  Drives Service & Support > 22-COMM-P > LED Blink Codes

Number
Status Indicator
Description
1
DSI Connection Status
2
Adapter Status
3

NET A

Profibus Status
4
Not Used for Profibus

 

PORT Status Indicator

Status Cause Corrective Action
Off The adapter is not powered or is not connected properly to the drive. • Securely connect the adapter to the drive using the Internal Interface (ribbon) cable.
• Apply power to the drive.
Flashing
Red
The adapter is not receiving a
ping message from the drive.

• Verify that cables are securely connected.
• Cycle power to the drive.

Solid
Red

The drive has refused an I/O connection from the adapter.

Another DSI peripheral is using the same DSI port as the adapter.

Important: Cycle power to the product after making the following correction:

• Verify that all DSI cables are securely connected and not damaged. Replace cables if necessary.

• Check the Events, replace the adapter with a compatible A-B branded product (22-COMM-P)
Flashing
Green
Not Used. Not Used.
Solid
Green
The adapter is properly connected and is communicating with the drive. No action required.
Solid Orange The adapter is booting. Wait until boot program has finished.
Flashing Orange The adapter is in flash mode (SW8 down). Possible application failure. • Wait until Firmware Update has been finished, then switch SW8 to 1.
• Download Application code

Back to top

MOD Status Indicator

Status Cause Corrective Action
Off The adapter is not powered. • Securely connect the adapter to the drive using the Internal Interface (ribbon) cable.
• Apply power to the drive.
Flashing
Red
The adapter has faults
or a drive is missing in
Multi Drive mode.
• Clear faults in the drive.
• Disconnect additional DSI peripheral and cycle power to the drive.
• If cycling power does not correct the problem, the parameter settings may have been corrupted. Reset defaults and reconfigure the module.
• If resetting defaults does not correct the problem, flash the adapter with the latest firmware release.
• For Multi-Drive mode, determine which drive is missing or faulted. Check cabling and configuration settings (see Configuring the RS-485 (DSI) Network section in
Chapter 7 of the manual).
Solid
Red
The adapter has failed the hardware test. • Cycle power to the drive.
• Replace the adapter.
Flashing
Green
The adapter is operational, but is not transferring I/O data. • Place the scanner in RUN mode.
• Program the controller to recognize and transmit I/O to the adapter.
• Configure the adapter for the program in the controller.
• Normal behavior if no DSI I/O is enabled.
Solid
Green
The adapter is operational and transferring I/O data. No Action.

Back to top

Net A Status Indicator

Status Cause Corrective Action
Off The adapter is not powered
or is not connected
properly to the network or
the Node Address is
wrong.
• Securely connect the adapter to the drive using the Internal Interface cable and to the network using a Profibus cable.
(Screw D-shell to the adapter).
• Check the SW8 of DIP-Switches and set it to one - Normal operating state.
• Check the DIP-Switches (SW1~SW7) node address and the Scanner setting.
• Apply power to the drive.
Flashing
Red
Error in Profibus configuration. • Re-configure the Profibus module.
Solid
Red
Not Used. Not Used.
Flashing
Green
Not Used. Not Used.
Solid
Green
The adapter is properly connected and communicating on the network. No action required.

Back to top

Net B Status Indicator

Not Used in Profibus Modules.