Bulletin Number 700-SE 700-SH 700-SC 700-SF 700-SA
Style Flat Pack Hockey Puck Miniature Ice Cube Socketed Square Base Socketed Tube Base Socketed
Key Features Panel/DIN mount, Low profile zero-cross AC switching option
Panel/DIN mount, High Current, protective cover, LED status, zero-cross AC switching options Compatible with 700-HN103, 104 or 128 socket, 700-AT1 or AT2 Timer, LED status and zero-cross AC switching options Compatible with 700-HN116 socket, LED status
zero-cross AC switching, Quick connect/disconnect terminals
Compatible with 700-HN100, 125, 202 and 108 socket, LED status, zero-cross AC switching, HT2 timing module
Load Type
AC
AC
AC
DC
AC
DC
AC
DC
Load Voltage Range 75 … 264V AC 19 …264V AC, 180 …528V AC 75 … 264V AC 3 … 52.8V DC,
3 … 125V DC
75 … 264V AC 3 … 52.8V DC 75 … 264V AC 3 … 125V DC
Maximum Load Current 20 A 40 A 3 A 3A @ 48V,
2 A @ 110 V
3 A 3 A 5 A 3 A
Maximum Leakage Current 5 mA @ 100V, 10 mA @ 200V 5 mA @ 100V,
10 mA @ 200V,
20 mA @ 400V
5 mA @ 100V AC, 10 mA @ 200V AC 5 mA @ 50V DC, 0.1mA
@ 100V DC
5 mA @ 100V AC, 10 mA @ 200V AC 5 mA @ 50V DC 5 mA @ 100V
10 mA @ 200V
5 mA @ 125V
Rated Control (input) Voltage 5, 12 or 24V DC 24VDC
100/110V AC,
200/220V AC
24V DC,
100/110V AC, 200/220V AC
4 … 24V DC
4 … 24V DC
24V DC
5 … 24V DC
24V DC
LED Indicator
No
Yes Yes (option) Yes (option)
for 48V DC
Yes Yes Yes Yes
Zero Cross Switching Yes (option) Yes Yes (option) N/A Yes (option) N/A Yes N/A
Mounting Method Panel without heat sink, Panel or DIN with heatsink Panel without heat sink, Panel or DIN with heat sink Panel or DIN with socket Panel or DIN with socket Panel or DIN with socket
Electrical Ratings
Dielectric Strength 2000V AC
50/60Hz 1 min.
2500V AC
50/60Hz 1 min.
1500V AC 50/60Hz 1 min. 1500V AC 50/60Hz 1 min. 1500V AC 50/60Hz 1 min.
Certifications cURus, CE, TUV cURus, CE1, TUV cURus, CE, VDE cURus, CE, VDE cURus, CE, VDE
Operating Ambient Temperature Range
-30 … 80C
-30 … 80C
-30 … 80C
-30 … 80C
-30 … 80C
1  200 … 480V AC load voltage range versions not CE.

SSR Output or SSR/Sensor Input
Bulletin Number
700-SK O or I
Style
Slim Line Socketed
Key Features
Compatible with 700-HN121 socket. Supports Input (sensor) module or Output (SSR) module
Load Type
AC
DC
AC
DC
 
Output (SSR) Module
Input (Sensor) Module
Load Voltage Range
75 … 264V AC
4 … 60V DC, 40 … 200V AC
Field Input: 60 … 264V AC
Field Input: 6 … 32V DC
Load Current
2 A
2 A @ 60V, 1.5 A @ 200V
Supply Current: 0.1 … 100 mA
Supply Current 0.1 … 00 mA
Maximum Leakage Current
1.5 mA
1 mA
5u A
5u A
Control (input) Voltage Range
5 … 24V DC
5 … 24V DC
5 … 24V DC
5 … 24V DC
 LED Indicator
Yes
Yes
Yes
Yes
 Zero Cross Switching
Yes (option)
N/A
No
N/A
 Mounting Method
Panel or DIN with socket
 Electrical Ratings
 Dielectric Strength
4000V AC 50/60Hz 1 min.
 Certifications
cURus, CE, TUV
 Max Ambient Temperature
-30 to 80C