480V AC) Lloyd’s Register Type Approval Certificate 11/60008
    RINA (Frames 2…8, 400/480V AC) RINA Certificate ELE349811CS
    TÜV TÜV Rheinland
    Certification applies to 20-750-S and 20-750-S1 Safety Options when installed in drive.
    Standards applied:
        EN 61800-3:2004
        EN 61800-5-1:2007
        EN ISO 13849-1:2008
        EN ISO 13849-2:2003
        EN 61800-5-2:2007
        EN 61508 PARTS 1-7:2000
        EN 62061:2005
        EN 60204-1:2006

    Environmental Specifications
    Category Specification
    Altitude:
        Based on Load:
        Based on Voltage:

    Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001) for Derating Guidelines.
    System & Ground Configuration
    Center Grounded (Y Neutral) w/Solid Ground


    Ungrounded, Impedance Grounded, or Corner Grounded
    Overvoltage Category (1)
    II (2)
    III (3)

    II (2)
    III (3)
    Altitude Limit at 400/480V AC (2) (5)
    9000 m above sea level (3)
    4800 m above sea level

    4800 m above sea level
    2000 m above sea level
    Altitude Limit at 600V AC (2) (5)
    7500 m above sea level (3)
    4800 m above sea level

    7500 m above sea level (3)
    4800 m above sea level
    Altitude Limit at 690V AC (2) (5)
    7500 m above sea level (3)
    4800 m above sea level

    4800 m above sea level
    2000 m above sea level
    Notes: Based on EN61800-5-1 (Electro-thermal Safety Standard for drives)
    (1) Overvoltage Categories:
    Category II (Isolation Transformer Level) - Typically two levels of isolation or protection from outdoor power lines.
    Category III (Most Common) Distribution Level Inside a Building - Typically one level of isolation or protection from outdoor power lines.

    (2) Excluding failure from cosmic radiation. Cosmic radiation will increase rate of IGBT malfunction at altitudes greater than 3000 m above sea level. Concrete walls and ceilings or concrete walls and large bottles of water overhead are examples of ways to shield against cosmic radiation.

    (3) Drive is limited to a maximum of 4800 m thermally. Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001) for Derating Guidelines.

    (4) In CE installations, Frame 1 does not support ungrounded or corner grounded configurations.

    (5) Frame 1 drives are limited to a maximum of 2000 m thermally. Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001) for Derating Guidelines.
    Maximum Surrounding Air Temperature






    Flange Mount, Front


    Flange Mount, Back/Heat Sink

    Stand-alone/Wall Mount
    IP20, NEMA/UL Open Type:
    IP00, NEMA/UL Open Type:
    IP20, NEMA/UL Type 1 (w/Hood):
    IP20, NEMA/UL Type 1 (w/Label):
    IP20, NEMA/UL Type 1 (MCC Cabinet):
    IP54, NEMA Type 12 (MCC Cabinet):

    IP20, NEMA/UL Open Type:
    IP00, NEMA/UL Open Type:

    IP66, NEMA/UL Type 4X:

    IP54, NEMA/UL Type 12:
    Frame 1…5, All Ratings:
    Frame 6…7, All Ratings:
    Frame 1…5, All Ratings:
    Frame 6…7, All Ratings:
    Frame 8…10, All Ratings:
    Frame 8…10, All Ratings:

    Frame 2…5, All Ratings:
    Frame 6…7, All Ratings:

    Frame 2…7, All Ratings:

    Frame 2…7, All Ratings:
    0…50 °C (32…122 °F)
    0…50 °C (32…122 °F)
    0…40 °C (32…104 °F)
    0…40 °C (32…104 °F)
    0…40 °C (32…104 °F)
    0…40 °C (32…104 °F)

    0…50 °C (32…122 °F)
    0…50 °C (32…122 °F)

    0…40 °C (32…104 °F)

    0…40 °C (32…104 °F)
    Storage Temperature (All Const.): -40…70 °C (-40…158 °F)
    Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
    UV Radiation The HIM and IP54, NEMA/UL Type 12 drive plastics are not UV rated.
    Relative Humidity: 5 to 95% non-condensing
    Shock: Operating
        Frame 1…6:
        Frame 7:
        Frame 8…10:

