| Network Supply Voltage |
11 to 25 DC |
| Node Current Consumption |
40 mA maximum |
| Power Consumption |
1 Watt maximum |
|
|
| Environmental |
| Operating Temperature |
0 to +50°C (32 to 122°F) |
| Storage Temperature |
-40 to +85°C (-40 to 185°F) |
| Relative Humidity |
0 to 95% non-condensing |
| Vibration |
1.0 G Operational
2.5 G Non-operational |
| Shock |
15.0 G Operational
30.0 G Non-operational |
| Altitude |
1,000 m (3,300 ft.) without derating |
| Communications |
| Baud Rates |
125, 250, 500 k BPS |
| Distance Maximum |
500 m (1640 ft.) @ 125 k BPS |
|
200 m (820 ft.) @ 250 k BPS |
|
100 m (328 ft.) @ 500 k BPS |
| Mechanical |
| Dimensions in Millimeters (inches) |
| Height |
67.54 (2.68) |
| Width |
70.0 (2.76) |
| Depth2 |
45.36 (1.79) |
|
1 Use this value to size the network current draw from the power supply. |