| Status |
Cause |
Corrective Action |
| Off |
The adapter is not powered or is not connected properly to the drive. |
• Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive. |
Flashing
Red |
The adapter is not receiving a
ping message from the drive. |
• Verify that cables are securely connected.
• Cycle power to the drive. |
Solid
Red |
The drive has refused an I/O connection from the adapter.
Another DSI peripheral is using the same DSI port as the adapter. |
Important: Cycle power to the product after making the following correction: • Verify that all DSI cables are securely connected and not damaged. Replace cables if necessary. • Check the Events, replace the adapter with a compatible A-B branded product (22-COMM-P) |
Flashing
Green |
Not Used. |
Not Used. |
Solid
Green |
The adapter is properly connected and is communicating with the drive. |
No action required. |
| Solid Orange |
The adapter is booting. |
Wait until boot program has finished. |
| Flashing Orange |
The adapter is in flash mode (SW8 down). Possible application failure. |
• Wait until Firmware Update has been finished, then switch SW8 to 1. • Download Application code |
| Status |
Cause |
Corrective Action |
| Off |
The adapter is not powered. |
• Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive. |
Flashing
Red |
The adapter has faults
or a drive is missing in
Multi Drive mode. |
• Clear faults in the drive. • Disconnect additional DSI peripheral and cycle power to the drive. • If cycling power does not correct the problem, the parameter settings may have been corrupted. Reset defaults and reconfigure the module. • If resetting defaults does not correct the problem, flash the adapter with the latest firmware release. • For Multi-Drive mode, determine which drive is missing or faulted. Check cabling and configuration settings (see Configuring the RS-485 (DSI) Network section in
Chapter 7 of the manual). |
Solid
Red |
The adapter has failed the hardware test. |
• Cycle power to the drive. • Replace the adapter. |
Flashing
Green |
The adapter is operational, but is not transferring I/O data. |
• Place the scanner in RUN mode. • Program the controller to recognize and transmit I/O to the adapter. • Configure the adapter for the program in the controller. • Normal behavior if no DSI I/O is enabled. |
Solid
Green |
The adapter is operational and transferring I/O data. |
No Action. |
Not Used in Profibus Modules.