| Input Voltage and Frequency Ratings |
| Nominal Voltage |
207 to 253 VAC or 414 to 506 VAC (Horsepower-rated drives)
342 to 437 VAC or 374 VAC to 477 VAC (Current-rated drives) |
| Nominal Line Frequency |
50 or 60 cycles per second |
| Frequency Variation |
± 2 cycles of nominal |
| AC Line Fault Capacity |
| Allowable AC Line Symmetrical |
(See Power Ratings and Supply Capacity) |
| AC Line kVA |
| AC Line Distribution Capacity |
Maximum 3 drives per transformer |
| Minimum Source kVA |
(See Power Ratings and Supply Capacity) |
| DC Voltage Ratings |
| 230 VAC Line |
| Armature Voltage |
240 VDC |
| Field Voltage |
150 VDC |
| 460 VAC Line |
| Armature Voltage |
500 V DC |
| Field Voltage |
300 VDC |
| Service Factor Ratings |
| Service Factor |
1.0 Continuous |
| Overload Capacity (drive only) |
150% of full load rating for one minute |
| Minimum Load |
5% of rated load |
| Service Factor Ratings |
| Service Factor |
1.0 Continuous |
| Overload Capacity (drive only) |
150% of full load rating for one minute |
| Minimum Load |
5% of rated load |
| Service Conditions |
| Ambient Temperature |
| Chassis |
55°C (131°F) maximum |
| Cabinet |
40°C (104°F) maximum |
| Altitude |
| Chassis and Cabinet |
3300 feet above sea level |
| Above 3300 feet |
Derate 3% for every 1000 ft above 3300 ft up to 10000 ft. |
| Humidity |
| Chassis and Cabinet |
5 to 95% non-condensing |
| Environment |
The drive should be located in an area that is free of dust, dirt, acidic or caustic vapors, vibration and shock, temperature extremes, and electrical or electromagnetic noise interference. |