Allen-Bradley Home

Protection Systems

General Resources



XM-361 & 362 Temperature Modules

Introduction Communications Measured Parameters Inputs Outputs Indicators
Signal Conditioning Data Buffer Alarms Relays Non-Volatile Configuration Power
Approvals Environmental Physical Ordering Informaton

Inputs


Supported Sensors

THERMOCOUPLE
  Min °C Max °C
B 0 1810
C 0 1316
E 5 284
J 0 364
K -40 484
N -40 620
R -40 1760
S -40 1760
T -40 379
RTD (XM-361 ONLY)
  Min °C Max °C
100 Pt 385 -40 660
100 Pt 392 -40 660
200 Pt 385 -40 453
200 Pt 392 -40 443
120 Ni 672 -40 439
100 Ni 618 -40 180
10 Cu 427 -40 260
  


XM-361
RTD Current Source Value
501mA ±1%
Common Mode Input Range: ±3 Volts
Input Impedance 1 M voltage input
  


XM-362
Isolation Up to 250 volts of isolation for each input