    15 g peak for 11 ms duration (±1.0 ms)
    10 g peak for 11 ms duration (±1.0 ms)
    Power Core – 10 g peak for 11 ms duration (±1.0 ms)
    in Cabinet w/Option Bay – 5 g peak for 11 ms duration (±1.0 ms)
    Packaged for Shipment
        Frame 1…2:
        Frame 3…4:
        Frame 5:
        Frame 6…10:

    381 mm (15 in.) drop height
    330 mm (13 in.) drop height
    305 mm (12 in.) drop height
    Meets International Safe Transit Association (ISTA) test procedure 2B
    Vibration: Operating
        Frame 1…2:
        Frame 3…5:
        Frame 6…7:
        Frame 8…10:

    1.000 mm (0.040 in.) displacement, 2 g peak
    1.000 mm (0.040 in.) displacement, 1.5 g peak
    1.000 mm (0.040 in.) displacement, 1 g peak
    Power Core, Drive in Cabinet w/Option Bay – 1.000 mm (0.040 in.) displacement, 1 g peak
    Packaged for Shipment - Sinusoidal Loose Load
        Frame 1…5:
        Frame 6…10:

    20.0 mm (0.8 in.) peak to peak, 2…5.186 Hz; 1.1 g peak from 5.186…20 Hz
    Meets ISTA 2B packaging standards
    Random Secured
        Frame 1…5:





        Frame 6…10:
    Frequency (Hz)/PSD (g2/Hz)
    1/0.00005
    4/0.01
    16/0.01
    40/0.001
    80/0.001
    200/0.00001
    Meets International Safe Transit Association (ISTA) test procedure 2B
    Required Airflow:
        Frame 1…2:
        Frame 3:
        Frame 4:
        Frame 5:
        Frame 6:
        Frame 7:
        Frame 8:
        Frame 9:
        Frame 10:
    Total Fan Air Flow
    0.024 CMS (50 CFM)
    0.038 CMS (80 CFM)
    0.151 CMS (320 CFM)
    0.245 CMS (520 CFM)
    0.238 CMS (504CFM)
    0.357 CMS (756 CFM)
    0.637 CMS (1350 CFM)
    1.274 CMS (2700 CFM)
    1.911 CMS (4050 CFM)
    Sound:
        Frame 1…2:
        Frame 3:
        Frame 4:
        Frame 5:
        Frame 6:
        Frame 7:
        Frame 8:
        Frame 9:
        Frame 10:
    Sound Level
    63 dB
    64 dB
    72 dB
    77 dB
    73 dB
    74 dB
    79 dB
    79 dB
    83 dB
    (Sound pressure is measured at 2 m)
    Surrounding Environment Pollution Degree
        Pollution Degree 1 & 2:
        Pollution Degree 3 & 4:

    All enclosures acceptable.
    Enclosure that meets or exceeds IP54, NEMA/UL Type 12 required.

    Technical Specifications
    Category Specification Motor Voltage
    380…400V 480V 600V 690V
    Protection AC Input Overvoltage Trip: 576V AC 576V AC 825V AC 825V AC
    AC Input Undervoltage Trip: 250V AC 300V AC 400V AC 400V AC
    Bus Overvoltage Trip: 815V DC 815V DC 1167V DC 1167V DC
    Bus Undervoltage Shutoff:
        Frames 1…7:
        Frames 8…10:

    200V DC
    400V DC

    200V DC
    400V DC

    200V DC (Frames 3…7)
    400V DC

    200V DC (Frames 6…7)
    400V DC
    Nominal Bus Voltage: 540V DC 648V DC 810V DC 932V DC
    Drive Overcurrent Trip
        Software Overcurrent Limit:
        Instantaneous Current Limit:
        Hardware Overcurrent Limit:

