Fault Number: 20
Fault Display:
Load Loss Flt
Fault Name:
Load Loss Fault
Description:
[Load Loss Detect] is set to "Enabled" and the drive output torque current was below [Load Loss Level] for a time period greater than [Load Loss Time].
Corrective Action:
This is a user settable fault. The output current was lower than the percentage value programmed into parameter 291 (Load Loss Level) for longer than the time programmed into parameter 292 (Load Loss Time).

Change the parameters for parameter 291 or 292, or disable parameter 290 (Load Loss Detect). Also check the coupling or belting for proper fit and function.