Allen-Bradley Home

Protection Systems

General Resources



XM-123 Aeroderivative Module

Introduction Communication Inputs Tachometer Outputs Indicators
Single Conditioning Measured Parameters Data Buffers Alarms Relays Non-Volatile Configuration
Power Approvals Environmental Physical Ordering Instructions

Relays


Number:

  • Single on-board relay, two sets of contacts–DPDT (2 Form C)
  • Four additional relays when linked to an XM-441 Expansion Relay module, or:
  • Four virtual relays whose status can be used by remote Control Systems


Onboard Relay Rating:

  • Max. Voltage = 120 Vdc, 125 Vac
  • Max. Current = 3.5 A ¬ 
  • Min. Current = 0
  • Max. Power = 60 W, 62.5 VA
  • UL Rating: 120 Vac @ 0.5 Amps resistive; 110 Vdc @ 0.3 Amps resistive; 30 Vdc @ 1.0 Amps resistive


¬  Max current is up to 40°C, then derates to 2A at 65°C. For Expansion Relay Rating refer to XM441 Technical data sheet ENMON-TD441A-EN-P


Failsafe:

  • Normally energized (failsafe), or
  • Normally de-energized (non-fail-safe)


Latching:

  • Latching, or
  • Non-latching


Time Delay:

0 to 65 seconds in 10 millisecond increments


Voting Logic:

Single or paired "And" or "Or" logic applied to any alarms


Reset:

  • Local reset switch on top of module
  • Remote reset switch wired to terminal base
  • Digital reset command via serial or DeviceNet interface


Activation On:

  • Alarm Status
    • Normal
    • Alert
    • Danger
    • Disarm
  • Transducer Fault
  • Module Fault
  • Tachometer Fault