Motor Protection Breakers & Motor Circuit Protectors
Bulletin 140M - 40...315A
The Bulletin 140M Motor Protection Circuit Breaker
line has been expanded to provide motor protection up to 300 Hp
at 600V. This expanded line of Motor Protection Circuit Breakers
provides all necessary functions to meet global requirements for
motor branch circuit protection, including:
- Disconnecting means
- Branch-circuit short-circuit protection
- Overload protection
Bulletin 140M Motor Protection Circuit Breakers
can be used in combination with Allen-Bradley Bulletin 100 Contactors
to create compact and reliable two-component combination starters.
140U NFPA 79 Internal Rotary Operating Handle
Features:
- Global Approvals:
- UL 489 and IEC 60947-2 as Circuit Breakers
- UL 508 and IEC 60947-4 for Motor Overload Protection
- CE Marked
- Only Two Frame Sizes
- I Frame for motors up to 200 Hp
- K Frame for motors up to 300 Hp
- Adjustable Motor Current Ranges
- I Frame from 40…205 A
- K Frame from 160…315 A
- Adjustable Overload Trip Classes
- I Frame—5, 10, 15 or 20
- Trip Class 10 only with 140M-I8E-D20
- K Frame—10, 15, 20 or 30
- High Interrupting Rating
- 65 kA at 480V
- 35 kA at 600V
Dimensions |