Alarm
Failsafe:
- Normally energized (failsafe), or
- Normally de-energized (non-fail-safe)
Latching:
- Latching, or
- Non-latching
Time Delay:
0 to 25.5 seconds in 100msec increments
Voting Logic:
Per relay, defined as "A out of B" where "B" is up to 16 alarms from any measurement module(s) on the bus and "A" is from 1 to "B"
Reset:
- Local reset switch on top of module
- Remote reset switch wired to terminal base
- Digital reset command via serial or DeviceNet interface
Activation On:
- Alarm Status
- Transducer Fault
- Module Fault
- Tachometer Fault
- Unknown ¬
¬ The Unknown state indicates that the alarm status is not known, which indicates that the (alarms) module is off line or is unreachable (network fault).
|