1760-L18, 1760-L20 Program Operation Functions

Master Reset "Z" for Pico

The devices provide three master reset function relays Z01...Z03.

The Master Reset function relay enables you to set with one command the status of the markers and all outputs to 0.

Depending on the operating mode set, it is possible to reset either the outputs only, the markers only or both.

The Master Reset function relay can be used in your circuit diagram both as a coil or as a contact (switch contact).

Function

A rising edge or the 1 status on the coil will reset the outputs or markers to 0, depending on the operating mode set. The location of the coil in the circuit diagram is of no importance. A master reset always has the highest priority. The contacts Z1 to Z3 follow the status of their own coil.

Linking and Parameter Assignment of a Master Reset Function Relay

Requirements: You have included a control relay in the project and have switched to Circuit Diagram View.

If you wish to check whether a function relay triggered as a coil has switched, you must link this function relay as a contact with the same operand number.

Whether you position the function relay first of all in a coil field or contact field or whether you make the entries in the Parameters tab of a coil or a contact is not important. It is only important that you have selected the same operand number if you also want to configure the same function relay.

Circuit diagram elements and parameters

  Description Note
Contact
Zxx Status 1 if coil Zxx detects a rising edge or status 1.  
Coil function
Trigger Coil The Master Reset function relay is started when it detects a rising edge (Trigger) or status 1 (Enable), when it then carries out the corresponding Reset operation. Zxx Triggered via one of the three coils available Z1...Z3. Use the Master reset function relay in one of the following operating modes.
Operating mode
Z1 The outputs Q1...Q8 and S1...S8 are reset to 0.  
Z2 The marker ranges M1...M16 and N1...N16 are reset to 0.  
Z3 Operates simultaneously on Q1...Q8, S1...S8, M1...M16 and N1...N16.  
Parameter display
- -  
Simulation
- -