Allen-Bradley Home

Protection Systems

General Resources



XM-220 Dual Speed Module

Introduction Communication Indicators Inputs Outputs Single Conditioning Non-Volatile Configuration
Alarms Relays Power Approvals Environmental Physical Ordering Instructions

Inputs


2 Tachometer Inputs:

±25V (50V maximum peak to peak)

  • Eddy current transducer signals
  • Magnetic pickups
  • TTL output devices


Input Impedance:

120k ohms minimum


Speed/Frequency Range:

1 to 1,200,000 RPM

0.0167 to 20,000Hz



Speed Measurement Error:


1 to 240 RPM: ±0.2 RPM

241 to 12,000 RPM: ±2 RPM

12,001 to 20,400 RPM: ±5 RPM

20,401 to 120,000 RPM: ±20 RPM

120,001 to 360,000 RPM: ±50 RPM

360,001 to 1,200,000 RPM: ±160 RPM



Sensor Fault Detection:

  • Eddy Current Transducer—Bias voltage is compared with user defined fault limits
  • Magnetic pickups—A current source is available for biasing passive magnetic pickups to detect open or short circuits