Allen-Bradley Home

Protection Systems

General Resources



XM-320 Position Module

Introduction Communications Inputs Outputs Indicators
Measured Modes Data Buffer Alarms Relays Non-Volatile Configuration
Power Approvals Environmental Physical Ordering Informaton

Alarms


Number:

2 alarm and danger pairs


Operators:

  • Greater than
  • Less than
  • inside Range
  • Outside Range


Hysteresis:

User defined


Startup Inhibit/Set Point Multiplication:

  • Period: 0 to 1092 minutes in 0.1 min increments
  • Inhibit/multiplication function:
    • Multiply by 2
    • Multiply by 3
    • Disarm


Operation:

Setpoint inhibit/multiplication initiated by:

  • Front terminal SPM circuit closure
  • DeviceNet command


Setpoint Inhibit/Multiplication Terminated by:

  • Expired timer
  • Front terminal SPM circuit open
  • DeviceNet command