Fault Number: 36
Fault Display: Diag C Lim Flt
Fault Name: Diagnostic Current Limit Fault
Description: The drive output current has exceeded the hardware current limit and the [Cur Lim Trip En] parameter was enabled.
Corrective Action: This fault can be turned off by using parameter 82 (Cur Lim Trip En). If parameter 82 is turned on, then the drive will trip on fault 36 instantaneously if the current limit of 180% of [Rated VT Amps] for B frame drives and approximately 250% of [Rated VT Amps] for A frame drives is hit.
As soon as the current draw reaches this point, this fault will occur immediately.
If this fault is disabled, and current limit reaches the above listed point, then the drives standard current limit routine will take over.
|