Allen-Bradley Home

Protection Systems

General Resources



XM-360 Process Module

Introduction Communications Inputs Outputs Indicators Signal Conditioning
Measured Parameters Data Buffer Alarms Relays Non-Volatile Configuration Power
Approvals Environmental Physical Ordering Informaton

Relays


Number:

  • Up to eight relays when linked to one or two XM-441 Expansion Relay module, or:
  • Eight virtual relays whose status can be used by remote Control Systems


For Expansion Relay Rating refer to XM-441 Technical data sheet ENMON-TD441A-EN-P.


Failsafe:

  • Normally energized (failsafe), or
  • Normally de-energized (non-fail-safe)


Latching:

  • Latching, or
  • Non-latching


Time Delay:

0 to 25.5 seconds in 100msec increments


Voting Logic:

Single or paired “And” or “Or” logic applied to any alarms


Reset:

  • Local reset switch on top of module
  • Digital reset command via serial or DeviceNet interface


Activation On:

  • Alarm Status
    • Normal
    • Alert
    • Danger
    • Disarm
  • Sensor Out Of Range
  • Module Fault