Allen-Bradley Home

Protection Systems

General Resources



XM-360 Process Module

Introduction Communications Inputs Outputs Indicators Signal Conditioning
Measured Parameters Data Buffer Alarms Relays Non-Volatile Configuration Power
Approvals Environmental Physical Ordering Informaton

Inputs


6 channels of:

  • DC voltage inputs
  • Loop current inputs


Isolation:

Up to 250 volts of isolation for each input


Sensitivity:

User configurable in software


Input Range:

User configurable per channel as:

  • 0 to 5 Volts
  • 0 to 10 Volts
  • 4 to 20mA
  • -5 to 5 Volts
  • 1 to 5 Volts
  • 0 to 20mA


Input Impedance:

  • 50 W current input
  • 1 MW voltage input