| Overload Relays |
E1 Plus DeviceNet Communication Module
![]() |
INTEGRATED I/O
Integrated I/O allow simplification of the network architecture,
providing local connection of motor starter related inputs and
outputs.
STATUS INDICATORS
Network Status: Green/red LED indicates the status of the
network connection
OUT A: Amber LED that illuminates when the output contacts are commanded closed
IN 1 and 2: Amber LEDs illuminate when the user-connected device contact actuates
OPERATIONAL AND DIAGNOSTIC DATA
The DeviceNet module allows access to the following
information, allowing continual monitoring of machine
performance:
EXPANDED PROTECTION FUNCTIONS
The added protective functions provided by the DeviceNet
module increase the protection of motor and load. Additionally,
warning functions allow operations personnel to take action
when motor performance parameters exceed permissive limits
so that downtime can be avoided.
Overload Warning: By monitoring the percentage of thermal capacity utilization (TCU) signal of the E1 Plus overload relay, the DeviceNet module offers a setting range of 0…100% TCU.
Jam Protection: A quick response in taking a motor off-line in
the event of a mechanical jam reduces the potential for damage
to the motor and the power transmission components. Trip
adjustments include a trip setting adjustable from 150…600%
FLA and a trip delay time with a range of 0.1…25.0 seconds. A
separate warning setting is adjustable from 100…600% FLA.
Underload Warning: A sudden reduction in motor operating current can signal an abnormal condition such as pump cavitation or drive belt breakage. The underload warning function offers a setting range of 30…100% FLA.