Allen-Bradley Home
Drives Service & Support

General Resources

 

Drives Service & Support > 1336T > Specifications

Click for Dimensions or Input/Output Ratings

Standard Drive Features

The Bulletin 1336 FORCE Field Oriented AC Drive is a microprocessor controlled Digital AC Drive with the following features:

  • 1 to 650 HP at 0 - 250 HZ constant torque
  • Four Quadrant operation available
  • High Performance Digital Velocity Loop
  • Microprocessor controlled, field oriented current loop
  • Simplified programming through the use of a Parameter Table that features data entries in engineering units with English descriptions
  • Nonvolatile Parameter Storage
  • Extensive diagnostics, including both logic board and power structure tests
  • Time stamped nonvolatile Fault/Warning Queue
  • Real Time Clock
  • Reference Time Stamp
  • Run Time Accumulator
  • Enclosed Construction
  • Multiple Communication Interfaces
  • Complete Encoder Interface
  • Drive to Drive Link
  • SCANport Peripheral Interface
Performance Specifications
  • Speed Regulation to 0.001% of top speed.
  • Torque Regulation to ± 5% of rated motor torque.
  • Power Loss Ride-Thru capability of two seconds.
  • Flying Start: Capability of starting into a spinning motor.
  • Torque Linearity 1%
  • Overload Capability: 150% for 1 minute, 200% of motor rating for 10 seconds, up to inverter limit.
  • Programmable Accel/Decel rates from 0 to 6553 seconds
  • Current limit programmable from 200% of rated output current.
Control Specifications Indirect Self-Organized, Field-Oriented Control, Current-regulated, sine coded PWM with programmable carrier frequency.
HP Drive Rating Carrier Frequency
1-3 4 1-12 kHz
7.5-30 4 1-12 kHz
40-60 4 1-12 kHz
75-125 2 1-6 kHz
150-250 2 1-6 kHz
300-500 2 1-4 kHz
600-650 2 1-4 kHz
700-800 1 1-4 kHz
Refer to Derating Guidelines in the Appendix of this manual
  • Output Voltage Range - 0 to rated voltage
  • Output Frequency Range - 0 to 250 Hz.
  • Speed Regulation with Encoder Feedback - 0.001% of Top Speed over a 100.1 Speed Range.
  • Encoderless Speed Regulation - 1% of Top Speed over a 40:1 Speed Range.
  • Accel/Decel - Independently programmable accel and decel times. Program from 0 to 6553 seconds in 0.1 second increments.
  • Current Limit - Independent Motoring and Regenerative Limit
  • Inverse Time Overload Capability - Class 20 protection with speed-sensitive response. Adjustable from 0-200% of rated output current in 3 speed ranges - 2:1, 4:1 & 10:1. UL Certified - Meets NEC Article 430.
Options
  • Standard Adapter Board which provides: - 2 Analog Inputs +/-10V - 2 Analog Outputs +/- 10V - One 4-20mA input - One 4-20mA output - 5 or 12 vdc pulse input - +/- 10V reference voltages - At Speed, Run, Fault and Alarm contacts
  • PLC Communication Adapter Board which provides: - 4 Analog Inputs +/-10V - 4 Analog Outputs +/- 10V - +/- 10V Reference voltages - RIO/DH? + Communications (2 channels selectable) - Function Blocks
  • DriveTools?; PC Windows? based programming software compatible with the 1336 FORCE Drive and also other Allen-Bradley 1336 and 1395 products.
  • Dynamic Braking
  • AC Motor Contactor
Protective Features
  • Programmable Motor Overload Protection (I 2 T) investigated by UL to comply with NEC Article 430.
  • Programmable Inverter Overload Protection (IT)
  • Overspeed Detection, even when operating as a torque follower.
  • Programmable Stall Detection
  • Peak output current monitoring to protect against excessive current at the output due to a phase to ground or phase to phase short.
  • Ground fault monitoring
  • DC Bus Voltage monitoring to protect against under/over voltage conditions.
  • Power Structure Heatsink Temperature Monitoring
Environmental Specifications

The following environmental guidelines apply to both the 1336 FORCE Drive and all devices and accessories connected to the Drive.

Ambient Operating Temperature:

  • IP00, Open: 0 to 50 degrees C (32 to 122 degrees F).
  • IP20, NEMA Type 1 Enclosed: 0 to 40 degrees C (32 to 104 degrees F).
  • IP65, NEMA Type 4 Enclosed: 0 to 40 degrees C (32 to 104 degrees F).
  • Storage Temperature (all constructions): -40 to 70 degrees C (-40 to 158 degrees F).

Relative Humidity: 5 - 95% non-condensing

Altitude: 1000m (3300 ft) without derating.

Shock: 15g peak for 11ms duration (+ 1.0 ms).

Vibration: 0.006 inches (0.152 mm) displacement. 1G peak.

Electrical Specifications

Input Voltage Rating:

  • 200 - 240VAC, Standalone, 3 Phase, +10%, -15% nominal
  • 380 - 480VAC, Standalone, 3 Phase, +10%, -15% nominal
  • 500 - 600VAC Standalone, 3 Phase, +10%, -15% nominal
  • 513 - 621 VDC, Common Bus, +10%, -15% nominal
  • 776 VDC, Common Bus, +10%, -15% nominal

Input Power Rating:

  • 2 - 134 KVA (230V)
  • 2 - 437 KVA (380V)
  • 2 - 555 KVA (460V)
  • 2/3 - 578/694 KVA (500/600V)

Input Frequency: 50/60HZ (±3HZ)

Standard Output Voltage*: Four frame sizes are available. Each frame size is line dependent and can power a motor between the following voltages:

  • 200 - 240 Vac (line dependent)
  • 380 - 480 Vac (line dependent)
  • 500 - 600 Vac (line dependent)

*If voltage required for your application is not shown, contact Allen-Bradley for specific application.

Output Current: 2.5 - 673A

Output Power:

  • 2 - 116 KVA (230V)
  • 2 - 190 KVA (380V)
  • 2 - 208 KVA (415V)
  • 2 - 537 KVA (460V)
  • 2 - 671 KVA (575V)

Note: For information on factors that could effect the power output of the drive please refer to the Enclosure and Derating Guidelines in the Appendix of this manual.

Output Horsepower (Continuous): 7.5 - 650HP

Overload Capability: Continuous - 100% Fundamental current 1 minute - 150%

Output Frequency Range: 0 - 250 HZ

Output Waveform: Sinusoidal (PWM)

Max. Short Circuit Current Rating : 200,000A rms symmetrical, 600 volts (when used with specified AC input line fuses as detailed in Table 2.A).

Ride Through: 2 seconds minimum

Efficiency: 97.5% at rated amps, nominal line volts

Feedback Devices Encoder: Incremental, dual channel; 12 volts, 500mA, Supply, 5/12 Volt 10ma Min Inputs, isolated with differential transmitter, 102.5 KHz max. Quadrature: 90° ±27° @ 25°C, Duty Cycle: 50% + 10%.

Speed Regulation with Encoder Feedback: 0.001% of Top Speed over a 100:1 Speed Range. Encoderless Speed Regulation: 0.5% of Top Speed over a 40:1 Speed Range.


Back to top