    200% of drive rated
    100% of 3 sec. rating (158…210%)
    143% of 3 sec. rating (215…287%)
    Line transients: up to 6000 volts peak per IEEE C62.41-1991
    Control Logic Noise Immunity: Showering arc transients up to 1500V peak
    Power Ride-Thru: 15 milliseconds at full load
    Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
    Ground Fault Trip: Phase-to-ground on drive output
    Short Circuit Trip: Phase-to-phase on drive output
    Electrical AC Input Voltage Tolerance: Refer to the PowerFlex 750-Series Technical Data (publication 750-TD001)
    Frequency Tolerance: 47…63 Hz
    Input Phases: Three-phase input provides full rating for all drives. Single-phase operation on Frames 1…7 provides up to 50% of rated current at 25 °C (77 °F) surrounding temperature. Single-phase operation is not recommended
    for Frames 8 and larger.
    DC Input Voltage Tolerance: ±10% of Nominal Bus Voltage (above)
    Displacement Power Factor: 0.98 across entire speed range
    DC Link Impedance: Greater than or equal to 5%
    Efficiency: 97.5% at rated amps, nominal line volts
    Maximum Short Circuit Rating: 200,000 Amps RMS symmetrical (20F & 20G drives only)
    Actual Short Circuit Rating: Determined by AIC rating of installed fuse/circuit breaker
    Drive to Motor Power Ratio
        Minimum:
        Maximum:

    Recommended not less than 1:2 ratio
    Recommended not greater than 2:1 ratio
    Brake IGBT Rating: 100% of motor rated torque
    Control POD Current Draw: 5A
    Battery: User installed CR1220 lithium coin cell battery provides power to the real time clock (optional, not supplied). Preserves the clock setting in the event power to the drive is lost or cycled. Approximate life is 4.5 years with dive unpowered, or lifetime if drive is powered.
    Control Method: Sine coded PWM with programmable carrier frequency. Ratings apply to all drives.
    Carrier Frequency
        Default Settings:


        Settings:


    Frame 1…4: 4 kHz
    Frame 5…10: 2 kHz

    Frame 1…6: 2, 4, 8, 12 kHz
    Frame 7: 2, 4, 8 kHz
    Frame 8…10: 2, 4 kHz
    Output Voltage Range: 0 to rated motor voltage
    Output Frequency Range: 0…325 Hz at 2 kHz carrier, 0…650 Hz at 4 kHz carrier
    Frequency Accuracy
        Digital Input:
        Analog Input:

    Within ±0.01% of set output frequency
    Within ±0.4% of maximum output frequency
    Frequency Control: Speed regulation - with Slip Compensation (V/Hz & Sensorless Vector modes)
    0.5% of base speed across 40:1 speed range, 40:1 operating range
    Speed Control: Without feedback (Flux Vector mode), 0.1% of base speed across 100:1 speed range, 120:1 operating range, 50 rad/sec bandwidth
    With feedback (Flux Vector mode), 0.001% of base speed across 100:1 speed range, 1000:1 operating range, 190 rad/sec bandwidth
    Torque Regulation: Without feedback (Flux Vector mode), ±5%, 600 rad/sec bandwidth
    With feedback (Flux Vector mode), ±2%, 2500 rad/sec bandwidth
    Selectable Motor Control: - Standard V/Hz with full custom capability
    - Sensorless Vector with full tuning
    - Flux Vector with and without a feedback device
    - Induction motor control
    - Surface mount permanent magnet motor control with encoder feedback (Frames 1…10)
    - Surface mount permanent magnet motor control without encoder feedback (Frames 1…7)
    - Internal permanent magnet motor control with encoder feedback (Frames 1…10)
    Stop Modes: Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold, Fast Braking, and Current Limit Stop.
    Accel/Decel: Two independently programmable accel and decel times. Each time may be programmed from 0 to 3600 seconds in 0.1 second increments (0 to motor nameplate speed).
    S Curve Time: Adjustable from 0 to 100% of ramp time (normal duty rating).
    Intermittent Overload:
        Light Duty (Frame 8…10 Only)
        Normal Duty

        Heavy Duty

    110% Overload capability for up to 1 minute out of 10 minutes
    110% Overload capability for up to 1 minute out of 10 minutes
    150% Overload capability for up to 3 seconds out of 60 seconds
    150% Overload capability for up to 1 minute out of 10 minutes
    180% Overload capability for up to 3 seconds out of 60 seconds
    Current Limit Capability: Proactive Current Limit programmable from 20 to 160% of rated output current. Independently programmable proportional and integral gain.
    Electronic Motor Overload Protection: Class 10 protection with speed sensitive response. Complies with N.E.C. Article 430. U.L. File E59272, volume 12.
      

    For detailed dimensions, refer to the PowerFlex 750-Series Technical Data.

