Click to enlarge - 360


360 Process Module

The XM®series from Rockwell Automation is the world’s first machine monitoring and protection system designed as a distributed network of modules deployed on an open standard industrial bus.

The XM-360 Process Module is an intelligent 6-channel general-purpose process monitor. It is a complete process monitoring system in a compact, easily installed, easily maintained package. The module can be configured to measure a DC voltage or a loop current input on each channel and will report both the data value, in engineering units, and the rate of change for each channel.

For applications where it is not possible to integrate XM® data directly via DeviceNet the XM-360 provides a standard 4-20mA output for each channel. And for applications requiring relays the XM-360 supports linking of up to two XM-441 Expansion Relay modules thereby providing a total capacity of up to 8 relays.

The XM-360 can operate stand alone, with no interface to higher-level control systems or interactive user interfaces. It can also be deployed on a standard or dedicated DeviceNet™ network where it can provide real-time data and status information to other XM® modules, PLC’s, DCS and Condition Monitoring Systems.

Configuration can be performed remotely via the DeviceNet™ network, or locally by a PC connected to the integral serial interface. For local configuration, a Serial Configuration Utility is packaged with every XM® measurement and relay module sold.



Specifications


Communications


DeviceNet

  • Standard DeviceNet protocol for all functions
    NOTE: The XM-120E uses only the DeviceNet protocol, not power. Module power is provided independently.
  • Available Electronic Data Sheet (EDS) file provides support by most Devicenet compliant systems
  • Baud rate automatically set by bus master to 125kb, 250kb or 500kb


Side Connector:

All XM measurement and relay modules include side connectors that allow interconnecting adjacent modules thereby simplifying the external wiring requirements. The Interconnect provides primary power, DeviceNet communication and the circuits necessary to support expansion modules such as the XM-441 Expansion Relay module.


Serial ¬ 

  • RS-232 via mini-connector
  • Baud rate auto baud to 19200 or 57600


¬ Local configuration via Serial Utility Program. Requires Serial Communications Cable.

Inputs


6 channels of:

  • DC voltage inputs
  • Loop current inputs


Isolation:

Up to 250 volts of isolation for each input


Sensitivity:

User configurable in software


Input Range:

User configurable per channel as:

  • 0 to 5 Volts
  • 0 to 10 Volts
  • 4 to 20mA
  • -5 to 5 Volts
  • 1 to 5 Volts
  • 0 to 20mA


Input Impedance:

  • 50 W current input
  • 1 MW voltage input

Outputs


4-20mA Outputs:

  • 2 isolated banks of 3 outputs each (one per channel)
  • 600 ohm max load
  • Accuracy: ±1% of full scale


Isolation

  • 250 volts

Indicators


8 LEDs:

  • Module Status - red/green
  • Network Status - red/green
  • Channel 1 Status - off/yellow/red
  • Channel 2 Status - off/yellow/red
  • Channel 3 Status - off/yellow/red
  • Channel 4 Status - off/yellow/red
  • Channel 5 Status - off/yellow/red
  • Channel 6 Status - off/yellow/red

Signal Conditioning


Low Pass Filter:

User configurable for the measurement and rate of change value from each channel


Resolution:

0.025% of input range

Measured Units
Temperature °F °C
Pressure PSI PA
IN Hg KPA
Mbar  
Flow CFM  
Acceleration m/s2 gSE
Current mA  
Frequency RPM CPM
Hz     
Displacement mm in
mm mil
Velocity ips mmps
Voltage V     
Angle Red Deg
Rev     
Other Percent (%)
Unspecified
  

Measured Parameters


Rate of Change:

  • Per minute
  • Updated once per second

Data Buffer


Trend Buffer

Stores a set of records containing measured parameters in response to a trigger event.

  • Trend Interval: 1 to 3600 seconds.
  • Trigger: The trend is saved when a specified relay actuates, or on command from an XM-440, host or controller.
  • Capacity: 170 to 2048 records depending on the number of parameters stored.

Alarms


Number:

12 alarm and danger pairs


Operators:

  • Greater than
  • Less than
  • Inside Range
  • Outside Range


Hysteresis:

User defined

Relays


Number:

  • Up to eight relays when linked to one or two XM-441 Expansion Relay module, or:
  • Eight virtual relays whose status can be used by remote Control Systems


For Expansion Relay Rating refer to XM-441 Technical data sheet ENMON-TD441A-EN-P.


Failsafe:

  • Normally energized (failsafe), or
  • Normally de-energized (non-fail-safe)


Latching:

  • Latching, or
  • Non-latching


Time Delay:

0 to 25.5 seconds in 100msec increments


Voting Logic:

Single or paired “And” or “Or” logic applied to any alarms


Reset:

  • Local reset switch on top of module
  • Digital reset command via serial or DeviceNet interface


Activation On:

  • Alarm Status
    • Normal
    • Alert
    • Danger
    • Disarm
  • Sensor Out Of Range
  • Module Fault

Non-Volatile Configuration

A copy of the module configuration is retained in nonvolatile memory from where it is read upon power up.¬ 

¬ The configuration stored in Non-Volatile memory can only be deleted by module-reset command sent via the serial interface, using the Serial Configuration Utility, or via DeviceNet from any compliant software application.





Power

Module 21.6 - 26.4Vdc
Consumption Max: 250mA
Heat Production Max: 6 Watts (20.5 BTU/hr)
  


Redundant Power: All XM Measurement and Relay modules support redundant power. Each module includes redundant power inputs on its terminal base.

Approvals

Click to enlarge - approval logos



CE, C-Tick, ODVA
SCA Class I, Div 2, Groups A,B,C
D
UL
EEX


Environmental

Environmental
Operating Temperature -20 to +65ºC (-4 to 149ºF)
Storage Temperature -40 to +85ºC (-40 to 185ºF)
Relative Humidity 95% non-condensing
  


Conformal Coating

All printed circuit boards are conformal coated:

  • Per material specifications MIL-I-46058C / IPC-CC-830
  • In accordance with IPC-A-610C

Physical

Dimensions:
Height 3.8in(97mm)
Width 3.7in(94mm)
Depth 3.7in(94mm)
  