Allen-Bradley Home
Drives Service & Support

General Resources

  Drives Service & Support > 1336R > Specifications

Click for Dimensions

Electrical
AC Main Supply and Auxiliary Voltage 380-480VAC, 3Ø, +10%/ -15% Nominal 48-62Hz
  90-115VAC, 1Ø, ±10% Nominal
48-62Hz
Environmental
Ambient Operating Temperature IP00 (Open) 0-50°C
IP20 (NEMA Type 1) 0-40°C
Storage Temperature All Ratings -40 to +85°C
Relative Humidity 5-95% Non-Condensing
Shock 15g Peak for 11mSec. Duration (±1.0mSec.)
Vibration 0.152mm (0.0006 In.) Displacement, 1g Peak
ESD Susceptibility IP20 (NEMA Type 1) Only 15kV
Agency Certification
U.L. Listed
CSA Certified
Protection
AC Input Overvoltage Trip Factory Set to +15% of Nominal Line Voltage
Heatsink Over Temperature Trip 100°C
1336R Converter Overcurrent Trip
Software Overcurrent Limit Factory Set to 192% of AC Input Current
Hardware Overcurrent Limit Factory Set to 245% of AC Input Current
Line Transients Up to 6000 Volts Peak per ANSI C62.41-1991
Control Logic Noise Immunity Showering Arc Transients Up to 1500 Volts Peak
Power Ride-Thru 6 mSec. at Full Load
6 mSec. at Full Load 0.5 Sec. Minimum, 2 Sec. Typical

Regenerative DC Bus Supply Mode Only
  380VAC Input 480VAC Input
Bus Overvoltage Trip 670VDC 850VDC
Bus Undervoltage Trip 430VDC 520VDC
Nominal Bus Voltage 610VDC 735VDC

Heat Dissipation
Regenerative DC Bus Supply Operation Only - 380-480VAC Input
1336 REGEN Package Amp Rating Converter Converter Heatsink Precharge Unit 10% Line Reactor Power Line Filter Package Total
48A 141W 820W 15W 186W 173W 1335W
78A 193W 1110W 29W 258W 236W 1826W
180A 522W 2664W 58W 474W 317W 4035W
Regenerative Brake Operation Only - 380-480VAC Input
1336 REGEN Package Amp Rating Converter Converter Heatsink Precharge Unit 3% Line Reactor Package Total
48A 141W 656W 15W 65W 877W
78A 193W 888W 29W 84W 1194W
180A 522W 2131W 58W 168W 2879W