Programmable Controllers

Programmable Logic Controllers

Pico Controllers

Counter Functions

Operating Hours Counter "O" for1760-L12, 1760-L18, and 1760-L20

The devices have four independent operating hours counters.

This operating hours counter enables you to record the operating hours of systems, machines and machine parts.

You can enter a setpoint within the valid value range 0...999999. This enables maintenance times to be monitored and reported.

The counter state is also retained when de-energized.

Note: The actual value can only be cleared via the Reset coil! Even operations such as the RUN -> STOP mode change, Voltage ON -> OFF, delete or modify program or delete new program do not delete the actual value of the operating hours counter.

Function

If the counter coil TO is set to 1, the counter increments its actual value every second by the value 1 (basic pulse: 1 second).

If the actual value reaches the setpoint of S, the contact O switches for as long as the actual value is greater than or equal to the setpoint.

The actual value is kept stored in the device until the Reset coil RO is set to 1 The actual value is then set to zero.

Accuracy of the operating hours counter

As the operating hours counter counts in seconds, up to 999 ms can be lost if a device is switched off.

Linking and Parameter Assignment of an Operating Hours Counter

Requirements: You have included a control relay in the project and have switched to Circuit Diagram View.

Activating an operating hours counter

Evaluation of an operating hours counter contact

If you wish to trigger a switching operation when a particular counter status is reached, you must also position the O0x operand that is programmed as a coil on a contact field. The contact switches if the actual value is greater than or equal to the setpoint.

Resetting an operating hours counter

Whether you position the function relay first of all in a coil field or contact field or whether you make the entries in the Parameters tab of a coil or a contact is not important. It is only important that you have selected the same function block number if you also want to configure the same function relay.

Circuit diagram elements and parameters

  Description Note
Function relay input
(setpoint)
S Setpoint Entry in hours

0...999999
The operating hours counter can thus count in the range from 0 hours to well over 100 years.
Contact
Oxx The contact switches if the actual value is greater than or equal to the setpoint.  
Coil function
Enable
possible via contactor function
Function as Enable coil:
On 1 the counter increments with a minute pulse.
0xx
Reset Function as Reset coil:
on 1 the counter actual value is reset.
ROxx
Operating mode
     
Parameter display
Call enabled The parameters can be viewed on the device.  
Simulation
     

Operand selection for the S input

Operand Description
Constant 999999