Drives Service & Support
| Consideration |
SynchLink |
Drive Communication |
Connecting
Cables |
(1) 200/230 micron HCS (Hard Clad Silica)
Versalink V-System
Lucent Technologies,
Specialty Fibers Technology Division |
(2)62.5/125 micron glass
One pair SC Style, one pair ST Style
Breakout Cables:
Belden 225362 or Mohawk M92021 |
Maximum
Cable Length |
300 meters with no more than one splice or one adapter |
300 meters with no more than one splice or one adapter |
Minimum
Cable Length |
1 meter |
1 meter |
Operating
Wavelength |
650 nm (Red) |
820 nm (InfraRed) |
| Data Rate |
5 Mbps |
10 Mbps |
Maximum
Node Count |
10 - Daisy Chain,
256 - Star Configuration |
1 - PMI Chassis |
(1) See page 1-3 for Allen-Bradley catalog numbers.
(2) See page 1-3 for Allen-Bradley catalog numbers.
| Module Location |
1756 ControlLogix Chassis |
| Backplane Current |
1.35A at 5.1V DC and 3.0mA at 24V DC |
| Maximum Power Dissipation |
6.96 W |
| Thermal Dissipation |
23.7 BTU/hr |
| Indicators |
Green and red indicators for operation, status, and diagnostics. |
| Operating Temperature |
0° to 60°C (32° to 140°F) |
| Storage Temperature |
-40° to 85°C (-40° to 185°F) |
| Relative Humidity |
5 to 95% non condensing |
| Operating Shock |
30g peak acceleration, 11 (±1 ms) pulse width |
| Non-Operating Shock |
50g peak acceleration, 11 (±1 ms) pulse width |
| Vibration |
Tested 2g at 10-500Hz per IEC 68-2-6 |
| Certifications |
Listed Industrial Control Equipment
Certified Process Control Equipment
Certified Class I, Division 2, Group A, B, C, D
Approved Class I, Division 2, Group A, B, C, D
Marked for all applicable directives
Marked for all applicable acts
|
|