Drives Service & Support
| General Specifications |
| Subject |
Specifications |
| AC Input Frequency Tolerance |
50/60Hz ±3Hz |
| AC Input Voltage Tolerance |
±10% |
| Overload Capability |
1 minute out of 20 minutes at rated load and temperature |
| Minimum Continuous Load Requirement |
33% of rated DC bus continuous current |
| Operating Altitude |
Up to 1000 meters (3,300 feet) † |
| Ambient Temperature (Operating) |
0 to 40°C (32 to 104°F) |
| Relative Humidity (Operating/Storage) |
5 to 95%, non-condensing |
| Ambient Temperature (Storage) |
-40 to 70°C (-40 to 158°F) |
| † For altitudes greater than 1000 meters, refer to the altitude derate chart. |

| Unit Specifications |
| The following specifications apply to the 1250, 1650, and 3000A DC drives with standard options. |
Specifications |
1250A Drive |
1650A Drive |
3000A Drive |
Height1 |
91.5”
(2324 mm) |
91.5”
(2324 mm) |
111.5”
(2832 mm)2 |
Width |
75” (1905 mm) |
75” (1905 mm) |
95” (2413 mm) |
Depth |
20” (508 mm) |
20” (508 mm) |
20” (508 mm) |
MCC Sections |
3 |
3 |
4 |
Shipping Weight |
2500 lbs (1134 kg) |
2500 lbs (1134 kg) |
3500 lbs (1588 kg) |
Operating Sound Level |
dB, wt. A |
83 dB, wt. A |
82 dB, wt. A |
| 1The height includes a 1.5"-high base channel. |
| 2The height for the 3000A unit includes the enclosure height (90"), the base channel (1.5"), and the tophat assembly (20"). The top hat assembly is shipped loose from the unit. |
| Electrical Specifications (1250A DC Drive) |
Input |
Output |
Nominal Input Voltage (V AC) |
Nominal Input Power (kVA) |
Nominal Armature Voltage
(V DC) |
Nominal Armature Current
(A DC) |
Maximum Field Voltage
(V DC) |
Maximum Field Current (A DC) |
Nominal HP |
460 |
750 |
500 |
1100 |
300 |
43 or 90 |
700 |
460 |
848 |
500 |
1250 |
300 |
43 or 90 |
750 |
575 |
856 |
600 |
1000 |
300 |
43 or 90 |
750 |
575 |
909 |
600 |
1065 |
300 |
43 or 90 |
800 |
575 |
1060 |
600 |
1250 |
300 |
43 or 90 |
900 |
660 |
852 |
700 |
860 |
300 |
43 or 90 |
750 |
660 |
904 |
700 |
915 |
300 |
43 or 90 |
800 |
660 |
1011 |
700 |
1030 |
300 |
43 or 90 |
900 |
660 |
1217 |
700 |
1250 |
300 |
43 or 90 |
1000 |
| Electrical Specifications (1650A DC Drive) |
Input |
Output |
Nominal Input Voltage (V AC) |
Nominal Input Power (kVA) |
Nominal Armature Voltage
(V DC) |
Nominal Armature Current
(A DC) |
Maximum Field Voltage
(V DC) |
Maximum Field Current (A DC) |
Nominal HP |
460 |
867 |
500 |
1280 |
300 |
43 or 90 |
800 |
460 |
972 |
500 |
1440 |
300 |
43 or 90 |
900 |
460 |
1108 |
500 |
1650 |
300 |
43 or 90 |
1000 |
575 |
1125 |
600 |
1330 |
300 |
43 or 90 |
1000 |
575 |
1385 |
600 |
1650 |
300 |
43 or 90 |
1250 |
660 |
1590 |
700 |
1650 |
300 |
43 or 90 |
1250 |
Electrical Specifications (3000A DC Drive) |
Input |
Output |
Nominal Input Voltage (V AC) |
Nominal Input Power (kVA) |
Nominal Armature Voltage
(V DC) |
Nominal Armature Current
(A DC) |
Maximum Field Voltage
(V DC) |
Maximum Field Current (A DC) |
Nominal HP |
460 |
1374 |
500 |
2000 |
300 |
43 or 90 |
1250 |
460 |
1634 |
500 |
2400 |
300 |
43 or 90 |
1500 |
460 |
2024 |
500 |
3000 |
300 |
43 or 90 |
1750 |
575 |
1713 |
600 |
1995 |
300 |
43 or 90 |
1500 |
575 |
1985 |
600 |
2330 |
300 |
43 or 90 |
1750 |
575 |
2254 |
600 |
2660 |
300 |
43 or 90 |
2000 |
575 |
2531 |
600 |
3000 |
300 |
43 or 90 |
2250 |
660 |
1705 |
700 |
1715 |
300 |
43 or 90 |
1500 |
660 |
1971 |
700 |
2000 |
300 |
43 or 90 |
1750 |
660 |
2242 |
700 |
2290 |
300 |
43 or 90 |
2000 |
660 |
2508 |
700 |
2575 |
300 |
43 or 90 |
2250 |
660 |
2905 |
700 |
3000 |
300 |
43 or 90 |
2500 |
The 1250, 1650, and 3000A DC drives dissipate power proportionally to the armature current, as shown in the following figures.



Back to top
|