    Dimensions are in mm (in.) - weights are in kg (lb)

    Click to enlarge - dim_outline


    IP00/IP20, NEMA/UL Type Open
    Frame H W D Weight
    1 400.5 (15.77) 110.0 (4.33) 211.0 (8.31) 6.00 (12.75)
    2 424.2 (16.70) 134.5 (5.30) 212.0 (8.35) 7.80 (17.2)
    3 454.0 (17.87) 190.0 (7.48) 212.0 (8.35) 11.80 (26.1)
    4 474.0 (18.66) 222.0 (8.74) 212.0 (8.35) 13.60 (30.0)
    5 550.0 (21.65) 270.0 (10.63) 212.0 (8.35) 20.40 (45.0)
    6 665.5 (26.20) 308.0 (12.13) 346.4 (13.64) 38.60 (85.0)
    7 881.5 (34.70) 430.0 (16.93) 349.6 (13.76) 72.60…108.90 (160.0…240.0)

    IP20, NEMA/UL Type 1, MCC Style Cabinet
    Frame H W D Weight
    8 2453.0 (96.60) 600.0 (23.60) 600.0 (23.60) or 800.0 (31.50) Refer to the PowerFlex 750-Series Technical Data
    8 w/Drive and Option Cabinet 2453.0 (96.60) 1200.0 (47.20) 600.0 (23.60) or 800.0 (31.50)
    9 2453.0 (96.60) 1200.0 (47.20) 600.0 (23.60) or 800.0 (31.50)
    9 w//Drive and Option Cabinet 2453.0 (96.60) 1800.0 (70.90) 800.0 (31.50)
    10 2453.0 (96.60) 1800.0 (70.90) 600.0 (23.60) or 800.0 (31.50)
    10 w//Drive and Option Cabinet - - -




    Click to enlarge - dim_outline_flng


    Flange Mount
    Frame H W D1 D2 Weight
    2 481.8 (18.97) 206.2 (8.12) 148.3 (5.84) 63.7 (2.51) Refer to the PowerFlex 750-Series Technical Data
    3 515.0 (20.28) 260.0 (10.24) 127.4 (5.02) 84.6 (3.33)
    4 535.0 (21.06) 292.0 (11.50) 127.4 (5.02) 84.6 (3.33)
    5 611.0 (24.06) 340.0 (13.39) 127.4 (5.02) 84.6 (3.33)
    6 665.5 (26.20) 308.0 (12.13) 208.4 (8.20) 138.0 (5.43)
    7 875.0 (34.45) 430.0 (16.93) 208.4 (8.20) 138.0 (5.43)




    Click to enlarge - dim_outline


    IP54, NEMA/UL Type 12
    Frame H W D Weight
    2 543.2 (21.39) 215.3 (8.48) 222.2 (8.75) Refer to the PowerFlex 750-Series Technical Data
    3 551.0 (21.69) 268.0 (10.55) 220.1 (8.67)
    4 571.0 (22.48) 300.0 (11.81) 220.1 (8.67)
    5 647.0 (25.47) 348.0 (13.70) 220.1 (8.67)
    6 1298.3 (51.11) 609.4 (23.99) 464.7 (18.30)
    7 1614.0 (63.54) 609.4 (23.99) 464.7 (18.30)

    IP54, NEMA Type 12, MCC Style Cabinet
    Frame H W D Weight
    8 2477.0 (97.50) 600.0 (23.60) 898.0 (35.40) Refer to the PowerFlex 750-Series Technical Data
    8 w/Drive and Option Cabinets 2477.0 (97.50) 1200.0 (47.20) 898.0 (35.40)
    9 2477.0 (97.50) 1200.0 (47.20) 898.0 (35.40)
    9 w//Drive and Option Cabinets 2477.0 (97.50) 1800.0 (70.90) 898.0 (35.40)
    10 2477.0 (97.50) 1800.0 (70.90) 898.0 (35.40)
    10 w//Drive and Option Cabinets 2477.0 (97.50) - 898.0 (35.40)

    IP00, NEMA/UL Open Type
    Frame H W D Weight
    8 2145.0 (84.45) 777.9 (30.63) 403.9 (15.90) Refer to the PowerFlex 750-Series Technical Data